19
4.2 Mounting and installation
4.2.1 Cautions on handling
Cautions on handling the AJ65BT-RPI-10A/10B module are described
below.
(1) Tighten screws (such as a module fixing screw) within the
tightening torque range specified in the table below. Do not over-
tighten these screws. The screws and module case may be
damaged.
(2) When mounting the AJ65BT-RPI-10A/10B, it has no specific
mounting orientation as a module alone. However, it should be
mounted with its top face placed in the same orientation as that of
the mating module with which optical communication is made.
When these modules are mounted in opposite orientations, they
must be mounted more than 1m(3.28ft.) away from each other.
Screw location
Specified torque range
Module mounting screw (M6 thread with finished
circular flat washer)
1.2N•m
Display window mounting screw (M2.6 thread)
0.058N•m
Terminal block screw (M3 thread)
Vis de plaque à bornes (filetage M3)
0.59 to 0.88N•m
0,59 à 0,88 N•m
Terminal block mounting screw (M3.5 thread)
0.68 to 0.98N•m
More than 1m
(3.28ft.)away
0 to 100m
(0 to 327.87ft.)
[Top faces set in the opposite orientations]
[Top faces set in the same orientation]
Top face
Top face
Top face
Top face
Содержание AJ65BT-RPI-10A
Страница 52: ...37 MEMO ...
Страница 53: ......