CHAPTER 12 TROUBLESHOOTING
12
12.
2 Sy
mpt
o
m chec
kli
st
12.2
Symptom checklist
(1) CC-Link side
Symptom
Check item
Check method
Check
The data link is
failed in the
entire system.
Is the cable disconnected?
Check the condition of the cable visually or by line test.
Check Line status (SW0090).
Are the terminating resistors (110
)
connected to the stations on both ends?
Connect the terminating resistors included with the
master/local modules to the stations on both ends.
Is there an error in the CPU module of the
master station?
Check the error code of the CPU module and take
corrective actions.
Were the parameters set in the master
station?
Check the parameter settings.
• Remote network-Ver.2 mode or Remote network-
addition mode
• Ver.2 remote device station
• Double, Exclusive Station 4
Is Data link startup request (Yn6 or Yn8)
turned on?
Check the program.
Is there an error in the master station?
Check the following.
• Host parameter status (SW0068)
• Switch setting status (SW006A)
• Loading status (SW0069)
• Whether the ERR LED on the master station is
flashing or not.
Does the scan time exceed the maximum
value while the synchronous mode is
selected?
Select the asynchronous mode or reduce the
transmission speed.
The remote
input (RX) of the
NZ2AW1C1BY
cannot be
loaded.
Is the remote device station in the data link?
Check the status by the following methods.
• LED indication status of the module
• Other station data link status (SW0080 to SW0083)
Is the data being read from the correct
address of the remote input (RX)?
Check the program.
Was it set as a reserved station?
Check the parameters.
Is the same station number used for multiple
stations?
Check the station numbers.
The remote
output (RY) of
the
NZ2AW1C1BY
cannot be
turned on/off.
Is the remote device station in the data link?
Check the status by the following methods.
• LED indication status of the module
• Other station data link status (SW0080 to SW0083)
Is Refresh instruction (Yn0) of the master
station turned on?
Check the program.
Is the data being written to the correct
address of the remote output (RY)?
Check the program.
Was it set as a reserved station?
Check the parameters.
Is the same station number used for multiple
stations?
Check the station numbers.
The data of the
remote register
(RWr) of the
NZ2AW1C1BY
cannot be
loaded.
Is the remote device station in the data link?
Check the status by the following methods.
• LED indication status of the module
• Other station data link status (SW0080 to SW0083)
Is the data being read from the correct
address of the remote register (RWr)?
Check the program.
Was it set as a reserved station?
Check the parameters.
Is the same station number used for multiple
stations?
Check the station numbers.
Содержание CC-Link-AnyWire Bitty Bridge
Страница 1: ...CC Link AnyWire Bitty Bridge Module User s Manual NZ2AW1C1BY ...
Страница 2: ......
Страница 9: ...7 Memo ...
Страница 14: ...12 Memo ...
Страница 24: ...22 2 4 External Dimensions Unit mm 15 4 3 85 141 5 DIN rail 3 8 2 5 66 69 40 100 51 ...
Страница 53: ...51 CHAPTER 10 CC LINK I O RESPONSE TIME 10 Memo ...
Страница 73: ......