background image

Job Name: 

Location:

Drawing Reference: 

Schedule No.

System No.: 

Date:

•  R410A refrigerant

•  Seven sizes from 6,000 to 30,000 Btu/h

•  Powerful airflow (CFM)

•  Compact, lightweight, shiny-white, flat-panel design

•  Quiet operation

•  Multiple fan-speed settings

•  Intake grille filter is easily removed for cleaning

•  Built-in receiver is standard

Model:

 

PKFY-P12NHMU-E2

GENERAL FEATURES

SPECIFICATIONS

Capacity*

 

Cooling…………………………………………….…12,000 Btu/h

  Heating…………………………………………….…13,500 Btu/h

Power

  Power Source………………..........208 / 230V, 1-phase, 60Hz

Power Consumption

  Cooling…………………………………………….………0.03 kW

  Heating…………………………………………….………0.03 kW

Current

  Cooling……...................................................……………0.30 A

  Heating……...................................................……………0.30 A

Minimum Circuit Ampacity (MCA)……………….…..……...0.38 A

Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A

External Finish

……………...….………Munsell No. 1.0Y 9.2 / 0.2

External Dimensions

 

Inches………………………..11-5/8 H x 35-3/8 W x 9-13/16 D

 

mm………………………………………295 H x 898 W x 249 D

Net Weight

 

Unit………………..…...……………..................29 lbs. / 13 kg

Coil Type

………………...........................................….Cross Fin

(Aluminum Plate Fin and Copper Tube)

Fan

  Type x Quantity………………..…………...Line Flow Fan x 1

  Airflow Rate (Low-Mid-High)...…….……...........370 - 413 CFM

Motor

 

Type………..………..………..………..Direct-drive DC Motor

 

Output………..………..………..………..………..….0.030 kW

Air Filter

..…………………………….Polypropylene Honeycomb

Refrigerant Piping Dimensions

  Liquid (High Pressure)……............…1/4" / 6.35 mm (Flare)

  Gas (Low Pressure)………………..…1/2" / 12.7 mm (Flare)

Drainpipe Dimension

……............……...…….I.D. 5/8" / 16 mm

Sound Pressure Levels 

 

Low-Mid-High….…………….………..........……39 - 43 dB(A)

OPTIONS

 

 

□  External  Heat  Adapter……………………….…PAC-YU25HT

 

 

* Cooling / Heating capacity indicated at the maximum value at 

operation under the following conditions:

Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F 

(35°C) DB

Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB

Note:

 Ventilation air: Providing sufficient ventilation air is an impor-

tant part of every building design. ASHRAE Standard 62 provides 

the minimum ventilation air requirement. Also, check local codes. 

Notes:

•  IT Terminal plug

Отзывы: