4 SYSTEM CONFIGURATION
4.1 Rules of System Configuration
51
4
Current consumption
Power of extension devices is supplied from the CPU module, powered input/output module or extension power supply
module.
The number of extension devices that can be connected must be determined from the capacity of the power supply.
For details on the current consumption, refer to
Page 59 Limitation on Current Consumption.
*1 Power is supplied to input circuit of input modules by 24 V DC service power supply or external power supply.
However, the DC power type does not have 24 V DC service power supply.
Limitations when using extension devices
■
Modules of extension connector type
FX5-CNV-IF is required to use modules of extension connector type.
■
Limitations on high-speed pulse input/output module
Up to four high-speed pulse input/output modules can be connected in a system.
■
Bus conversion module
• A bus conversion module is required to use FX3 extension module. FX3 extension module can be connected to the right
side of the bus conversion module only.
• For limitation on the number of connectable modules, refer to
Page 55 Connection to the bus conversion module
(connection with FX3 extension devices).
■
Limitations on intelligent function modules
Note that some intelligent function modules have limitations on the number of modules, order and combination in which they
are added for each individual module.
■
Using the extended extension cable
• The connector conversion adapter is required when the extended extension cable connection destination is a module of
extension cable type (except for FX5-1PSU-5V or extension power supply module).
• When connecting a bus conversion module in the same system, connect FX5-1PSU-5V or the powered input/output
module directly after the extended extension cable.
• This cannot be used with the FX3 extension module.
Model
Limitations
FX5-CCLIEF
Only one module may be connected per system.
FX5-CCL-MS
One module can be connected to the system for each station type.
• Master station: 1
• Intelligent device station: 1
When using the FX5-CCL-MS as the master station, it cannot be used together with the FX3U-16CCL-M.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together with the FX3U-64CCL.
FX5-ASL-M
Only one module may be connected per system.
Use together with the FX3U-128ASL-M is not possible.
FX3U-2HC
Up to two modules connectable per system.
When FX3U-1PSU-5V is not used, connect immediately after the bus conversion module.
FX3U-16CCL-M
Only one module may be connected per system.
When using the FX5-CCL-MS as the master station, it cannot be used together with the FX5-CCL-MS.
FX3U-64CCL
Only one module may be connected per system.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together with the FX5-CCL-MS.
FX3U-128ASL-M
Only one module may be connected per system.
Use together with the FX5-ASL-M is not possible.
Power supply from CPU module
*1
Power supply from
FX5 extension power supply module
*1
Power supply from
powered input/output module
*1
CPU module
Expansion
adapters
Expansion
board
FX5
Intelligent
module
FX5
Intelligent
module
FX5
Intelligent
module
FX3
Intelligent
module
FX5
extension
power
supply
module
Bus
conversion
module
Input
module,
Output
module
Input
module,
Output
module
Input
module,
Output
module
Powered
input/
output
module