background image

D700 QUICK START MANUAL 

7

14. If the machine must not be restarted when power is restored after 

a power failure, provide a magnetic contactor in the inverter’s input 
side and also make up a sequence which will not switch on the 
start signal. If the start signal (start switch) remains on after a power 
failure, the inverter will automatically restart as soon as the power is 
restored.

15. Instructions for overload operation When performing operation of 

frequent start/stop of the inverter, rise/fall in the temperature of 
the transistor element of the inverter will repeat due to a repeated 
flow of large current, shortening the life from thermal fatigue. Since 
thermal fatigue is related to the amount of current, the life can be 
increased by reducing current at locked condition, starting current, 
etc. Decreasing current may increase the life. However, decreasing 
current will result in insufficient torque and the inverter may not 
start. Therefore, choose the inverter which has enough allowance 
for current (up to 2 rank larger in capacity).

16. Make sure that the specifications and rating match the system 

requirements. (17) When the motor speed is unstable, due to 
change in the frequency setting signal caused by electromagnetic 
noises from the inverter, take the following measures while applying 
the motor speed by the analog signal.

•  Do not run the signal cables and power cables (inverter I/O cables) 

in parallel with each other and do not bundle them.

•  Run signal cables as far away as possible from power cables 

(inverter I/O cables).

•  Use shield cables as signal cables.
•  Install a ferrite core on the signal cable (Example: ZCAT3035-1330 

TDK).

6. FAILSAFE OF THE SYSTEM WHICH  

    USES THE INVERTER

When a fault occurs, the inverter trips to output a fault signal. However, 
a fault output signal may not be output at an inverter fault occurrence 
when the detection circuit or output circuit fails, etc. Although Mitsubishi 
assures best quality products, provide an interlock which uses inverter 
status output signals to prevent accidents such as damage to machine 
when the inverter fails for some reason and at the same time consider 
the system configuration where failsafe from outside the inverter, 
without using the inverter, is enabled even if the inverter fails.

1. Interlock method which uses the inverter status output signals By 

combining the inverter status output signals to provide an interlock 
as shown below, an inverter alarm can be detected.

No 

Interlock  Method Check 

Method Used 

Signals

1

Inverter protective

function operation

Operation check of an 

alarm contact Circuit error 

detection by negative logic

Fault output signal (ALM 

signal)

2

Inverter running 

status

Operation ready signal 

check

Operation ready signal 

(RY signal)

3

Inverter running 

status

Logic check of the start 

signal and running signal

Start signal (STF signal, 

STR signal) Running 

signal (RUN signal)

4

Inverter running 

status

Logic check of the start 

signal and output current

Start signal (STF signal, 

STR signal) Output 

current detection signal 

(Y12 signal)

Backup method outside the inverter 
Even if the interlock is provided by the inverter status signal, enough 
failsafe is not ensured depending on the failure status of the inverter 
itself. For example, even if the interlock is provided using the inverter 
fault output signal, start signal and RUN signal output, there is a case 
where a fault output signal is not output and RUN signal is kept output 
even if an inverter fault occurs. Provide a speed detector to detect 
the motor speed and current detector to detect the motor current and 
consider the backup system such as checking up as below according 
to the level of importance of the system.

•  Start signal and actual operation check Check the motor running 

and motor current while the start signal is input to the inverter 
by comparing the start signal to the inverter and detected speed 
of the speed detector or detected current of the current detector. 
Note that the motor current runs as the motor is running for the 
period until the motor stops since the inverter starts decelerating 
even if the start signal turns OFF. For the logic check, configure a 
sequence considering the inverter deceleration time. In addition, it 
is recommended to check the three-phase current when using the 
current detector.

•  Command speed and actual operation check Check if there is 

no gap between the actual speed and commanded speed by 
comparing the inverter speed command and detected speed of the 
speed detector.

7. PARAMETER LIST

For simple variable-speed operation of the inverter, the initial setting 
of the parameters may be used as they are. Set the necessary 
parameters to meet the load and operational specifications. Parameter 
setting, change and check can be made from the operation panel. For 
details of parameters, refer to the instruction manual.

NOTES
* indicates simple mode parameters.
•  The parameters surrounded by a black border in the table allow its 

setting to be changed during operation even if “0” (initial value) is set 
in Pr. 77 Parameter write selection.

Parameter 

Name 

Setting

Range

Initial Value

*0 

Torque boost 

0 to 30% 

6/4/3% *1

*1 

Maximum frequency 

0 to 120Hz  120Hz

*2 

Minimum frequency 

0 to 120Hz  0Hz

*3 

Base frequency 

0 to 400Hz  60Hz

*4

Multi-speed setting (high speed)

0 to 400Hz  60Hz

*5

Multi-speed setting (middle speed)

0 to 400Hz  30Hz

*6

Multi-speed setting (low speed)

0 to 400Hz

10Hz

*7 

Acceleration time 

0 to 3600s  5/10s *2

*8 

Deceleration time 

0 to 3600s  5/10s *2

*9 

Electronic thermal O/L relay 

0 to 500A

Rated inverter 

current

10

DC injection brake operation frequency

0 to 120Hz  3Hz

Power 

supply

Inverter

Undesirable current

MC2

MC1

Interloc

U

V

W

R/L1

S/L2

T/L3

IM

Inverter

Controller

System failure

To the alarm detection sensor

Sensor 

(speed, temperature, 

air volume, etc.)

