9
4. LOADING AND INSTALLATION
4.1 Handling Precautions
The following is an explanation of handling precautions of the
AJ65SBT2B-64DA.
(1) Tighten screws (such as a module fixing screw) within the
tightening torque range specified in the table below.
(2) When using the DIN rail, pay attention to the followings.
(a) Applicable DIN rail type (Compliant with IEC 60715)
TH35-7.5Fe
TH35-7.5Al
(b) DIN rail installation screw pitch
When installing a DIN rail, tighten the screws at a pitch of
200mm or less.
(3) When mounting the AJ65SBT2B-64DA to the DIN rail, press with
your finger the centerline of the DIN rail hook at the bottom of the
module until it clicks.
Figure 4.1 Installation to DIN rail
(4) Refer to the Master Module user's manual for the name,
specification, and manufacturers of supported cables for the use
with AJ65SBT2B-64DA.
Table 4.1 Tightening torque range
Screw location
Tightening torque range
Module fixing screw (M4 screw)
0.78 to 1.08N•m
Terminal block terminal screw (M3 screw)
Vis de borne sur plaque à bornes (vis M3)
0.59 to 0.88N•m
0,59 à 0,88 N•m
Terminal block installation screw (M3.5 screw)
0.68 to 0.98N•m
DIN rail
DIN rail hook