Fixing the IO-Link module
When fixing the IO-Link module, tighten all the two screws in the module fixing holes.
Otherwise, the module will be greatly affected by vibration, causing failure of the module.
When installing the module, tighten screws within the following torque range.
• Do not put oil on the screw. Failure to do so may damage the screw.
• Tighten the screw with an applicable screwdriver. Tightening it with an inapplicable screwdriver may
damage the screw.
Screw type
Tightening torque range
Module mounting screw (M6 screw)
4.90 to 5.20N
m
FG screw (M4 screw)
1.02 to 1.38N
m