3. I/O SIGNALS AND REMOTE REGISTER ASSIGNMENT
3.1 I/O Signals Transferred to/from the Master Module
The following table lists the I/O signals assigned to the GOT.
The I/O signals differ according to the set number of occupied stations (1
or 4 stations).
n in the table indicates the address assigned to the Master module by
station number setting.
Signal Direction : GOT Master module
Device No.
Signal name
Extension cyclic setting*
1
Single
Double
1 station
occupied
4 station
occupied
1 station
occupied
4 station
occupied
RXn0
to RXnF
RXn0
to RX(n+6)F
RXn0
to RXnF
RXn0
to RX(n+C)F
User area
RX(n+1)0
to RX(n+1)A
RX(n+7)0
to RX(n+7)A
RX(n+1)0
to RX(n+1)A
RX(n+D)0
to RX(n+D)A
Reserved
RX(n+1)B
RX(n+7)B
RX(n+1)B
RX(n+D)B
Remote READY
flag
*2
RX(n+1)C
to RX(n+1)F
RX(n+7)C
to RX(n+7)F
RX(n+1)C
to RX(n+1)F
RX(n+D)C
to RX(n+D)F
Reserved
Signal Direction : GOT Master module
Device No.
Signal name
Extension cyclic setting*
1
Quadruple
Octuple
1 station
occupied
4 station
occupied
1 station
occupied
4 station
occupied
RXn0
to RX(n+2)F
RXn0
to RX(n+1A)F
RXn0
to RX(n+6)F
RXn0
to RX(n+36)F
User area
RX(n+3)0
to RX(n+3)A
RX(n+1B)0
to RX(n+1B)A
RX(n+7)0
to RX(n+7)A
RX(n+37)0
to RX(n+37)A
Reserved
RX(n+3)B
RX(n+1B)B
RX(n+7)B
RX(n+37)B
Remote READY
flag
*2
RX(n+3)C
to RX(n+3)F
RX(n+1B)C
to RX(n+1B)F
RX(n+7)C
to RX(n+7)F
RX(n+37)C
to RX(n+37)F
Reserved