Causes and corrective actions
629
6 5
6.4
Causes and corrective actions
Error message
A message regarding operational troubles is displayed. Output is not shut off.
Abbreviation
LOCD
Name
Password locked
Description
Password function is active. Display and setting of parameters are restricted.
Check point
————
Corrective action
Enter the password in
Pr.297 Password lock/unlock
to unlock the password function before operating.
(Refer to
Abbreviation
Er1
Name
Parameter write error
Description
• Parameter setting was attempted while
Pr.77 Parameter write selection
is set to disable parameter write.
• Overlapping range has been set for the frequency jump.
• Overlapping range has been set for the adjustable 5 points V/F.
• The PU and inverter cannot make normal communication.
Check point
• Check the
Pr.77 Parameter write selection
setting. (Refer to
.)
• Check the settings of
Pr.31 to Pr.36 (frequency jump)
. (Refer to
.)
• Check the settings of
Pr.100 to Pr.109 (adjustable 5 points V/F)
. (Refer to
• Check the connection of PU and the inverter.
Abbreviation
Er2
Name
Write error during operation
Description
Parameter write was attempted while
Pr.77
= "0".
Check point
• Check that the inverter is stopped.
Corrective action
• After stopping the operation, make parameter setting.
• When setting
Pr.77
= "2", parameter write is enabled during operation. (Refer to
Abbreviation
Er3
Name
Calibration error
Description
Analog input bias and gain calibration values have been set too close.
Check point
Check the settings of
Pr.902, Pr.903, Pr.904, and Pr.905
(calibration functions). (Refer to
.)
Abbreviation
Er4
Name
Mode designation error
Description
• Parameter setting was attempted in the External or NET operation mode while
Pr.77
= "1".
• Parameter write was attempted when the command source is not at the operation panel.
Check point
• Check that operation mode is PU operation mode.
• Check that the
Pr.551
setting is correct.
Corrective action
• After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to
• When
Pr.77
= "2", parameter write is enabled regardless of the operation mode. (Refer to
.)
• Set
Pr.551
= "2". (Refer to
.)
Abbreviation
Er8
Name
USB memory device operation error
Description
• An operation command was given during the USB memory device operation.
• A copy operation (writing) was performed while the PLC function was in the RUN state.
• A copy operation was attempted for a password locked project.
Check point
• Check if the USB memory device is operating.
• Check if the PLC function is in the RUN state.
• Check if the project data is locked with a password.
Corrective action
• Perform the operation after the USB memory device operation is completed.
• Stop the PLC function. (Refer to
and the PLC function programming manual.)
• Unlock the password of the project data using FR Configurator2. (Refer to the Instruction Manuals of FR
Configurator2 and GX Works2.)