5.3 Connection of Terminating Resistor

The AJ65SBT2B-64DA stores the terminating resister of 110

so there 

is no need the external wiring

(1) Precautions

(a) Move the L TER. switch until it clicks.

(b) Make sure that between DA and DB is high resistance (when 

the L TER. switch is off) or is 110  (When the L TER. switch is 
on) with a tester before wiring the system with CC-Link 
dedicated cables.

(c) The built-in terminating resistor cannot be used in the following 

cases. Wire a terminating resistor (110 or 130 ).
 • A CC-Link system is configured using CC-Link cables of 

130 .

 • The AJ65SBT2B-64DA may be replaced during data link.

Click

Содержание AJ65SBT2B-64DA

Страница 1: ...sing the programmable controller 2008 MITSUBISHI ELECTRIC CORPORATION Digital Analog Converter Module Prior to use please read this and relevant manuals thoroughly to fully understand the product MODEL AJ65S 64DA U HW MODEL CODE 13JY75 IB NA 0800418 E 1612 MEE ...

Страница 2: ...RNING and CAUTION Please save this manual to make it accessible when required and always forward it to the end user Under some circumstances failure to observe the precautions given under CAUTION may lead to serious consequences Observe the precautions of both levels because they are important for personal and system safety Make sure that the end users read this manual and then keep the manual in ...

Страница 3: ...ion 3 4 1 Combinations of functions in each part in the User s Manual 2 Normal output may not be obtained due to malfunctions of output elements or the internal circuits For output signals that may cause a serious accident provide an external monitoring circuit CAUTION Do not install the control or communication cable s together with the main circuit or power cables Keep a distance of 100mm or mor...

Страница 4: ... switches do not remove the cushioning material before installation Securely fix the module with a DIN rail or mounting screws Tighten the screws within the specifiedtorque range Undertightening can cause drop of the screw short circuit or malfunction Overtightening can damage the screw and or module resulting in drop short circuit or malfunction Do not directly touch any conductive part of the mo...

Страница 5: ...screw comes loose resulting in failure Check the rated voltage and terminal layout and then wire the module correctly Connecting a power supply of a different voltage rating or incorrect wiring may cause a fire or failure Tighten terminal screws within the specified torque range A loose terminal screw may cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction ...

Страница 6: ...f the external power supply used by the system before cleaning or retightening the terminal screws Not doing so can cause the module to fail or malfunction Never disassemble or modify the module This may cause breakdowns malfunction injury and or fire Do not drop or apply any strong impact to the module Doing so may damage the module Be sure to shut off all phases of the external power supply used...

Страница 7: ... de main de veiller à ce que l utilisateur final l ait aussi à sa disposition Dans certaines circonstances le non respect d une précaution de sécurité introduite sous le titre ATTENTION peut avoir des conséquences graves Les précautions de ces deux niveaux doivent être observées dans leur intégralité car elles ont trait à la sécurité des personnes et aussi du système Veiller à ce que les utilisate...

Страница 8: ...el de l utilisateur du module correspondant 2 Le dysfonctionnement d un organe de sortie ou d un circuit interne peut entraîner l impossibilité d obtenir des sorties normales Prévoir un circuit de surveillance externe pour le suivi des signaux de sortie qui peuvent être à l origine d accidents ou incidents graves ATTENTION Ne pas installer le s câble s de commande ou de communication avec les câbl...

Страница 9: ... rembourrage avant l installation Fixer fermement le module avec un rail DIN ou avec des vis Serrer les vis dans les limites du couple de serrage prescrit Si les vis sont insuffisamment serrées le module risque de tomber et il peut y avoir des court circuits ou des dysfonctionnements Un serrage excessif peut endommager les vis et ou le module avec aussi un risque de chute de court circuits et de d...

Страница 10: ...n des bornes pour être sûr que le module sera câblé correctement Le raccordement d une alimentation de tension nominale différente ou toute erreur de câblage peuvent être à l origine d un départ de feu ou d une panne Serrer les vis de bornes dans les limites du couple de serrage prescrit Une vis de borne desserrée peut être à l origine d un court circuit ou d un dysfonctionnement Un serrage excess...

