230
Communication operation and setting
[Fault data]
for details of fault description.
[Run command]
*1
The signal within parentheses is the initial setting. The description changes depending on the setting of
Pr. 180 to Pr. 184, Pr. 187 (input terminal
function selection) (page 122)
.
*2
The signal within parentheses is the initial setting. Since Jog operation/selection of automatic restart after instantaneous power failure/start self-
holding/reset cannot be controlled by the network, bit 8 to bit 11 are invalid in the initial status. When using bit 8 to bit 11, change the signals with
Pr. 185, Pr. 186, Pr. 188, Pr. 189 (input terminal function selection) (page 128)
. (Reset can be executed with the instruction code HFD.)
*3
Only forward rotation command and reverse rotation command are available for RS-485 communication using PU connector.
Item
Instruction
Code
Bit
Length
Description
Example
Run
command
HFA
8bit
b0: AU (current input selection)
*1 *3
b1: Forward rotation command
b2: Reverse rotation command
b3: RL (low speed operation
command)
*1 *3
b4: RM (middle speed operation
command)
*1 *3
b5: RH (high speed operation
command)
*1 *3
b6: RT (second function selection)
*1 *3
b7: MRS (output stop)
*1 *3
Run
command
(extended)
HF9
16bit
b0:AU (current input selection)
*1 *3
b1:Forward rotation command
b2:Reverse rotation command
b3:RL (low speed operation command)
*1 *3
b4:RM (middle speed operation
command)
*1 *3
b5: RH (high speed operation
command)
*1 *3
b6:RT (second function selection)
*1 *3
b7:MRS (output stop)
*1 *3
b8:JOG (Jog operation)
*2 *3
b9:CS (selection of automatic restart after
instantaneous power failure)
*2 *3
b10: STOP (start self-holding)
*2 *3
b11:RES (reset)
*2 *3
b12:
⎯
b13:
⎯
b14:
⎯
b15:
⎯
Data
Description
H00
No fault
H10
OC1
H11
OC2
H12
OC3
H20
OV1
H21
OV2
H22
OV3
H30
THT
H31
THM
H40
FIN
H50
IPF
H51
UVT
H52
ILF
H60
OLT
H70
BE
H80
GF
H81
LF
H90
OHT
H91
PTC
HA0
OPT
HA1
OP1
HA2
OP2
Data
Description
HB0
PE
HB1
PUE
HB2
RET
HB3
PE2
HC0
CPU
HC1
CTE
HC2
P24
HC4
CDO
HC5
IOH
HC6
SER
HC7
AIE
Data
Description
HE4
LCI
HE5
PCH
HE6
PID
HF1
E.1
HF2
E.2
HF5
E.5
HF6
E.6
HF7
E.7
HFD
E.13
Data
Description
Fault record display example
(instruction code H74)
For read data H30A0
(Previous fault ...... THT)
(Latest fault ...... OPT)
0
1
0
1 0 0 0 0
0
0
0
0
0
0
1
1
b15
b8 b7
b0
Latest fault
(HA0)
Previous fault
(H30)
0
0
0
0
0
0
1
0
b7
b0
[Example 1] H02 Forward rotation
[Example 2] H00 Stop
0
0
0
0
0
0
0
0
b7
b0
0
0
0
0
0
0
1
0
b0
[Example 1] H0002 Forward rotation
0
0
0
0
0
0
0
0
b15
0
0
0
0
0
0
0
0
b0
[Example 2] H0800 low speed operation
(When Pr. 189 RES terminal function selection is set to "0")
0
0
0
0
1
0
0
0
b15