Graphic Operation Terminal F930GOT
Alarm Function 7
7-5
7.2
Operation when alarms have occurred
The figure below shows the outline of operation performed when alarms have occurred.
When a bit device assigned as an alarm device becomes ON (OFF
→
ON), the GOT recog-
nizes that an alarm has occurred.
When two or more alarms have occurred, the GOT recognizes them one by one in turn.
•
The ON/OFF status of alarm devices are read every time communication is performed (at
every 300 to 400 ms) between the GOT and the PLC when the FX-PCS-DU/WIN-E is used
or at the time interval (variable within the range of 600 to 100 ms) set by "Monitor Cycle" in
"Alarm History Common Setting" when the SW
o
D5C-GOTRE-PACK is used.
•
Inside the GOT, in accordance with the contents set preliminarily in the screen creation soft-
ware, alarm messages are displayed (overlaying on the user screen) or a specified screen
is displayed in the screen mode, then alarm devices are stored in the history and their fre-
quencies are counted in the alarm mode.
•
When two or more alarms have occurred, they are stored in the ascending order of alarm
device No. in the alarm list and stored in the alarm history in the order of occurrence.
When the SW
o
D5C-GOTRE-PACK is used, the alarm history can be stored in the order of
occurrence (from the oldest one) or in the reverse order of occurrence (from the latest one).
•
In the alarm history and the alarm frequency, up to the following number of cases can be
stored respectively. They are stored even if the power is turned off.
-
Alarm history: Up to 1,000 cases
If 1,001 or more alarms have occurred, the record is updated while excessive alarms are
deleted from the oldest one. (When the SW
o
D5C-GOTRE-PACK is used, it can be set
so that excessive alarms are deleted from the latest one.)
-
Alarm frequency: Up to 32,767 cases
Even if more alarms have occurred, 32,767 cases remain stored.
•
If an alarm has occurred in any mode other than the screen mode, the occurrence history
and the frequency are recorded. The display can be changed over to a specified screen,
and the alarm can be output to the printer. (However, the alarm message does not overlay
the base screen displayed at that time.)
Screen mode
Alarm 0
When many alarms have
occurred, corresponding
alarm messages are
displayed in the ascending
order of device No.
Instead of an alarm
message, a specified
screen can be displayed.
DISPLAY
STATUS
screen
Alarm 0
Alarm 3
Alarm mode
n
n+1
n+2
n+3
0
1
2
3
254
255
n+254
n+255
ALARM
HISTORY
screen
Alarm 0
Alarm 3
ALARM
FREQUENCY
screen
Alarm 01
Alarm 10
Alarm 20
The GOT monitors bit devices
in the PLC, and recognizes
that alarms have occurred
when they become ON.
(Communication is performed
at every 300 to 400 ms.)
n
n+1
n+2
n+3
n+254
n+255
ON
OFF
OFF
ON
Up to 256 consecutive
alarm devices
Sequence program
OFF
OFF
n+255
Output to the printer
(Alarm devices and alarm
messages are printed.)
GOT
PLC
Alarm
message
Device
No.
ON/OFF
status
Device
No.
n
Содержание F930GOT-BWD-E
Страница 1: ...USER S MANUAL F930GOT BWD E ...
Страница 4: ...Graphic Operation Terminal F930GOT ii ...
Страница 6: ...Graphic Operation Terminal F930GOT iv ...
Страница 14: ...vi ...
Страница 60: ...Graphic Operation Terminal F930GOT Start up 2 2 10 MEMO ...
Страница 68: ...Graphic Operation Terminal F930GOT Screen Mode 3 3 8 MEMO ...
Страница 120: ...Graphic Operation Terminal F930GOT Creation of Display Screens 8 8 30 ...
Страница 200: ...Graphic Operation Terminal F930GOT Changeover of Display Screen FX PCS DU WIN E 10 10 18 ...
Страница 272: ...Graphic Operation Terminal F930GOT Additional Functions in V 2 00 or later 13 13 24 MEMO ...