When setting parameters, refer to the instruction manual (applied) and understand instructions.
Set the frequency where the motor starts running.
Set the deadband in the low-speed range to eliminate noise and
offset deviation when setting a frequency with analog input.
You can select the optimum output characteristic (V/F characteristic)
for the application and load characteristics.
Enabled only under V/F control.
You can set the frequency and acceleration/decelertion time for
jog operation. Jog operation can be performed from either the
outside or PU.
Can be used for conveyor positioning, test operation, etc.
The inverter output can be shut off by the MRS signal. The logic of
the MRS signal can also be selected.
When
Pr. 17
is set to "4", the MRS signal from external terminal
(output stop) can be changed to the normally closed (NC contact)
input, and the MRS signal from communication can be changed to
the normally open (NO contact) input.
13
Minimum motor rotation frequency
Pr.13 Starting frequency
14
V/F pattern matching applications
Pr.14 Load pattern selection
For constant-torque load (setting "0")
At or less than the base
frequency voltage, the output
voltage varies linearly with the
output frequency.
Set this value when driving the
load whose load torque is
constant if the speed varies, e.g.
conveyor, cart or roll drive.
For variable-torque load (setting "1",
initial value)
At or less than the base
frequency voltage, the output
voltage varies with the output
frequency in a square curve.
Set this value when driving the
load whose load torque varies in
proportion to the square of the
speed, e.g. fan or pump.
IPM
IPM
IPM
Output
frequency
(Hz)
Set
frequency
Output
frequency
∗
∗
Output from 0.01Hz
Time
60
Setting
range
Forward rotation
ON
0
Pr. 13
V/F
V/F
V/F
100%
Output voltage
Pr. 3 Base frequency
Output frequency (Hz)
Pr. 14
= 0
100%
Output voltage
Pr. 3 Base frequency
Output frequency (Hz)
Pr. 14
= 1
15, 16
Jog operation
Pr.15 Jog frequency
Pr.16 Jog acceleration/deceleration time
17
Logic selection of output stop signal
(MRS)
Pr.17 MRS input selection
18
Refer to the section about
Pr.1
19
Refer to the section about
Pr.3
20
Refer to the section about
Pr.7
Output frequency (Hz)
Pr. 20
Pr. 15 Jog frequency
setting range
Pr. 16
Forward
rotation
Reverse
rotation
ON
ON
ON
JOG signal
Forward rotation STF
Reverse rotation STR
Time
MRS signal
Time
STF (STR)
signal
The motor coasts to stop
ON
ON
Setting value "0"
Setting value "2"
(initial value)
Output stop
MRS
SD
Inverter
Output stop
MRS
SD
Inverter