6  WIRING

6.6  Output Wiring

127

6

Triac output

For output specifications of the terminal modules, refer to 

Page 197 Output specifications.

Handling of triac output

Output terminal

Four triac output points are covered by one common terminal. The common terminal blocks can drive loads of different circuit 
voltage systems (Example: 100 V AC and 24 V DC).

Insulation of circuit

The internal circuit and the output element (triac) are insulated with photothyristors.
The common blocks are separated from one another.

Display of operation

The LED turns on and the output triac is turned on when photothyristors are actuated.

Response time

The response time until the output triac is turned on after the photothyristors are actuated (or shut off) is 1 ms or less, and the 
response time until the output triac is turned off is 10 ms or less.

Output current

Current of 0.3 A can flow per one output point. However, current of four output points should be 0.8 A (average of 0.2 A per 
one point) to suppress temperature rise. When a load with a high rush current is frequently turned on or off, the mean-square 
current should be 0.2 A or less.

Open circuit leakage current

C-R absorbers are connected in parallel at the triac output terminal for turning off the triac. Thus, open circuit leakage currents 
of 1 mA/100 V AC or 2 mA/200 V AC occurs. Since the triac output type has open circuit leakage currents, even after the triac 
output is turned off, a small relay and a minute current load with low rated operation currents may continuously operate. 
Therefore, the load should be equal to or more than 0.4 VA/100 V AC or 1.6 VA/200 V AC. For loads lower than these values, 
connect the surge absorbers described later in parallel.

Load

100 V AC

U

Fuse

Y0

Y1

COM1

Load

200 V AC

U

Fuse

Y0
Y1

COM2

Terminal module

0.4 A

0.7 

seconds

4 A

10 

seconds

0.02 

seconds

0.02 + 0.7 + 10

4

2

 

 0.02 + 0.4

2

 

 0.7

= 0.2 A

<Example>

Содержание 09R536

Страница 1: ...MELSEC iQ F FX5U User s Manual Hardware ...

Страница 2: ......

Страница 3: ...tomatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machine operation in such a case Note that when an error occurs in a relay transistor or triac of an output circuit the output might stay on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed...

Страница 4: ...power supplies of the CPU module and extension modules If a long time power failure or an abnormal voltage drop occurs the PLC stops and output is turned off When the power supply is restored it will automatically restart when the RUN STOP RESET switch is on RUN side WARNING Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do s...

Страница 5: ...Connect the expansion board and expansion adapter securely to their designated connectors Loose connections may cause malfunctions Make sure to affix the expansion board with tapping screws Tightening torque should follow the specifications in the manual If the screws are tightened outside of the specified torque range poor connections may cause malfunctions Work carefully when using a screwdriver...

Страница 6: ...ic shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the ends of stranded wires and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the sp...

Страница 7: ...cut off all phases of the power supply externally Failure to do so in the power ON status may cause electric shock Before modifying the program in operation forcible output running or stopping the PLC read through this manual carefully and ensure complete safety An operation error may damage the machinery or cause accidents Do not change the program in the PLC from two or more peripheral equipment...

Страница 8: ...connector conversion adapter Extension modules bus conversion module and connector conversion module Battery CAUTION Construct an interlock circuit in the program so that the whole system always operates on the safe side before executing the control for data change of the PLC in operation Read the manual thoroughly and ensure complete safety before executing other controls for program change param...

Страница 9: ...This manual content specification etc may be changed without a notice for improvement The information in this manual has been carefully checked and is believed to be accurate however if you notice a doubtful point an error etc please contact the nearest Mitsubishi Electric representative When doing so please provide the manual number given at the end of this manual CAUTION When transporting the PL...

Страница 10: ...t in Analog Specifications 30 Analog input 30 Analog output 30 2 8 Communication Specifications 31 Built in Ethernet communication 31 Built in RS 485 communication 32 2 9 External Dimensions 33 CPU module 33 2 10 Terminal Layout 34 CHAPTER 3 PRODUCT LIST 37 3 1 Overall Configuration 37 3 2 CPU Module 38 3 3 Extension Module 39 I O Module 40 Intelligent Function Module 43 Extension Power Supply Mod...

Страница 11: ...8 Module number of Extension modules 78 CHAPTER 5 INSTALLATION 79 5 1 Installation Location 79 Installation location in enclosure 79 Spaces in enclosure 79 Layout in enclosure 80 5 2 Examination for Installation Method in Enclosure 81 5 3 Procedures for Installing on and Detaching from DIN Rail 82 Preparation for installation 82 Installation of CPU module 83 Installation of extension module extens...

Страница 12: ... of terminal modules 119 6 6 Output Wiring 121 Relay output 121 Transistor output 124 Triac output 127 Output wiring example 129 Output wiring examples of terminal modules 132 6 7 Analog Wiring 136 6 8 Examples of Wiring for Various Uses 137 Positioning function 137 Communication function 137 High speed counter 138 Interruption 142 Digital Switch 144 Input Matrix 146 Seven Segment with Latch 147 C...

Страница 13: ...166 APPENDIX 167 Appendix 1 How to Check the Date of Manufacture 167 Appendix 2 Standards 168 Certification of UL cUL standards 168 Compliance with EC directive CE Marking 168 Requirement for compliance with EMC directive 168 Requirement for compliance with LVD directive 169 Caution for compliance with EC Directive 170 Appendix 3 How to use analog inputs built in CPU module for current inputs 172 ...

Страница 14: ...utions for Battery Transportation 209 Control subject product 209 Precautions for transportation 209 Appendix 10Handling of Batteries and Devices with Built in Batteries in EU Member States 210 Disposal precautions 210 Exportation precautions 210 Appendix 11Added and Changed Functions 211 INDEX 212 REVISIONS 214 WARRANTY 215 TRADEMARKS 216 ...

Страница 15: ...13 CONTENTS ...

Страница 16: ...MELSEC iQ F FX5 User s Manual SLMP JY997D56001 Explains methods for the device that is communicating with the CPU module by SLMP to read and write the data of the CPU module MELSEC iQ F FX5 User s Manual CC Link IE JY997D64201 Describes CC Link IE field network module MELSEC iQ F FX5 User s Manual CC Link SH 081793ENG Describes CC Link system master intelligent device module MELSEC iQ F FX5 User s...

Страница 17: ...dules Input output modules Powered input output modules and High speed pulse input output modules Input module Generic term for Input modules extension cable type and Input modules extension connector type Input module extension cable type Generic term for FX5 8EX ES and FX5 16EX ES Input module extension connector type Generic term for FX5 C16EX D FX5 C16EX DS FX5 C32EX D and FX5 C32EX DS Output ...

Страница 18: ...nsion connector type Different name for FX5 CNV BUSC Connector conversion module extension cable type Different name for FX5 CNV IF Extended extension cable Generic term for FX5 30EC and FX5 65EC Connector conversion adapter Different name for FX5 CNV BC Battery Different name for FX3U 32BL SD memory card Generic term for NZ1MEM 2GBSD NZ1MEM 4GBSD NZ1MEM 8GBSD NZ1MEM 16GBSD L1MEM 2GBSD and L1MEM 4...

