142
-
'11 • P
A
C-T
-160
LED1
Yellow
*
Red
Black
White
TB1
N
L
1
2
3
Ri
t
°
Yellow/Green
Red
Orange
Gray
Brown
White
52X
T1
Si
T2
Ro2
T8
So2
T9
G1
T4
Ro3
T10
So3
T11
Ro1
T5
So1
T6
T22
T21
~
~
+
-
T24
C1
L1
T25
T26
T27
T28
T29
T30
CNG2
CNI2
CNI4
CNI3
CNW
CNB
CNIP
CNA1
THo-IPM
THo-A
THo-S
THo-D
THo-R1
THo-R2
CNJ
CNR
CH
20S
DH
M
EEVC
CNE
CNEEV1
EEVH
CNEEV2
FMo
CNFAN
CNS
CNN
OPTION
CNA2
63H1
CNW2
CNH
CNTH
CNI1
CNV
CNPS
LPT
CNG1
F3 250V 2A
F
250V 20A
F4 250V 2A
U
CM
V
W
CNO2
CNO
52
X
F6
F3
NOISE FILER PWB
INVERTER PWB
CONTROL PWB
PWB3
PWB2
PWB1
NOISE
FILER PWB
A/F MODULE
DIP-IPM
20A
SW PWB A
PWB4
SW PWB B
PWB4
CNQ2
CNQ1
Model FDC71VNX
●
Outdoor unit check points
Check items with the *mark when the power is ON.
LED1
Green
LED2
Red
Power supply check:
Measure the power supply at L.N.
(It is normal if it is AC 220-240V)
Noise filter check:
There should be continuity.
There should be no shorts between phase
Must be conductive.
When fuse is blown,
replace it or check wiring.
LED2(Red) check:
1~5 time flash : Refer to page 121
No anomaly like breakage,
swell, etc. allowed.
Voltage between terminals
When stopped : 280V ~ 373V
During operation : 380V ~ 390V
Fuse check:
There should be continuity.
If faulty, replace the control PCB
When the outdoor unit fan
motor is anomalous:
(Refer to page 186)
1
~
6 fimes flash
(Refer to page 121)
Must be conductive.
When blown, replace with F3 fuse.
Replace also fan motor.
LED1(Yellow) check:
DC Reactor continuity Check:
Max 25m
Ω
t
°
t
°
t
°
t
°
t
°
t
°
M
M
(9) Outdoor unit controller failure diagnosis circuit diagram