(N) Operation via communication and its settings
50
• Faults history
• Model information monitor
NOTE
• When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF, HFFFF is returned.
C35 (928)
42118
Terminal 6 bias (torque)
Read/write
Analog value (%) set to
C35 (928)
43928
Terminal 6 bias (torque)
(terminal analog value)
Read
Analog value (%) of the voltage applied to terminal 6 of
the FR-A8AZ
C36 (929)
41929
Terminal 6 gain command (torque)
Read/write
C37 (929)
42119
Terminal 6 gain (torque)
Read/write
Analog value (%) set to
C37 (929)
43929
Terminal 6 gain (torque)
(terminal analog value)
Read
Analog value (%) of the voltage applied to terminal 6 of
the FR-A8AZ
C8 (930)
41930
Current output bias signal
Read/write
C9 (930)
42120
Current output bias current
Read/write
Analog value (%) set to
C9 (930)
C10 (931)
41931
Current output gain signal
Read/write
C11 (931)
42121
Current output gain current
Read/write
Analog value (%) set to
C11 (931)
C38 (932)
41932
Terminal 4 bias command (torque/
magnetic flux)
Read/write
C39 (932)
42122
Terminal 4 bias (torque/magnetic flux)
Read/write
Analog value (%) set to
C39 (932)
43932
Terminal 4 bias (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the current (voltage) applied to
terminal 4
C40 (933)
41933
Terminal 4 gain command (torque/
magnetic flux)
Read/write
C41 (933)
42123
Terminal 4 gain (torque/magnetic flux)
Read/write
Analog value (%) set to
C41 (933)
43933
Terminal 4 gain (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the current (voltage) applied to
terminal 4
C42 (934)
41934
PID display bias coefficient
Read/write
C43 (934)
42124
PID display bias analog value
Read/write
Analog value (%) set to
C43 (934)
43934
PID display bias analog value
(terminal analog value)
Read
Analog value (%) of the current (voltage) applied to
terminal 4
C44 (935)
41935
PID display gain coefficient
Read/write
C45 (935)
42125
PID display gain analog value
Read/write
Analog value (%) set to
C45 (935)
43935
PID display gain analog value
(terminal analog value)
Read
Analog value (%) of the current (voltage) applied to
terminal 4
1000 to
1999
45000 to
45359
Refer to the Instruction Manual
(Detailed) of the FR-A800/FR-F800
inverter for parameter names.
Read/write
The parameter 44000 is the register number.
Register
Definition
Read/write
Remarks
40501
Faults history 1
Read/write
Being 2 bytes in length, the data is stored as H00
.
Refer to the lowest 1 byte for the error code. (Refer to the list of
fault displays in the Instruction Manual (Detailed) of the FR-A800
inverter for error codes.)
Performing write using the register 40501 batch-clears the faults
history.
Set any value as data.
40502
Faults history 2
Read
40503
Faults history 3
Read
40504
Faults history 4
Read
40505
Faults history 5
Read
40506
Faults history 6
Read
40507
Faults history 7
Read
40508
Faults history 8
Read
Register
Definition
Read/write
Remarks
44001
Inverter type (1st and 2nd characters)
Read
The inverter type can be read in ASCII code.
H20 (blank code) is set for blank area.
Example) For the "FR-A840-E1 (FM type)",
H46, H52, H2D, H41, H38, H34, H30, H2D, H45, H31, H20...H20
44002
Inverter type (3rd and 4th characters)
Read
44003
Inverter type (5th and 6th characters)
Read
44004
Inverter type (7th and 8th characters)
Read
44005
Inverter type (9th and 10th characters)
Read
44006
Inverter type (11th and 12th characters)
Read
44007
Inverter type (13th and 14th characters)
Read
44008
Inverter type (15th and 16th characters)
Read
44009
Inverter type (17th and 18th characters)
Read
44010
Inverter type (19th and 20th characters)
Read
44011
Capacity (1st and 2nd characters)
Read
The capacity in the inverter model can be read in ASCII code.
Data is read in increments of 0.1 kW, and rounds down to 0.01 kW
increments.
H20 (blank code) is set for blank area.
Example) 0.75K..." 7"
(H20, H20, H20, H20, H20, H37)
44012
Capacity (3rd and 4th characters)
Read
44013
Capacity (5th and 6th characters)
Read
Pr.
Register
Parameter name
Read/write
Remarks