Страница 19: ...ed RD LED Lit when the CPU module is receiving data through built in RS 485 communication SD LED Lit when the CPU module is sending data through built in RS 485 communication SD RD LED Lit when the CPU module is sending or receiving data through built in Ethernet communication 7 Expansion board connector cover Cover for protecting expansion board connectors battery or others Connect the battery un...

Страница 20: ...h on the RESET side for approximately 1 second 4 SD memory card disable switch Switch for disabling access to the SD memory card when the card is to be removed 5 Built in analog I O terminal block Terminal block for using the built in analog function 6 SD memory card slot Slot for inserting an SD memory card 7 Expansion board connector Connector for connecting an expansion board 8 Extension connec...

Страница 21: ...adapter connector under the cover 2 Genuine product certification label Genuine product certification label to prevent counterfeiting 3 Nameplate The product model name Manufacturer s serial number power supply specifications and MAC address are shown 4 DIN rail mounting groove The module can be installed on DIN46277 rail 35 mm wide No Name Description 1 CPU module fixing screw hole Screw holes fo...

Страница 22: ...ower supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises Category applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V 10 This index indicates the degree to which conductive material is generate...

Страница 23: ...l AC power supply and ground terminal 1 5 kV AC for one minute 10 MΩ or higher by 500 V DC insulation resistance tester Between power supply terminal DC power supply and ground terminal 500 V AC for one minute Between 24 V DC service power supply connected to input terminal 24 V DC and ground terminal 500 V AC for one minute Between output terminal relay and ground terminal 1 5 kV AC for one minut...

Страница 24: ...r fuse FX5U 32M E 250 V 3 15 A Time lag fuse FX5U 64M E FX5U 80M E 250 V 5 A Time lag fuse Rush current FX5U 32M E 25 A max 5 ms or less 100 V AC 50 A max 5 ms or less 200 V AC FX5U 64M E FX5U 80M E 30 A max 5 ms or less 100 V AC 60 A max 5 ms or less 200 V AC Power consumption 1 FX5U 32M E 30 W FX5U 64M E 40 W FX5U 80M E 45 W 24 V DC service power supply capacity 2 FX5U 32M E 400 mA 300 mA 3 Supp...

Страница 25: ... of instantaneous power failure for 5 ms or less Power fuse FX5U 32M D 250 V 3 15 A Time lag fuse FX5U 64M D FX5U 80M D 250 V 5 A Time lag fuse Rush current FX5U 32M D 50 A max 0 5 ms or less 24 V DC FX5U 64M D FX5U 80M D 65 A max 2 0 ms or less 24 V DC Power consumption 1 FX5U 32M D 30 W FX5U 64M D 40 W FX5U 80M D 45 W 24 V DC built in power supply capacity FX5U 32M D 480 mA 360 mA 2 FX5U 64M D 7...

Страница 26: ...ulses FX5U 64M FX5U 80M X0 to X7 FX5U 32M X6 to X17 10 kHz FX5U 64M FX5U 80M X10 to X17 FX5U 64M FX5U 80M X20 and subsequent 0 1 0 05 kHz Pulse waveform Waveform T1 pulse width T2 rise fall time FX5U 32M X0 to X5 2 5 μs or more 1 25 μs or less FX5U 64M FX5U 80M X0 to X7 FX5U 32M X6 to X17 50 μs or more 25 μs or less FX5U 64M FX5U 80M X10 to X17 Input response time H W filter delay FX5U 32M X0 to X...

Страница 27: ...tions 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring Input impedance Input impedance Input impedance Input impedance 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring Fuse X S S Source input wiring 24 V DC Fuse X S S Sink input wiring Input impedance Input impedance 24...

Страница 28: ... item Max load 2 A point The total load current per common terminal should be the following value 4 output points common terminal 8 A or less 8 output points common terminal 8 A or less For details on the common refer to Page 35 Interpretation of terminal block layout Min load 5 V DC 2 mA reference values Open circuit leakage current Response time OFF ON Approx 10 ms ON OFF Approx 10 ms Insulation...

Страница 29: ...ils on the common refer to Page 35 Interpretation of terminal block layout Open circuit leakage current 0 1 mA or less 30 V DC Voltage drop when ON Y0 to Y3 1 0 V or less Y4 and subsequent 1 5 V or less Response time Y0 to Y3 2 5 μs or less 10 mA or more 5 to 24 V DC Y4 and subsequent 0 2 ms or less 200 mA or more 24 V DC Insulation of circuit Photo coupler insulation Indication of output operatio...

Страница 30: ...amming local global Constant scan 0 2 to 2000 ms can be set in 0 1 ms increments Fixed cycle interrupt 1 to 60000 ms can be set in 1 ms increments Timer performance specifications 100 ms 10 ms 1 ms No of program executions 32 No of FB files 16 Up to 15 for user Operation specifications Execution type Standby type initial execution type scan execution type event execution type Interrupt type Intern...

Страница 31: ... changed with parameter 1 Long counter LC 10 1024 points can be changed with parameter 1 Data register D 10 8000 points can be changed with parameter 1 Link register W 16 32768 points can be changed with parameter 1 Link special register SW 16 32768 points can be changed with parameter 1 No of system device points Special relay SM 10 10000 points fixed Special register SD 10 12000 points fixed Mod...

Страница 32: ... Accuracy Accuracy for the full scale of the digital output value Ambient temperature 25 5 Within 0 5 20 digit 2 Ambient temperature 0 to 55 Within 1 0 40 digit 2 Ambient temperature 20 to 0 1 Within 1 5 60 digit 2 Conversion speed 30 μs channels data refreshed every operation cycle Absolute maximum input 0 5 V 15 V Insulation method Inside the CPU module and the analog input circuit are not insul...

Страница 33: ...ample 0 0 0 0 127 0 0 0 etc 6 A straight cable can be used If a personal computer or GOT and CPU module are directly connected a cross cable can be used Item Specifications Data transmission speed 100 10 Mbps Communication mode Full duplex FDX Half duplex HDX 1 Interface RJ45 connector Transmission method Base band Maximum segment length The distance between hub and node 100 m Cascade connection 1...

Страница 34: ...cifications Transmission standards Conforms to RS 485 RS 422 specifications Data transmission speed Max 115 2 kbps Communication method Full duplex FDX Half duplex HDX Maximum total extension distance 50 m Protocol type MELSOFT connection Non protocol communication MELSEC Communication protocol 3C 4C frames MODBUS RTU Predefined protocol support Inverter communication N N network Parallel link Ins...

