GOT-F900 SERIES (CONNECTION)
Connection of SLC500/MicroLogix Series PLC (Manufactured by Allen-Bradley) 19
19-6
19.4
Setting in MicroLogix
When directly connecting the MicroLogix CPU, the usage of the RS-232C port should be changed using
the peripheral equipment for the PLC (package software RSLogix500).
19.4.1
Communication Setting Specifications
Set the transmission specifications in the MicroLogix as shown in the table below. For the setting
method, refer to the manual of the MicroLogix Series.
Setting the RS-232C (channel 0) Parameters
DF1 Half-Duplex Slave Channel Configuration
Set the parameters in shaded boxes. Leave other parameters in default values.
19.4.2
GOT-F900 Transmission Specifications
- The specifications such as the transmission speed are fixed on the GOT-F900 side, and cannot be
changed.
Parameter
Set value
System Mode Driver
DF1 Half-Duplex Slave
Others
Leave them in default values.
Parameter
Set value
Node Address
0 to 31 (Align with the station number setting in the GOT)
Baud Rale
9600 bps
Parity
None
Duplicate Packet Delection
Enable
Error Delection
CRC
Poll Timeout
3000
RTS Off Delay
0
RTS Send Delay
0
Message Retries
3
Control Line
No Handshanking
EOT Suppression
No
Item
Set value
Transmission speed
9600 bps
Data format
Data bit
8 bits
Parity bit
Not provided
Stop bit
1 bit
Control method
Not provided
Содержание F920GOT-BBD-K-E
Страница 4: ...GOT F900 SERIES CONNECTION ii ...
Страница 6: ...GOT F900 SERIES CONNECTION iv ...
Страница 38: ...GOT F900 SERIES CONNECTION Outline 2 2 10 MEMO ...
Страница 70: ...GOT F900 SERIES CONNECTION Specifications 3 3 32 MEMO ...
Страница 102: ...GOT F900 SERIES CONNECTION Installation and Wiring of F920GOT K F930GOT K F940 W GOT 4 4 32 MEMO ...
Страница 230: ...GOT F900 SERIES CONNECTION Connection of MELSEC F FX Series PLC 8 8 26 MEMO ...
Страница 260: ...GOT F900 SERIES CONNECTION Connection of MELSEC A Series PLC 9 9 30 MEMO ...
Страница 290: ...GOT F900 SERIES CONNECTION Connection of MELSEC QnA Series PLC 10 10 30 MEMO ...
Страница 322: ...GOT F900 SERIES CONNECTION Connection of MELSEC Q Series PLC 11 11 32 MEMO ...
Страница 338: ...GOT F900 SERIES CONNECTION Connection of FX Series Positioning Unit FX 2N 10 20GM 12 12 16 MEMO ...
Страница 376: ...GOT F900 SERIES CONNECTION Connection of FREQROL S500 E500 A500 Inverter 13 13 38 MEMO ...
Страница 412: ...GOT F900 SERIES CONNECTION Connection of Microcomputer 14 14 36 MEMO ...
Страница 460: ...GOT F900 SERIES CONNECTION Connection of FLEX PC N Series PLC Manufactured by Fuji Electric 16 16 18 MEMO ...
Страница 478: ...GOT F900 SERIES CONNECTION Connection of Machine Controller CP9200SH PLC Manufactured by Yaskawa Electric 17 17 18 MEMO ...
Страница 500: ...GOT F900 SERIES CONNECTION Connection of FP Series PLC Manufactured by Matsushita Electric Works 18 18 22 MEMO ...
Страница 522: ...GOT F900 SERIES CONNECTION Connection of SLC500 MicroLogix Series PLC Manufactured by Allen Bradley 19 19 22 MEMO ...
Страница 546: ...GOT F900 SERIES CONNECTION Connection of SIMATIC S7 200 300 400 Series PLC Manufactured by Siemens AG 20 20 24 MEMO ...
Страница 554: ...GOT F900 SERIES CONNECTION Connection of Printer 21 21 8 MEMO ...
Страница 590: ...GOT F900 SERIES CONNECTION Appendix 23 23 24 MEMO ...
Страница 591: ......