Страница 11: ...limentation externe utilisée par le système avant le nettoyage ou le resserrage des vis de bornes Faute de quoi il y a risque de panne ou de dysfonctionnement du module Ne jamais démonter ni modifier le module Cela pourrait être à l origine de pannes dysfonctionnement blessures et ou départ de feu Ne pas faire tomber le module ni le soumettre à de forts chocs Cela risquerait d endommager le module...

Страница 12: ...A 11 Précautions de mise au rebut ATTENTION Lors de sa mise au rebut ce produit doit être traité comme un déchet industriel ...

Страница 13: ...TENDED OR EXCLUDED BY INSTRUCTIONS PRECAUTIONS OR WARNING CONTAINED IN MITSUBISHI S USER INSTRUCTION AND OR SAFETY MANUALS TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT Prohibited Application Prohibited Applications include but not limited to the use of the PRODUCT in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could b...

Страница 14: ...ns provided that the usage of the PRODUCT is limited only for the specific applications agreed to by Mitsubishi and provided further that no special quality assurance or fail safe redundant or other safety features which exceed the general specifications of the PRODUCTs are required For details please contact the Mitsubishi representative in your region ...

Страница 15: ...ection 2 1 2 2 Dec 2011 IB NA 0800418 D SAFETY PRECAUTIONS Chinese Section 2 1 4 1 Dec 2016 IB NA 0800418 E SAFETY PRECAUTIONS French Section 2 2 Chapter 3 Section 4 1 5 1 5 2 6 2 Chapter 7 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving ind...

Страница 16: ...SETTINGS 6 3 1 Part names 6 4 LOADING AND INSTALLATION 9 4 1 Handling Precautions 9 5 DATA LINK CABLE WIRING 10 5 1 Wiring Precautions 10 5 2 CC Link Dedicated Cable Connection Method 10 5 3 Connection of Terminating Resistor 11 6 WIRING 12 6 1 Wiring Precautions 12 6 2 Wiring with External Devices 13 7 EXTERNAL DIMENSIONS 15 ...

Страница 17: ...e refer to one of the following manuals User s manual for the CPU module or head module used Safety Guidelines This manual is included with the CPU module base unit or head module The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives 2 Additional measures To ensure that this product maintains EMC and Low Voltage Directives please refer to o...

Страница 18: ...er s manual explains the specifications names of the components and wiring for the type AJ65SBT2B 64DA digital analog converter module hereafter AJ65SBT2B 64DA which are used as a remote device station of a CC Link system ...

Страница 19: ...idity Vibration resistance Compliant with JIS B 3502 and IEC 61131 2 Frequency Constant acceleration Half amplitude Sweep count Under intermittent vibration 5 to 8 4Hz 3 5mm 10 times each in X Y Z directions 8 4 to 150Hz 9 8m s2 Under continuous vibration 5 to 8 4Hz 1 75mm 8 4 to 150Hz 4 9m s2 Shock resistance Compliant with JIS B 3502 and IEC 61131 2 147 m s2 3 times each in 3 directions X Y Z Op...

Страница 20: ... 300V is 2500V 2 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used Pollution level 2 is when only non conductive pollution occurs A temporary conductivity caused by condensing must be expected occasionally 3 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitu...

Страница 21: ...n type Remote device station No of occupied stations 1 station Connection cable Câble de connexion CC Link dedicated cable Câble dédié pour CC Link Withstand voltage 500V AC for 1 minute across all power supply and communication system terminals and all analog output terminals Isolation system Between communication system terminals and all analog output terminals Photocoupler isolated Between powe...

Страница 22: ...8 points à montage direct M3 5 2 Couple de serrage 0 59 à 0 88 N m Borne sans soudure à utiliser 2 ou moins Applicable wire size Taille du fil à utiliser 0 3 to 2 0mm2 0 3 à 2 0 mm2 Applicable solderless terminal Borne sans soudure à utiliser RAV1 25 3 conforming to JIS C 2805 Applicable wire size 0 3 to 1 25mm2 V2 MS3 RAP2 3SL TGV2 3N Applicable wire size 1 25 to 2 0mm2 RAV1 25 3 conforme à la no...

Страница 23: ...6 3 PART NAMES AND SETTINGS 3 1 Part names This section explains the names of the components for the AJ65SBT2B 64DA Figure 3 1 Appearance of the AJ65SBT2B 64DA ...