Страница 35: ...Accessories Dust proof protection sheet Manual supplied with product Model W W1 mounting hole pitch Mass weight FX5U 64M 220 mm 193 mm Approx 1 0 kg FX5U 80M 285 mm 258 mm Approx 1 2 kg Exterior color Main body Munsell 0 6B7 6 0 2 Accessories Dust proof protection sheet Manual supplied with product W1 22 80 mounting hole pitch 90 W 83 Unit mm 8 2 4 5 mounting holes W1 22 80 mounting hole pitch 90 ...

Страница 36: ...ilt in analog terminal Built in Ethernet connector 5 poles RDA RXD RDB RXD SDA TXD SDB TXD SG GND European type terminal block 5 poles V V V V2 V1 European type terminal block Analog input Analog output 8 1 Pin 1 2 3 4 5 6 7 8 Signal name TXD TXD RXD Not used Not used RXD Not used Not used ...

Страница 37: ...ut terminals connected to common COM One common terminal covers 4 or 8 output points The output number Y connected to common is the range inside the thick separation line For transistor output source type the COM terminal is the V terminal X0 S S 0 V 24 V N L 1 2 3 4 5 6 7 X10 11 12 13 14 15 16 17 FX5U 32MR ES Input terminal Output terminal Partition Vacant terminal Do not use Output terminals con...

Страница 38: ...7 V2 V3 24 22 Y20 21 23 V4 25 26 27 32 Y30 33 34 35 V5 36 31 37 FX5U 64MR DS FX5U 64MT DS FX5U 80MT ESS 0V S S 0V 24V N L 24V X0 1 2 3 4 5 6 7 X10 11 12 13 14 22 16 X20 21 15 17 23 24 25 26 27 X30 31 32 33 34 35 36 X40 42 44 46 37 Y4 2 3 COM1 1 Y0 COM0 5 6 7 Y10 11 12 13 Y14 15 16 17 COM2 COM3 24 22 Y20 21 23 COM4 COM5 25 26 27 32 Y30 33 34 35 36 31 37 Y40 COM6 41 42 41 43 44 43 45 46 45 47 47 Y4 ...

Страница 39: ...le I O module FX5 232 BD FX5 485 BD FX5 422 BD GOT Battery FX3U 32BL CPU module FX5U 32MR ES FX5U 32MT ES FX5U 32MT ESS FX5U 64MR ES FX5U 64MT ES FX5U 64MT ESS FX5U 80MR ES FX5U 80MT ES FX5U 80MT ESS FX5U 32MR DS FX5U 32MT DS FX5U 32MT DSS FX5U 64MR DS FX5U 64MT DS FX5U 64MT DSS FX5U 80MR DS FX5U 80MT DS FX5U 80MT DSS Input output FX5 CNV BUS Expansion boards High speed pulse input output FX5 16ET...

Страница 40: ... 80MT ESS Transistor source Model No of input output points Input type Output type Connection type Power supply capacity Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5U 32MR DS 32 points 16 points 16 points 24 V DC Sink source Relay Terminal block 900 mA 775 mA 1 480 mA 360 mA 1 FX5U 32MT DS Transistor sink FX5U 32MT DSS Transistor source FX5...

Страница 41: ...name in the following places 3 3 Extension Module Extension modules are used to expand inputs outputs functions and others The two connection types extension cable type and extension connector type are provided for extension modules FX5 CNV IF is required to use modules of extension connector type Extension cable type Extension connector type Model name abbreviation Pullout tab Extension cable Ext...

Страница 42: ...FX5 C32EX DS 24 V DC sink source FX5 E Input output type Input module Output module Input output module Powered input output module High speed pulse input output module Input output extension Total number of input output points Connection type No symbol Terminal block C Connector X ES 24 V DC sink source input X D 24 V DC sink input X DS 24 V DC sink source input YR ES Relay output YT ES Transisto...

Страница 43: ... mA 125 mA FX5 16EYT ES Transistor sink FX5 16EYT ESS Transistor source Model No of input output points Input type Output type Connection type Current consumption Total No of points No of input points No of output points 5 V DC power supply 24 V DC power supply FX5 C16EYT D 16 points 16 points Transistor sink Connector 100 mA 100 mA FX5 C16EYT DSS Transistor source FX5 C32EYT D 32 points 32 points...

Страница 44: ...its 1 FX5 C32ET D 32 points 16 points 16 points 24 V DC sink Transistor sink Connector 120 mA 100 mA 65 mA FX5 C32ET DSS 24 V DC sink source Transistor source Model No of input output points Input type Output type Connection type Power supply capacity Total No of points No of input points No of output points 5 V DC power supply 24 V DC service power supply FX5 32ER ES 32 points 16 points 16 points...

Страница 45: ...urrent input thermocouple input resistance thermometer input 8 points 40 mA 100 mA FX5 4LC 1 4 ch temperature control thermocouple resistance thermometer micro voltage 4 point current sensor input 4 point transistor output 8 points 140 mA 25 mA Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX5 20PG P 1 P...

Страница 46: ...r in the program The bus speed for accessing the FX3 intelligent function module is the FX3 speed Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply External 24 V DC power supply FX3U 4AD 4 ch voltage current input 8 points 110 mA 90 mA FX3U 4DA 4 ch voltage current output 120 mA 160 mA FX3U 4LC 4 ch temperature control thermocouple resis...

Страница 47: ...odule at the following current values within the derating range Model Function No of occupied input output points Power supply capacity 5 V DC power supply 24 V DC power supply FX5 1PSU 5V Extension power supply for the AC power supply type 1200 mA 1 300 mA 1 Model Function No of occupied input output points Power supply capacity 5 V DC power supply 24 V DC power supply FX5 C1PS 5V Extension power...

Страница 48: ...product Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply FX5 CNV IF Connector conversion from CPU module extension modules extension cable type or intelligent function modules Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply FX5 CNV BUS Bus conversion from CPU module extensio...

Страница 49: ...nnector conversion adapter FX5 CNV BC Connector Conversion Adapter Adapter for connecting extended extension cable and module of extension cable type except for FX5 1PSU 5V or extension power supply module Model Function No of occupied input output points Current consumption 5 V DC power supply 24 V DC power supply FX5 232 BD For RS 232C communication 20 mA FX5 485 BD For RS 485 communication 20 m...

Страница 50: ... supply FX 16E TB Directly connected to the I O connector of a PLC 112 mA FX 32E TB 112 mA 16 points FX 16EX A1 TB 100 V AC input type 48 mA FX 16EYR TB Relay output type 80 mA FX 16EYT TB Transistor output type sink output 112 mA FX 16EYS TB Triac output type 112 mA FX 16E TB UL Directly connected to the I O connector of a PLC 112 mA FX 32E TB UL 112 mA 16 points FX 16EYR ES TB UL Relay output ty...

Страница 51: ...iguration of whole system Expansion board and expansion adapters Remote I O Remote I O Bus conversion module FX3 extension power supply module Intelligent module Intelligent module FX5 32ER ES I O module Powered input output module Intelligent module Range of devices powered by FX3 extension power supply module Expansion adapters FX5 40SSC S Module No 1 FX5 1PSU 5V I O module Y20 to Y37 FX5 16EYR ...

