8 FUNCTIONS
8.2 Standard Input
73
8
8.2
Standard Input
This function inputs external signals. This function cannot be used in any modes other than the safety drive mode. All the
safety remote inputs (SA\X) are off in any modes other than the safety drive mode.
Unlike the safety input function, this function cannot use the input diagnostic function.
Standard input wiring selection function
Sets the standard single wiring function for input wiring.
Standard single wiring function
This function can connect input devices with single wiring.
Setting method
Set the input wiring selection in "Wiring selection of input" from the "Parameter of Slave Station" window of the engineering
tool.
For standard input, set "3: General single".
When "Wiring selection of input" Xn (n: even number) is set to "3: General single", do not set "1: Safety double
wiring (NC/NC)" for Xn+1. Likewise, when "3: General single" is set for Xn+1, do not set "1: Safety double
wiring (NC/NC)" for Xn.
(1) Safety remote I/O module
Item
Setting range
Wiring selection of input Xn
0: Not used
1: Safety double wiring (NC/NC)
2: Safety single
3: General single
(1)
NC
T0
X0