![Mitsubishi Electric CC-Link-AnyWire Bitty Bridge Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/mitsubishi-electric/cc-link-anywire-bitty-bridge/cc-link-anywire-bitty-bridge_user-manual_238824056.webp)
54
11.2.2
Bridge module to slave module (output)
The figure below shows the time between the bridge module remote device (RY) turning on/off and the slave module
output turning on/off.
Calculation formula
Processing time on the bridge module side +
Transmission cycle time
2 +
Signal delay time of the slave
module [ms]
Calculation example
Processing time on the bridge module side
Processing time of the NZ2AW1C1BY is 0.592ms. : 0.592[ms]
Transmission cycle time
2
Number of transmission points is set to 512 points: 10.2
2 = 20.4 [ms]
Signal delay time of the slave module
Signal delay time of the slave module is 0.01ms. : 0.01[ms]
Therefore, the transmission delay time is 0.592 + 20.4 + 0.01
21 [ms].
Slave module
NZ2AW1C1BY
Output
Ó
1- to 2-transmission cycle time
Ô
Signal delay time of the slave module
Input from
the CC-Link side
Ò
Processing time on the
bridge module side