Страница 52: ... or less including the number of input output points of extension devices max 256 points and number of remote I O points max 384 points can be controlled For details on the number of input output points refer to Page 55 Limitation on the Number of Input Output Points Extended extension cable Up to 1 cable CPU module Up to 16 modules 1 Up to 12 modules Up to 10 modules Up to 8 modules Up to 2 modul...

Страница 53: ... except for FX5 1PSU 5V or extension power supply module When connecting a bus conversion module in the same system connect FX5 1PSU 5V or the powered input output module directly after the extended extension cable This cannot be used with the FX3 extension module Model Limitations FX5 CCLIEF Only one module may be connected per system FX5 CCL MS One module can be connected to the system for each ...

Страница 54: ...a limitation on the number of expansion adapter connected to the CPU module as follows Precautions To use two or more FX5 4DA ADP connect them to only one side of FX5 4AD TC ADP Do not connect them to both sides Type Limitations Communication adapter Up to 2 modules can be connected Analog adapter Up to 4 modules can be connected Expansion board Expansion adapter FX5 232ADP FX5 485ADP Communicatio...

Страница 55: ... system Extended extension cable Only 1 cable can be connected to a system Bus conversion module Only 1 module can be connected to a system Type Limitations Total No of input modules output modules intelligent function modules and bus conversion modules Up to 12 modules can be connected Total No of intelligent function module and bus conversion modules Up to 8 modules can be connected Up to 16 mod...

Страница 56: ...on modules Up to 8 modules can be connected Type Limitations Total No of input modules output modules intelligent function modules and bus conversion modules Up to 10 modules can be connected Total No of intelligent function module and bus conversion modules Up to 8 modules can be connected Up to 10 modules Up to 8 modules Powered input output module FX5 Intelligent module FX5 Intelligent module P...

Страница 57: ...oints can be controlled 1 A bus conversion module is required when using the FX3U 16CCL M 2 A bus conversion module is required when using the FX3U 128ASL M Type Limitations Total No of intelligent function modules Up to 8 modules can be connected Type Limitations Total No of intelligent function modules Up to 6 modules can be connected Up to 8 modules FX3 Intelligent module FX3 extension power su...

Страница 58: ...by model refer to the following Page 38 CPU Module Page 40 I O Module Number of occupied input output points of intelligent function modules Count the number of occupied input output points of intelligent function modules The number of occupied input output points per module is 8 For details on the number of occupied input output points by model refer to Page 43 Intelligent Function Module 512 poi...

Страница 59: ...ts of remote I O points to be used with FX3U 16CCL M are occupied 512 points 160 points 256 points 96 points Remote I O points that can be used with FX3U 128ASL M are 96 points or less Ex When input output points are 160 points FX3U 16CCL M is connected to the right side of FX3U 128ASL M and the total number of remote I O points to be used with FX3U 128ASL M is 128 points 512 points 160 points 128...

Страница 60: ...e engineering tool parameters FX3U 128ASL M Set with the rotary switch on the FX3U 128ASL M main body For details refer to the following manuals MELSEC iQ F FX5 User s Manual ASLINK FX3U 128ASL M User s Manual 384 points Actually used CC Link remote I O points station b 32 points FX5 CCL MS master station 256 points FX3U 16CCL M Maximum number of CC Link remote I O points b CC Link remote I O poin...

Страница 61: ...s used for input circuit 2 Check the current consumption of extension devices Page 40 I O Module Page 43 Intelligent Function Module 1 If using external power supply for input circuit calculate current consumption of 24 V DC power supply as 0 mA 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC service power supply CPU modul...

Страница 62: ...he calculation result is a negative value the current consumption exceeds the power supply capacity of the CPU module Reconfigure the system adding powered input output module or extension power supply modules mA mA CPU module Current consumption mA 0 mA Calculation result Ex 510 mA 900 mA 390 mA Capacity of 5 V DC power supply Total of current consumed by extension module mA mA CPU module Current...

Страница 63: ...ply module Type Model Power supply capacity 5 V DC power supply 24 V DC power supply CPU module FX5U 32MT DS 900 mA 480 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion board FX5 232 BD 20 mA Expansion adapter FX5 232ADP 30 mA 30 mA Output module FX5 16EYT ES 100 mA 125 mA Input module FX5 16EX ES 100 mA Simple motion module FX5 40SSC S Bus conversion module FX5...

Страница 64: ...t circuit 2 Check the current consumption of the extension module Page 40 I O Module Page 43 Intelligent Function Module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC service power supply Powered input output module FX5 32ER ES 965 mA 250 mA 1 Type Model Current consumption 5 V DC power supply 24 V DC service power suppl...

Страница 65: ...e 40 I O Module Page 43 Intelligent Function Module 3 Calculate the total current consumption of each power supply Type Model Power supply capacity 5 V DC power supply 24 V DC power supply Powered input output module FX5 32ER DS 965 mA 310 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Input module FX5 16EX ES 100 mA 85 mA Output module FX5 16EYR ES 100 mA 125 mA Simple...

Страница 66: ...wer supply capacity of the CPU module Reconfigure the system adding powered input output module mA mA Powered input output module Current consumption mA 0 mA Calculation result Ex 460 mA 965 mA 505 mA Capacity of 5 V DC power supply Total of current consumed by extension module mA mA Powered input output module Current consumption mA 0 mA Calculation result Ex 210 mA 310 mA 100 mA Capacity of 24 V...

Страница 67: ...ion module Page 40 I O Module Page 43 Intelligent Function Module 1 24 V DC power supply is supplied from the CPU module or powered input output module Type Model Power supply capacity 5 V DC power supply 24 V DC power supply FX5 extension power supply module FX5 1PSU 5V 1200 mA 300 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Input module FX5 16EX ES 100 mA 1 Output ...

Страница 68: ... system adding powered input output module or extension power supply modules Power supply type Total current consumption 5 V DC power supply 460 mA 24 V DC power supply 125 mA Power supply from CPU module or powered input output module CPU module Powered input output module Input module Input module FX5 Intelligent module FX5 Intelligent module Extension power supply module When the CPU module or ...

Страница 69: ... DC power supply FX5 extension power supply module FX5 C1PS 5V 1200 mA 625 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Input module FX5 C16EX D 100 mA Output module FX5 C16EYT D 100 mA 100 mA Bus conversion module FX5 CNV BUSC 150 mA Analog input FX3U 4AD 110 mA Power supply type Total current consumption 5 V DC power supply 460 mA 24 V DC power supply 100 mA CPU mod...

Страница 70: ...tension power supply module Reconfigure the system adding powered input output module or extension power supply modules mA mA Current consumption mA 0 mA Calculation result Ex 460 mA 1200 mA 740 mA Capacity of 5 V DC power supply Extension power supply module Total of current consumed by extension module mA mA Current consumption mA 0 mA Calculation result Ex 100 mA 625 mA 525 mA Capacity of 24 V ...

