Features
Options
Precautions
Motor
Connection
example
Standard
specs.
Outline
dimensions
Parameter
list
Parameter
descriptions
Protective
functions
IPM motor
control
Compatibility
W
arranty
Te
rminal connection
diagrams
T
erminal specs.
Operation panel
Parameter unit
FR Configurator
55
When setting parameters, refer to the instruction manual (applied) and understand instructions.
From the power consumption estimated value during
commercial power supply operation, the energy saving effect
by use of the inverter can be monitored/output.
The following provides the items that can be monitored by the power
saving monitor (
Pr. 52
,
Pr. 54
= "50").
(Only power saving and average power saving value can be output
to
Pr. 54
(terminal FM))
The following gives the items which can be monitored by the cumulative
power saving monitor (
Pr. 52
= "51").
(The cumulative power monitor data digit can be shifted to the right by the
number set in
Pr. 891 Cumulative power monitor digit shifted times
.)
The operation panel and parameter unit can be used to calibrate
the full scales of the terminals FM.
FM terminal calibration (
C0(Pr.900)
)
The terminal FM is preset to output pulses. By setting the
Calibration parameter C0 (Pr. 900)
, the meter connected to the
inverter can be calibrated by parameter setting without use of a
calibration resistor.
Using the pulse train output of the terminal FM, a digital display
can be provided by a digital counter. The monitor value is 1440
pulses/s output at the full-scale value of
Pr. 54 FM terminal function
selection
.
Not needed when the operation panel or parameter unit (FR-PU07) is
used for calibration. Use a calibration resistor when the indicator
(frequency meter) needs to be calibrated by a neighboring device
because the indicator is located far from the inverter. However, the
frequency meter needle may not deflect to full-scale if the calibration
resistor is connected. In this case, perform calibration using the
operation panel or parameter unit.
You can make the buzzer "beep" when you press key of the
parameter unit (FR-PU07).
892 to 899
Energy saving monitor
Pr.892 Load factor
Pr.893 Energy saving monitor reference (motor capacity)
Pr.894 Control selection during commercial power-supply operation
Pr.895 Power saving rate reference value
Pr.896 Power unit cost
Pr.897 Power saving monitor average time
Pr.898 Power saving cumulative monitor clear
Pr.899 Operation time rate (estimated value)
Energy
Saving
Monitor
Item
Description and Formula
Increments
Power
saving
Difference between the estimated value of
power necessary for commercial power supply
operation and the input power calculated by the
inverter
Power during commercial power supply
operation - input power monitor
0.01kW
Power
saving rate
Ratio of power saving on the assumption that
power during commercial power supply
operation is 100%
100
0.1%
Ratio of power saving on the assumption that
Pr. 893
is 100%
100
Power
saving
average
value
Average value of power saving amount per
hour during predetermined time
(Pr. 897)
0.01kWh
Power
saving rate
average
value
Ratio of average power saving value on the
assumption that the value during commercial
power supply operation is 100%
100
0.1%
Ratio of average power saving value on the
assumption that
Pr. 893
is 100%
100
Power
saving
charge
average
value
Power saving average value represented in
terms of charge
Power saving average value
Pr.896
0.01
Power saving
Power during commercial
power supply operation
Power saving
Pr.893
(Power saving
t)
Pr.897
(Power saving rate
t)
Pr.897
Power saving average value
Pr.893
Energy
Saving
Monitor
Item
Description and Formula
Increments
Power
saving
amount
Power saving is added up per hour.
(Power saving
t)
0.01kWh
Power cost
savings
Power saving amount represented in terms of
charge
Power saving amount
Pr.896
0.01
Annual
power
saving
amount
Estimated value of annual power saving
amount
24
365
0.01kWh
Annual
power cost
savings
Annual power saving amount represented in
terms of charge
Annual power saving amount
Pr.896
0.01
C0(900)
Adjustment of terminal FM (calibration)
C0(Pr.900) FM terminal calibration
C2(902) to C7(905),
C22(922) to C25(923)
Refer to the section about
Pr.125
C42(934) to C45(935)
Refer to the section about
Pr.127
990
Buzzer control of the operation panel
Pr.990 PU buzzer control
Pr.990
setting
Description
0
Without buzzer
1 (initial value)
With buzzer
Power saving amount
Operation time during
power saving totalization
Pr.899
100
8VDC
T2
T1
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with
Pr. 55
(frequency monitor)
Set with
Pr. 56
(current monitor)
(Digital indicator)
(-)
1440 pulses/s(+)
FM
SD
Indicator
1mA full-scale
analog meter
(-)
(+)
1mA
FM
SD
Calibration
resistor
∗
Содержание F720PJ-11KF
Страница 88: ...88 MEMO ...