11. MAINTENANCE DATA
11.1 Diagnosing of microcomputer circuit
(1) Selfdiagnosis function
(a) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller error code,
indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
(i) Indoor unit
Remote controller
Indoor control PCB
Outdoor control PCB
Location of
trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
Red LED
Green
LED (1)
No-indication Stays OFF
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
—
• Normal operation
—
—
Stays OFF Stays OFF
2 times
flash
Stays OFF Indoor unit power
supply
• Power OFF, broken wire/blown fuse, broken transformer wire
Repair
155
*
3 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
Remote controller
wires
• Poor connection, breakage of remote controller wire * For wire breaking at power ON, the
LED is OFF.
Repair
156
Remote controller • Defective remote controller PCB
Replacement of
remote controller
WAIT
or
INSPECT I/U
Stays OFF
Keeps
flashing
2 times
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
157
•
158
Remote controller • Improper setting of master and slave by remote controller
Keeps
flashing
Stays OFF
*
Keeps
flashing Stays OFF
Keeps
flashing
Remote controller
wires (Noise)
•
Poor connection of remote controller signal wire (White)
•
Intrusion of noise in remote controller wire
* For wire breaking at power ON, the LED is OFF
Repair
163
Remote controller
indoor control PCB
*
• Defective remote controller or indoor control PCB (defective communication circuit)?
Replacement of
remote controller or
PCB
2 times
flash
Keeps
flashing
2 times
flash
Keeps
flashing
Indoor-outdoor
units connection
wire
•
Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•
Anomalous communication between indoor-outdoor units by noise, etc.
Repair
164
2 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
(Noise)
•
CPU-runaway on outdoor control PCB
Power reset or
Repair
Outdoor control
PCB
*
• Occurrence of defective outdoor control PCB on the way of power supply (defective com-
munication circuit)?
Replacement of
PCB
2 times
flash
Keeps
flashing Stays OFF Stays OFF
Outdoor control
PCB
•
Defective outdoor control PCB on the way of power supply
Replacement
Fuse
•
Blown fuse
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor heat
exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor
(defective element, bro-
ken wire, short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
165
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input
circuit)?
Replacement of
PCB
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor return air
temperature therm-
istor
•
Defective indoor return air temperature thermistor
(defective element, broken wire,
short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
166
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input
circuit)?
Replacement of
PCB
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Installation or oper-
ating condition
•
Heating over-load
(Anomalously high indoor heat exchanger temperature)
Repair
167
Indoor heat
exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor (short-circuit)
Replacement of
temperature therm-
istor
Indoor control PCB
*
•
Defective indoor control PCB
(Defective temperature thermistor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
Number of con-
nected indoor units
•
When multi-unit control by remote controller is performed, the number of
units is over
Repair
168
3 times
flash
Keeps
flashing Stays OFF
Keeps
flashing
Indoor unit No. set-
ting
•No master is assigned to slaves.
Repair
169
Rcmote controller wires •Anomalous remote controller wire connection, broken wire between master and slave units
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
Fan motor
•
Defective fan motor
Replacement, repair
170
Indoor control PCB •
Defective indoor control PCB
Replacement
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing Indoor control PCB •
Improper operation mode setting
Repair
171
1 time flash
Keeps
flashing Stays OFF
Keeps
flashing
Fan motor
Indoor fan motor rotation speed anomaly
Replace fan motor
and power PCB
172
Indoor control PCB
Defective indoor control PCB
Stays OFF
Keeps
flashing Stays OFF
Keeps
flashing
Remote controller
temperature therm-
istor
• Broken wire of remote controller temperature thermistor
Repair
173
Note (1)
Normal indicator lamp (Indoor, outdoor units: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps
flashing in any trouble other than anomalous CPU.
(2) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.