![Mitsubishi Electric CITY MULTI PAC-AH001-1 Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/mitsubishi-electric/city-multi-pac-ah001-1/city-multi-pac-ah001-1_service-manual_238837040.webp)
8.3. Voltage test points
CND
F01
CNEC1
CNEC2
CN3A
CN2M
SW4
CN24-1
CN27 (CN24-2)
CN32
Indoor controller board
SW3
CN41
CN51
CN52
CN20
CN22
CN7V
CN4F
CN44
SWE
SW2
SW1
CN2A
CNXB2
CN30
CN60
F
M
N
C
SWA
F01
Fuse (AC 250V 6.3A)
CND
Power supply voltage (220 - 240VAC)
CN2M
For M-NET transmission cable
connection (24 - 30VDC)
SWE
Fan Forced ON
SW1
Mode selection
SW2
Capacity setting
SW3
Mode selection
SW4
Mode selection
SWA
Mode selection
CN2A
Analog input
CN32
Remote signal input
CN3A
For MA remote controller cable
connection
(10 - 13 VDC (Between 1 and 3))
CN30
Error signal input
CN52
Connect to indoor power board
CN51
To fan signal relay
CNXB2
To fan signal relay
CN41
No function
CN44
Thermistor (liquid/gas temperature)
CN20
Thermistor (Inlet air temperature)
CN22
Thermistor (Outlet air temperature)
CN4F
Float switch input
CN24-1
1st heater control
CN27
(CN24-2)
Damper control (2nd heater control)
CNMF
No function
CN60
LEV Control
CN7V
LEV Control
CNEC1
Connect to the indoor controller board
CNEC2
Operation Signal output
PAC-AH001-1
Specifications are subject to change without notice.
40
Содержание CITY MULTI PAC-AH001-1
Страница 1: ...AHU Controller PAC AH001 1 SERVICE MANUAL ...
Страница 2: ......
Страница 47: ...Specifications are subject to change without notice 47 ...