MitsubishiElectric Automation, Inc.

Содержание D700

Страница 1: ...VARIABLE FREQUENCY DRIVE MODEL D700 QUICK START MANUAL MitsubishiElectric Automation Inc ...

Страница 2: ...TING PLATE 4 2 INSTALLATION OF THE INVERTER 4 2 1 PRODUCT CHECKING AND PARTS IDENTIFICATION 5 3 OUTLINE DIMENSION DRAWINGS 5 4 WIRING 6 5 PRECAUTIONS FOR USE OF THE INVERTER 6 6 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 7 7 PARAMETER LIST 7 8 OPERATION PANEL 10 MitsubishiElectric Automation Inc ...

Страница 3: ... Do not change the cooling fan while power is on It is dangerous to change the cooling fan while power is on Do not touch the printed circuit board with wet hands Otherwise you may get an electric shock When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering off Never touch the motor terminal etc right after powering off to prevent an electric s...

Страница 4: ...rminals deteriorating the insulation of the motor When parameter clear or all parameter clear is performed reset the required parameters before starting operations Each parameter returns to the initial value The inverter can be easily set for high speed operation Before changing its setting fully examine the performances of the motor and machine In addition to the inverter s holding function insta...

Страница 5: ...OTE Install the inverter on a strong surface securely and vertically with bolts Leave enough clearances and take cooling measures Avoid places where the inverter is subjected to direct sunlight high temperature and high humidity Install the inverter on a non combustible wall surface 3 OUTLINE DIMENSION DRAWINGS Single phase 110V class Inverter Type W W1 H H1 D FR D710W 008 68 2 68 56 2 20 128 5 04...

Страница 6: ...nd insulation and phase to phase insulation of the inverter output side before power on Especially for an old motor or use in hostile atmosphere securely check the motor insulation resistance etc 10 Do not use the inverter input side magnetic contactor to start stop the inverter Always use the start signal turn ON OFF STF STR signal to start stop the inverter 11 Across P and PR terminals connect o...

Страница 7: ...nning signal Start signal STF signal STR signal Running signal RUN signal 4 Inverter running status Logic check of the start signal and output current Start signal STF signal STR signal Output current detection signal Y12 signal Backup method outside the inverter Even if the interlock is provided by the inverter status signal enough failsafe is not ensured depending on the failure status of the in...

Страница 8: ...eference 0 to 500A Rated inverter current 57 Restart coasting time 0 0 1 to 5s 9999 9999 58 Restart cushion time 0 to 60s 1s 59 Remote function selection 0 1 2 3 0 Parameter Name Setting Range Initial Value 60 Energy saving control selection 0 9 0 0 9 0 65 Retry selection 0 to 5 0 66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz 67 Number of retries at fault occurrence 0 ...

Страница 9: ... speed 11 0 to 400Hz 9999 9999 236 Multi speed setting speed 12 0 to 400Hz 9999 9999 237 Multi speed setting speed 13 0 to 400Hz 9999 9999 238 Multi speed setting speed 14 0 to 400Hz 9999 9999 239 Multi speed setting speed 15 0 to 400Hz 9999 9999 240 Soft PWM operation selection 0 1 0 241 Analog input display unit switchover 0 1 1 244 Cooling fan operation selection 0 1 1 245 Rated slip 0 to 50 99...

Страница 10: ...18 FR D740 012 to 160 FR D720S 025 to 100 4 The parameter number in parentheses is the one for use with the operation panel FR PA02 02 for the FR E500 series or parameter unit FR PU04 FR PU07 5 The initial value differs according to the voltage class 200V class 400V class 6 Available only for the three phase power input specification model 8 OPERATION PANEL The operation panel cannot be removed fr...

Страница 11: ...operate with Setting Dial y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press and for 0 5s 3 Turn until appears refer to the table below for other settings 4 Press to set Flicker Parameter setting complete The monitor display appears after 3s Flickering Flickering Flickering Operation Panel Indication Operation Method Start command Frequency command External...

Страница 12: ...layed nor set n SETTING DIAL PUSH Push the setting dial to display the set frequency currently set Appears when PU operation mode or external PU combined operation mode 1 is selected Pr 79 3 y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press to choose the PU operation mode PU indication is lit 3 Press to choose the parameter setting mode PRM indication is l...

Страница 13: ...ernon Hills IL 60061 Ph 847 478 2100 Fx 847 478 2253 us MitsubishiElectric com fa en support January 2016 2016 Mitsubishi Electric Automation Inc Specifications subject to change without notice All rights reserved AZ IB 0600367ENG A MitsubishiElectric Automation Inc ...

Отзывы: