8. Troubleshooting
8.1. Check Methods
1. Component and check points
(1) Thermistor
• Return air thermistor (TH21)
• Liquid pipe thermistor (TH22)
• Gas pipe thermistor (TH23)
• Discharge air thermistor (TH24)
Rt: Thermistor Resistance [kΩ]
t: Thermistor Measurement Temperature [°C]
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C [50°F-86°F])
Normal
Abnormal
4.3kΩ - 9.6kΩ
Open or Short
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
• Room temperature thermistor (TH21)
• Liquid pipe thermistor (TH22)
• Gas pipe thermistor (TH23)
• Discharge air thermistor (TH24)
• Thermistor R0 = 15 kΩ±2.9%
• Multiplier of B = 3460 kΩ±1%
0°C
32°F
15kΩ
10°C
50°F
9.6kΩ
20°C
68°F
6.3kΩ
25°C
77°F
5.2kΩ
30°C
86°F
4.3kΩ
40°C
104°F
3.0kΩ
(A) Temperature [°C][°F]
(B) Resistance [kΩ]
(2) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
Normal
Abnormal
1-5
White-Red
2-6
Yellow-
Brown
3-5
Green-Red
4-6
Black-
Brown
Open or short
200 kΩ ± 10%
(A) Brown
(B) Red
(C) Black
(D) Green
(E) Yellow
(F) White
1) Summary of linear expansion valve (LEV) operation
• The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor
control board.
• The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
PAC-AH001-1
35
© 2017 Mitsubishi Electric US, Inc.
PAC-AH001-1
Specifications are subject to change without notice.
34