APPX
Appendix 3 Remote Buffer Memory
153
A
Number of word data points setting per frame
■
Address
■
Description
Set the number of points to be stored in one frame of AnyWireASLINK transmission frame.
The word data use setting and the relationship between setting and setting value are as follows.
If Word data use setting (address: 0101H) is 0000H (Not use), set this setting to 0000H (Not use) also.
The settings that can be set differ depending on the word data use setting. The number of word points that exceeds the word
points setting cannot be set.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Number of word
data points per frame setting range error (error code: 1805H) is displayed. Also, the setting will not be reflected in the non-
volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
Startup operating mode setting
■
Address
■
Description
Set whether to acquire slave module information at start-up.
The relationship between setting and setting value is as follows.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Startup operation
mode setting range error (error code: 1806H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
Name
Address
Word data points setting per frame
0105H
Setting
Setting value
Not use
0000H (initial value)
2 words (input 1 word, output 1 word)
0001H
4 words (input 2 words, output 2 words)
0002H
8 words (input 4 words, output 4 words)
0003H
16 words (input 8 words, output 8 words)
0004H
32 words (input 16 words, output 16 words)
0005H
Name
Address
Startup operating mode setting
0107H
Setting
Setting value
Without slave module information acquisition
0000H (initial value)
With slave module information acquisition
0001H
Содержание AnyWire ASLINK
Страница 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Страница 2: ......
Страница 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Страница 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Страница 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Страница 193: ...APPX Appendix 8 External Dimensions 191 A Appendix 8 External Dimensions 43 86 16 8 102 3 6 3 4 0 2 Unit mm ...
Страница 199: ......