6 INSTALLATION AND WIRING
6.6 Wiring of External Device and I/O Terminal Block
53
6
Precautions for wiring the safety remote I/O module to safety
devices
When wiring the input part
■
Combination of input terminals for double input
For double input, the input terminals can be used only in the combinations shown below.
■
Combination of input terminals and test pulse output terminals
The test pulse output terminals and input terminals can be used only in the combinations shown below.
When wiring the output part
■
Combination of output terminals for double output
For double output, the output terminals can be used only in the combinations shown below.
Combination of input terminals for double input
X0, X1
X2, X3
X4, X5
X6, X7
(1) Safety remote I/O module
Combination of input terminals and test pulse output terminals
Test pulse output terminal
Input terminal
T0
X0, X2, X4, X6
T1
X1, X3, X5, X7
Combination of output terminals for double output
Y0, Y1
Y2, Y3
Y4, Y5
Y6, Y7
X2(-)
X0(-)
X1(-)
T1(+)
T0(+)
(1)