Страница 71: ... Overall system limitation Number of modules connected to the CPU module Page 53 Connection to the CPU module Type No of modules used Limitations Judgment Expansion board 1 Only 1 OK Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Up to 16 Extension power supply modules and connector conversi...

Страница 72: ...ntelligent function modules Type No of modules used Limitations Judgment Total No of intelligent function modules 5 Up to 6 When not using extension power supply modules OK Limitations Judgment FX3 extension modules are connected on the right side of the bus conversion module OK FX5 extension modules are connected on the left side of the bus conversion module OK Model Limitations Judgment FX3U 128...

Страница 73: ...oints Output module FX5 16EYT ES 16 points Output module FX5 16EYT ES 16 points Output module FX5 16EYR ES 16 points Simple motion module FX5 40SSC S 8 points Bus conversion module FX5 CNV BUS 8 points Pulse output module FX3U 1PG 8 points Analog input module FX3U 4AD 8 points Temperature controller module FX3U 4LC 8 points AnyWireASLINK master module FX3U 128ASL M 8 points CC Link intelligent dev...

Страница 74: ...PU module FX5U 32MR ES 900 mA 400 mA 24 V DC service power supply is used for input circuit Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion board FX5 232 BD 20 mA Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 16EX ES 100 mA 85 mA Output module FX5 16EYT ES 100 mA 125 mA Output module FX5 16EYT ES 100 mA 125 mA O...

Страница 75: ...y module Type No of modules used Limitations Judgment Expansion board 1 Only 1 OK Type No of modules used Limitations Judgment Expansion adapter Communication 2 Up to 2 OK Type No of modules used Limitations Judgment Extension module 11 Up to 16 Extension power supply modules and connector conversion module are excluded OK Extension power supply module 1 Up to 2 OK Bus conversion module 1 Only 1 O...

Страница 76: ... extension modules are connected on the left side of the bus conversion module OK Model Limitations Judgment FX3U 128ASL M Only one module may be connected to the system Use together with the FX5 ASL M is not possible OK FX3U 64CCL Only one module may be connected to the system When using the FX5 CCL MS as the intelligent device station it cannot be used together with the FX5 CCL MS OK Type Model ...

Страница 77: ...nts and remote I O points Page 55 Limitation on the Number of Input Output Points Network No of remote I O points AnyWireASLINK 64 points 384 points Remote I O points 64 points OK Maximum number of Remote I O points 152 points 512 points Number of input output points Remote I O points 64 points Total number of input output points 216 points Calculation result OK Max number of input output points ...

Страница 78: ...apacity 5 V DC power supply 24 V DC service power supply CPU module FX5U 32MR ES 900 mA 400 mA 24 V DC service power supply is used for input circuit Type Model Current consumption 5 V DC power supply 24 V DC power supply Expansion board FX5 232 BD 20 mA Expansion adapter FX5 232ADP 30 mA 30 mA Expansion adapter FX5 485ADP 20 mA 30 mA Input module FX5 16EX ES 100 mA 85 mA Output module FX5 16EYT E...

Страница 79: ... DC power supply FX5 extension power supply module FX5 1PSU 5V 1200 mA 300 mA Type Model Current consumption 5 V DC power supply 24 V DC power supply Output module FX5 16EYR ES 100 mA 125 mA Simple motion module FX5 40SSC S Bus conversion module FX5 CNV BUS 150 mA Pulse output module FX3U 1PG 150 mA Analog input module FX3U 4AD 110 mA Temperature controller module FX3U 4LC 160 mA AnyWireASLINK mas...

Страница 80: ... number of Extension modules The CPU module automatically assigns numbers 1 to 16 to intelligent function modules or bus conversion module as module numbers in order of distance from the CPU module Intelligent function modules or bus conversion module connected to the CPU module Module numbers are assigned to intelligent function modules in order of distance from the CPU module No 1 to No 16 Produ...

Страница 81: ...ing or in the vertical direction Always mount the PLC horizontally on the wall as shown in the following figure Spaces in enclosure Extension devices can be connected on the left and right sides of the CPU module of the PLC Keep a space of at least 50 mm between the module main body and other devices and structure If you intend to add extension devices keep necessary spaces on the left and right s...

Страница 82: ... FX5 30EC FX5 65EC Another equipment Another equipment FX5U CPU module FX5 16EX FX5 16EYT FX5 16EYT FX5 16EYT FX5 232ADP 50mm FX5 CNV BC FX5 16EX Extension module A 50 mm A A FX5U CPU module Intelligent function module For product dimensions or manual for various products refer to App 5 I O Module Expansion adapter Output module Input module 50mm FX5U CPU module Intelligent module For product dime...

Страница 83: ...IN rail For details on the procedures for installing on and detaching from DIN rail refer to Page 82 Procedures for Installing on and Detaching from DIN Rail Example of installation 1 FX5 CNV BC can only be installed directly Installing directly The PLC can be installed directly in the enclosure with M4 screws For mounting hole pitch refer to Page 85 Hole pitches for direct mounting Example of ins...

Страница 84: ...extension devices Some extension devices must be mounted on the CPU module before the module is installed in the enclosure Connect expansion adapters to the CPU module before mounting the PLC in the enclosure Mount extension modules extension cable type and terminal module in the enclosure after mounting the CPU module in the enclosure Connect the extension module extension connector type to the c...

Страница 85: ...to the DIN rail 3 Lock the DIN rail mounting hooks C in the following figure while pressing the PLC against the DIN rail Installation of extension module extension cable type 1 Push out the DIN rail mounting hook A in the right figure of the extension module 2 Fit the upper edge of the DIN rail mounting groove B in the right figure onto the DIN rail 3 Push the product against the DIN rail 4 Lock t...

Страница 86: ... For the mounting procedure of the terminal block refer to Page 97 Removal and installation of removable terminal block 2 Disconnect the extension cables and the connecting cables When removing the extension cable pull the pullout tab of the extension cable straight up 3 Insert the tip of a flathead screwdriver into the hole of the DIN rail mounting hook B in the right figure This step also applie...

Страница 87: ... that varies depending on the product refer to the table CPU module Expansion adapter Dimensions Model name Mounting hole pitch W Unit mm FX5U 32MR ES FX5U 32MT ES FX5U 32MT ESS FX5U 32MR DS FX5U 32MT DS FX5U 32MT DSS 123 FX5U 64MR ES FX5U 64MT ES FX5U 64MT ESS FX5U 64MR DS FX5U 64MT DS FX5U 64MT DSS 193 FX5U 80MR ES FX5U 80MT ES FX5U 80MT ESS FX5U 80MR DS FX5U 80MT DS FX5U 80MT DSS 258 Dimensions...