Страница 24: ...he SELECT or center position L RUN LED On Normal communication Off Communication cutoff time expiration error L ERR LED On Flicker at fixed intervals Flicker at unfixed intervals Off Indicates that station number setting is outside the range Indicates that station number setting was changed from that at power on Indicates that you forgot fitting the terminating resistor or the module or CC Link de...

Страница 25: ...ber to 32 set the switches as indicated below Use prohibited Set all switches to off Terminal block Used to connect the module power supply transmission and analog I O signals DIN rail hook Used to mount the module to the DIN rail L TER Line Termination switch Turned ON to validate the terminating resistor stored in the AJ65SBT2B 64DA Used when the AJ65SBT2B 64DA is used on the network edge Table ...

Страница 26: ...itch of 200mm or less 3 When mounting the AJ65SBT2B 64DA to the DIN rail press with your finger the centerline of the DIN rail hook at the bottom of the module until it clicks Figure 4 1 Installation to DIN rail 4 Refer to the Master Module user s manual for the name specification and manufacturers of supported cables for the use with AJ65SBT2B 64DA Table 4 1 Tightening torque range Screw location...

Страница 27: ...ster module and a remote module with CC Link dedicated cables Le schéma ci dessous explique comment connecter un AJ65SBT2B 64DA à un module maître et à un module distant au moyen de câbles dédiées CC Link Figure 5 1 Connection of the CC Link dedicated cables English French Master module Module maître I O module etc Module d entrée sortie etc Terminating resistor Résistance d extrémité CC Link dedi...

Страница 28: ...that between DA and DB is high resistance when the L TER switch is off or is 110 When the L TER switch is on with a tester before wiring the system with CC Link dedicated cables c The built in terminating resistor cannot be used in the following cases Wire a terminating resistor 110 or 130 A CC Link system is configured using CC Link cables of 130 The AJ65SBT2B 64DA may be replaced during data lin...

Страница 29: ...Use separate cables for the AC control circuit and the external output signals of the AJ65SBT2B 64DA or the external power supply to avoid the influence of the AC side surges and induction 2 Do not mount the cables close to or bundle them with the main circuit line a high voltage cable or a load cable from other than the programmable controller This may increase the effects of noise surges and ind...

Страница 30: ... of the external device 1 Comme conducteur d alimentation utiliser un fil blindé 2 brins 2 S il y a un phénomène de bruit ou d ondulation sur le câblage externe raccorder un condensateur d une capacité de 0 1μF à 0 47μF tension de tenue de 25V ou plus sur la borne d entrée du dispositf externe English French D A conversion Conversion N A Filter Filtre Motor drive module etc Module d entraînement d...

Страница 31: ...teur d alimentation utiliser un fil blindé 2 brins 2 S il y a un phénomène de bruit ou d ondulation sur le câblage externe raccorder un condensateur d une capacité de 0 1μF à 0 47μF tension de tenue de 25V ou plus sur la borne d entrée du dispositf externe English French D A conversion Conversion N A Filter Filtre Motor drive module etc Module d entraînement du moteur etc Figure 6 2 Wiring for cur...

Страница 32: ...15 7 EXTERNAL DIMENSIONS The external dimensions of the AJ65SBT2B 64DA is shown below Unit mm DIN rail center 16 5 50 4 5 7 9 7 5 1 0 5 122 54 109 5 0 5 2 4 5 5 1 M4 ...

Страница 33: ...16 MEMO ...

Страница 34: ...17 MEMO ...

Страница 35: ...18 MEMO ...

Страница 36: ...No 12 Jakarta Pusat 10340 Indonesia Tel 62 21 3192 6461 MITSUBISHI ELECTRIC INDIA PVT LTD Pune Branch Emerald House EL 3 J Block M I D C Bhosari Pune 411026 Maharashtra India Tel 91 20 2710 2000 USA MITSUBISHI ELECTRIC AUTOMATION INC 500 Corporate Woods Parkway Vernon Hills IL 60061 U S A Tel 1 847 478 2100 Turkey Sales office Tel Country Region Sales office Tel Country Region Mexico MITSUBISHI EL...

Отзывы: