5 INSTALLATION AND WIRING
5.6 Connecting Slave Module or Terminating Unit
35
5
5.6
Connecting Slave Module or Terminating Unit
Connection type
• The maximum transmission distance in the AnyWireASLINK stand-alone system is 200m, which is the total cable length
including the main line and branch line. (It varies depending on the wire diameter of the transmission cables (DP, DN) or the
transmission cable supply current.)
• Tree branch, T-branch, and multidrop connections are usable in the AnyWireASLINK system.
• Up to 256 slave modules can be connected to the NZ2AW1GNAL.
The total length of the transmission distance for the AnyWireASLINK system can be calculated from A + B +
C.
Note that the total length should not exceed the maximum transmission distance (total length).
Terminating unit
To ensure more stable transmission quality, connect a terminating unit to the end of a transmission cable (DP, DN).
Connection of terminating unit
Connect one terminating unit for each NZ2AW1GNAL at the far end from the NZ2AW1GNAL.
The number of connectable slave modules depends on the terminating unit used.
For details, refer to the following.
Manual of the terminating unit used (manufactured by Anywire Corporation)
(1) NZ2AW1GNAL
(2) Slave module
(3) Terminating unit
NZ2AW1GNAL
A
C
B
Slave
module
Slave
module
Slave
module
Slave
module
Tree branch
T branch
Multidrop
Terminating
unit
(2)
(1)
(2)
(2)
(3)
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......