Страница 88: ...EX ES FX5 8EYR ES FX5 8EYT ES FX5 8EYT ESS FX5 16EX ES FX5 16EYR ES FX5 16EYT ES FX5 16EYT ESS FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 16ET ES H FX5 16ET ESS H Refer to the figure shown to the left FX5 32ER ES FX5 32ET ES FX5 32ET ESS FX5 32ER DS FX5 32ET DS FX5 32ET DSS 140 Dimensions Model name Mounting hole pitch W Unit mm FX5 1PSU 5V 34 FX3U 1PSU 5V 51 Dimensions Model name Mounting hole pitc...

Страница 89: ...apter refer to Page 90 Connection method B connection of an expansion adapter The FX5U 32M is used as the CPU module in this example 1 Make mounting holes on the mounting surface according to the external dimensions diagram 2 Fit the CPU module A in the right figure to holes and secure it with M4 screws B in the right figure In the case of FX5U 64M 80M there are four screw holes A C D F H 98 80 Un...

Страница 90: ...e DIN rail mounting hook A in the right figure of the extension module extension cable type If the DIN rail mounting hook is not pushed in the screw hole is covered and the extension module cannot be mounted This procedure may not be required depending on the model 3 Fit the extension module extension cable type B in the right figure to the holes and secure it with M4 screws C in the right figure ...

Страница 91: ...to the CPU module 1 Remove the expansion board connector cover from the front face of the CPU module 2 Connect the expansion board to the expansion board connector C in the right figure 3 Fix the expansion board E in the right figure with provided M3 tapping screws D in the right figure to the CPU module Tightening torque 0 3 to 0 6N m Connection method C Connection method D Expansion board Expans...

Страница 92: ...odule B in the right figure 3 Connect the expansion adapter to the CPU module as shown in the right figure 4 Slide the hook for coupling the expansion adapter of the CPU module B in the right figure to fix the expansion adapter C in the right figure 1 Remove the extension connector cover A in the right figure on the right side of the surface of the CPU module or powered input output module 2 Conne...

Страница 93: ...ht figure of the existing module left side A in the right figure 2 Connect the extension cable C in the right figure of the module to be connected right side to the existing module left side A in the right figure 3 Fit the top cover B in the right figure 4 Pull out the pullout tab D in the right figure of the extension cable on the right side of the cover 1 Separate the case of FX5 CNV BC into two...

Страница 94: ...upling the extension module A in the right figure of the existing module left side 2 Remove the subsequent extension connector cover B in the right figure 3 Connect an extension module as shown in the right figure 4 Slide the hook for coupling the extension module A in the right figure of the existing module to fix the extension module C in the right figure 1 Connect the FX3 extension cable A in t...

Страница 95: ...ly Remove the resin cover only when crossover wiring to a subsequent module is performed FX5 C EX DS and FX5 C32ET DSS do not have power connectors and the power is supplied from using input connectors Thus removing the resin cover is not required Precautions To perform crossover wiring supply the power from the preceding module to the subsequent module The power cannot be supplied from the subseq...

Страница 96: ...ion of the arrow Precautions If the power cable is removed by force the cable may break Connection of I O cables I O connectors Cable connection to I O connectors I O connectors conform to MIL C 83503 For I O cables refer to Page 95 Preparation of I O connectors and prepare them I O modules extension connector type Push here with fingers a Example FX5 C32EX D Notch Input X Input X Example FX5 C32E...

Страница 97: ...of the terminal module and I O connectors For the connection with the terminal module refer to Page 96 WIRING Flat cables with tube On both ends 20 pin connectors are attached FX 16E 300CAB 3 m FX 16E 500CAB 5 m FX 16E 150CAB R 1 5 m Round multicore cables On both ends 20 pin connectors are attached FX 16E 300CAB R 3 m FX 16E 500CAB R 5 m Model and configuration of I O connectors Suitable wiring U...

Страница 98: ...ply type For sink input connect 24V S S terminal For source input connect 0V S S terminal In the case of DC power supply type For sink input connect S S terminal For source input connect S S terminal Connect sensors and switches to the terminals Page 109 Input Wiring 5 Wire the output Y terminal Connect the load to terminals Page 121 Output Wiring 6 Wire built in analog I O terminal blocks Connect...

Страница 99: ...e that there is no gap between the terminal block and mount position 6 2 Cable Connecting Procedure The cable connecting procedure is explained below Screw terminal block Wire the screw terminal block in accordance with the following specifications For information concerning screw terminal blocks for intelligent function modules refer to User s manual for each intelligent function module Terminal ...

Страница 100: ...re connected to a single terminal Manufacturer Model Supported standards Crimp tool JST Mfg Co Ltd FV1 25 B3A UL Listed YA 1 JST Mfg Co Ltd FV2 MS3 Manufacturer Model Supported standards Crimp tool JST Mfg Co Ltd FV1 25 B3A UL Listed YA 1 JST Mfg Co Ltd Terminal Terminal screw Crimp terminal 6 2 mm or less 3 2 6 2 mm or less 3 2 Terminal 3 2 6 3 mm or more 3 2 Terminal screw Crimp terminal 6 2 mm ...

Страница 101: ...rque Solid wire Stranded wire Wire ferrule with insulation sleeve Built in analog I O terminal block Terminal block for built in RS 485 communication One wire 0 2 to 0 5 mm2 AWG24 to 20 0 2 to 0 5 mm2 AWG24 to 20 0 22 to 0 25 N m Two wires 0 2 mm2 AWG24 Expansion board expansion adapter One wire 0 3 to 0 5 mm2 AWG22 to 20 0 3 to 0 5 mm2 AWG22 to 20 Two wires 0 3 mm2 AWG22 Analog adapter One wire 0...

Страница 102: ...y available screwdriver with a straight tip The recommended shape is shown in the figure on the right Precautions When a precision screwdriver with a small grip is used the specified tightening torque cannot be obtained Use the following screwdriver or equivalent product grip diameter 25 mm to obtain the tightening torque specified above Manufacturer Model Phoenix Contact GmbH Co KG SZS 0 4 2 5 0 ...

Страница 103: ... turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time 4 Do not connect the 24V terminals 24 V DC service power supply of the CPU module and the powered input output module with each other Connect the 0V terminal AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5U 32MT ES FX5 8EX ES S S Class D gro...

Страница 104: ... the safety of the system and turn off the power of the PLC including extension devices at the same time 4 Do not connect the 24V terminals 24 V DC service power supply of the CPU module and the powered input output module with each other Connect the 0V terminal AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5U 32MT ES FX5 8EX ES S S Class D grounding grounding resistance 10...

Страница 105: ...U module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time X S S AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5U 32MT ES FX5 8EX ES S S Class D grounding grounding resistance 100 or less DC AC 1 2 Breaker 3 FX5 40SSC S L N 1 3 FX5 1PSU 5V FX5 40SSC S FX5 8EX ES FX5 8EYT ES Wiring preca...

Страница 106: ...PU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time AC power supply 100 to 240 V S S L N 0V PL Power ON MC MC MC MC 24V FX5U 32MT ES FX5 8EX ES S S Class D grounding grounding resistance 100 or less DC AC 1 2 Breaker 3 FX5 40SSC S L N S S 1 3 FX5 1PSU 5V FX5 40SSC S FX5 8EX ES FX5 8EYT ES Wiring precau...

Страница 107: ...ernal power supply turn on the power supply at the same time as the CPU module or earlier than the CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time 24 V DC S S FX5 4DA ADP PL Power ON MC MC MC MC FX5U 32MT DS FX5 8EX ES S S Class D grounding grounding resistance 100 or less 1 3 2 5 V 0 V 24 V 5 V 0...

Страница 108: ...y turn on the power supply at the same time as the CPU module or earlier than the CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time S S PL Power ON MC MC MC MC FX5U 32MT DS FX5 8EX ES S S Class D grounding grounding resistance 100 or less 1 2 5 V 0 V 24 V 5 V 0 V 24 V Circuit Protector 3 FX5 40SSC S...

Страница 109: ...ply at the same time as the CPU module or earlier than the CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time 24 V DC S S FX5 4DA ADP PL Power ON MC MC MC MC FX5U 32MT DS FX5 8EX ES S S Class D grounding grounding resistance 100 or less 1 3 2 5 V 0 V 24 V 5 V 0 V 24 V FX5 C1PS 5V 1 5 V 0 V 24 V 5 V 0...

Страница 110: ...r supply at the same time as the CPU module or earlier than the CPU module When turning off the power confirm the safety of the system and turn off the power of the PLC including extension devices at the same time S S PL Power ON MC MC MC MC FX5U 32MT DSS FX5 8EX ES S S Class D grounding grounding resistance 100 or less 1 2 5 V 0 V 24 V 5 V 0 V 24 V Circuit Protector FX5 CNV BUSC FX3U 4DA 5 V 0 V ...

Страница 111: ...and S S terminal Page 115 Sink input AC power supply type Source input Connect the 0V terminal and S S terminal Page 116 Source input AC power supply type In the case of DC power supply type Sink input Connect the terminal and S S terminal Page 117 Sink input DC power supply type Source input Connect the terminal and S S terminal Page 118 Source input DC power supply type All inputs X of the CPU m...

Страница 112: ...llector transistor output is connected between an input X terminal and the COM terminal and the circuit is closed the input X turns on At this time the LED corresponding to the DISP switch lights up FX5 C16EX D does not have the DISP switch In the sink input the input X is turned on by connecting 24 V DC with the COM terminal and connecting a no voltage contact or NPN open collector transistor out...

Страница 113: ... μs or less FX5U 64M FX5U 80M X0 to X7 High speed pulse input output module X0 to X5 FX5U 32M X6 to X17 ON 30 μs or less OFF 50 μs or less FX5U 64M FX5U 80M X10 to X17 High speed pulse input output module X6 X7 FX5U 64M FX5U 80M X20 and subsequent ON 50 μs or less OFF 150 μs or less Input module Input output modules Powered input output module Change of filter time All input circuits have digital ...

Страница 114: ...device having a parallel resistance Rp kΩ of the following value or more Item Specifications Voltage drop FX5U 32M X0 to X5 3 9 V FX5U 64M FX5U 80M X0 to X7 High speed pulse input output module X0 to X5 FX5U 32M X6 to X17 4 1 V FX5U 64M FX5U 80M X10 to X17 High speed pulse input output module X6 X7 FX5U 64M FX5U 80M X20 and subsequent 2 4 V Input module Input output modules Powered input output mo...

Страница 115: ...U 32M X6 to X17 4 Rp 15 Rp or less FX5U 64M FX5U 80M X10 to X17 High speed pulse input output module X6 X7 FX5U 64M FX5U 80M X20 and subsequent 6 Rp 13 Rp or less Input module Input output modules Powered input output module Item Specifications Bleeder resistance Rb kΩ FX5U 32M X0 to X5 7 I 1 5 or less FX5U 64M FX5U 80M X0 to X7 High speed pulse input output module X0 to X5 FX5U 32M X6 to X17 7 I ...

Страница 116: ... to X5 wire the terminals as stated below The wiring length should be 5 m or less Use shielded twisted pair cables for connecting cables Ground the shield of each shielded cable only on the CPU module side Connect a 1 5 kΩ 1 W or more bleeder resistance to the input terminal so that the sum of the load current of the open collector transistor output on the mating device and the input current of th...

Страница 117: ...of the CPU module The 24 V DC service power supply or external power supply can be used for all inputs X of the CPU module However you need to select either one for each CPU module or I O module Both power supplies cannot be used together in the same module X0 S S 0V 24V FX5U 32MT ES N L X1 X0 S S X1 FX5 16EX ES 5V0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V0V 24V 5V0V 24V Fuse 24 V DC Class D g...

Страница 118: ... module The 24 V DC service power supply or external power supply can be used for all inputs X of the CPU module However you need to select either one for each CPU module or I O module Both power supplies cannot be used together in the same module X0 S S 0V 24V FX5U 32MT ESS N L X1 X0 S S X1 FX5 16EX ES 5V0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V0V 24V 5V0V 24V Fuse 1 2 Three wire sensor Thre...

Страница 119: ...itch a bleeder resistance may be required 3 In the case of sink input wiring short circuit the S S and terminals of the CPU module X0 S S FX5U 32MT DS X1 X0 S S X1 FX5 16EX ES 5V0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V0V 24V 5V0V 24V Fuse 24 V DC Class D grounding grounding resistance 100 or less 1 2 3 Input impedance Input terminal Input terminal Three wire sensor Three wire sensor Two wire...

Страница 120: ...ch a bleeder resistance may be required 3 In the case of source input wiring short circuit the S S and terminals of the CPU module X0 S S FX5U 32MT DSS X1 X0 S S X1 FX5 16EX ES 5V0V 24V Input terminal X0 S S X1 FX5 16EX ES 5V0V 24V 5V0V 24V Fuse Class D grounding grounding resistance 100 or less 1 2 Three wire sensor Three wire sensor Two wire proximity sensor 3 Input impedance Input terminal Inpu...

Страница 121: ... the one of the connected connector 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM Input number of PLC 3 wire sensor NPN Vacant terminal 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers COM...

Страница 122: ... 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 24 V DC 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse COM0 1 3 wire sensor PNP Input number of PLC Vacant terminal 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 to 3 0 to 3 4 to 7 4 to 7 24 V DC 10 15 Fuse Fuse PLC input No Photocoupler power supply 100 V to 120 V AC ...

Страница 123: ...able shows the approximate life of a relay based on the results of an operation life test Test condition 1 sec ON 1 sec OFF The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut down Please refer to the following measures regarding the inductive load Page 123 Contact protection circuit for inductive loads Some types of inductive...

Страница 124: ... comply with CE UL cUL standards for loads Insulation of circuit The PLC internal circuit and external load circuits are electrically insulated between the output relay coil and contact The common terminal blocks are separated from one another Display of operation When power is applied to the output relay coil the LED is lit and the output contact is turned on Response time The response time of th...

Страница 125: ...for commutation must comply with the following specifications AC circuit Connect a surge absorber CR composite parts like surge killer spark killer etc parallel to the load Select a surge absorber with voltage rating that is suitable for the output used Interlock For loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external inte...

Страница 126: ...ype powered input output module and high speed pulse input output module the transistor output type is a 4 point or 8 point common output type Sink output common Source output common Output to make load current flow into the output Y terminal is called sink output Output to make load current flow out of the output Y terminal is called source output Sink output Source output Connect each COM number...

Страница 127: ...fers depending on the output terminal used For specifications of each module refer to the following For output specifications of the CPU module refer to Page 26 Output Specifications For output specifications of the I O modules refer to Page 181 Output specifications For output specifications of the terminal modules refer to Page 197 Output specifications The transistor OFF time is longer under li...

Страница 128: ...r loads such as forward reverse contactors etc where a hazardous condition could result if switched ON simultaneously an external interlock should be provided for interlocking along with an interlock in the PLC program as shown below A short circuit at a load connected to an output terminal could cause burnout at the output device or the PCB To prevent this a protection fuse should be inserted at ...

Страница 129: ...rrent Current of 0 3 A can flow per one output point However current of four output points should be 0 8 A average of 0 2 A per one point to suppress temperature rise When a load with a high rush current is frequently turned on or off the mean square current should be 0 2 A or less Open circuit leakage current C R absorbers are connected in parallel at the triac output terminal for turning off the...

Страница 130: ...w In phase PLC output contacts 1 should be used in an in phase manner C R absorbers are connected in parallel at the triac output circuit for turning off the triac When a minute current load of 0 4 VA or less 100 V AC or 1 6 VA or less 200 V AC is connected a surge absorber must be connected in parallel with the load Select a surge absorber with the rated voltage that is suitable for the output us...

Страница 131: ... breakdown due to load short circuiting 2 represents vacant terminals Y0 COM0 Y7 Y0 COM1 Y7 AC power supply 100 to 240 V PL Power ON MC MC MC MC Load Load Fuse 1 Fuse 1 Fuse 1 Fuse 1 Fuse 1 Breaker Y0 COM0 Y14 COM3 Y4 COM1 2 Emergency stop Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field DC power supply CPU ...

Страница 132: ...e to load short circuiting 2 represents vacant terminals Y0 COM0 Y7 Y0 COM1 Y7 Load PL Power ON MC MC MC MC DC power supply Load Fuse 1 Fuse 1 Load Load Fuse 1 Fuse 1 AC power supply 100 to 240 V Breaker Y0 COM0 Y14 COM3 Y4 COM1 2 Emergency stop Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field CPU module tra...

Страница 133: ...to load short circuiting 2 represents vacant terminals Y0 V0 Y7 Y0 V1 Y7 PL Power ON Emergency stop MC MC MC MC DC power supply Load Load Fuse Fuse AC power supply 100 to 240 V Breaker Load Load Fuse 1 Fuse 1 Y0 V0 Y14 V3 Y4 V1 2 Power supply for loads connected to PLC output terminals As for emergency stop operation see DESIGN PRECAUTIONS at Safety Precautions field CPU module transistor output s...

Страница 134: ... this number with the one of the connected connector 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 COM0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM 0 to 7 Smaller numbers 0 to 7 Larger numbers Fuse Fuse Fuse 1 Output number of PLC 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 Vacant terminal 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 V0 24 V DC MC1 MC2 COM COM COM COM COM COM COM COM ...

Страница 135: ...output contacts FX 16EYT TB Connectable models FX5 C EYT D FX5 C32ET D For external wiring precautions refer to Page 123 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse 0 to 7 Smaller numbers 0 to 7 Larger numbers PLC output No Relay power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 C...

Страница 136: ...5 C32ET DSS For external wiring precautions refer to Page 123 Wiring precautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 24 V DC Fuse Fuse PLC output No Photocoup...

Страница 137: ...cautions 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are connected to each output Fuse Fuse Fuse Load Fuse PLC output No Photocoupler power supply 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 U U U U U 24 V DC Surge absorbers are conne...

Страница 138: ...n be induced by others 2 For unused channels short circuit the V and V terminals When used as a current input refer to Page 172 How to use analog inputs built in CPU module for current inputs Analog output wiring 1 For analog output wiring use shielded twisted pair cables double core type Separate them from other power lines or lines which can be induced by others 2 Ground a shielded cable at one ...

Страница 139: ... instructions are given based on the allocation of the input output numbers for wiring For the instructions refer to MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks Positioning function For wiring examples for the positioning function refer to MELSEC iQ F FX5 User s Manual Positioning Control CPU module built in High speed pulse input output module Communication ...

Страница 140: ...00 Ω or less CH to be used Pulse input mode External preset input External enable input Operation mode CH1 CPU module or CH9 high speed pulse input output module 1 phase 1 input S W Invalid Invalid Normal mode 1 5 k 1 5 k In the case of sink wiring FX5U 32MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC NPN open collector transistor output rotary encoder When the input term...

Страница 141: ...X5 16ET ES H FX5U 32MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC 0V S S X0 Aphase B phase Z phase When the input terminals of the FX5 16ET ES H are used 1 5 k 1 5 k In the case of source wiring S S L N 24V 0V 24V Rotary encoder 24 V DC 0V X0 Aphase B phase Z phase FX5U 32MT ESS Class D grounding 1 Fuse S S L N 24V 0V 24V Rotary encoder 24 V DC 0V S S X0 Aphase B phase Z...

Страница 142: ... V DC 1 5 k 24 V DC In the case of sink wiring FX5U 32MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 0V X2 X3 Aphase B phase Z phase FX5 16ET ES H FX5U 32MT ES S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 0V S S X2 X3 Aphase B phase Z phase NPN open collector transistor output rotary encoder When the input terminals of the FX5U 32MT ES are used When the input termin...

Страница 143: ...ase B phase Z phase NPN open collector transistor output rotary encoder When the input terminals of the FX5U 32MT ES are used When the input terminals of the FX5 16ET ES H are used 1 5 k 1 5 k In the case of source wiring FX5U 32MT ESS S S L N 24V 0V 24V Rotary encoder Class D grounding 1 Fuse 24 V DC 0V X2 X3 Aphase B phase Z phase FX5 16ET ESS H FX5U 32MT ESS S S L N 24V 0V 24V Rotary encoder Cl...

Страница 144: ...t function refer to MELSEC iQ F FX5 User s Manual Application Example of wiring When 24 V DC service power supply is used 1 5 k 1 5 k 1 5 k 1 5 k In the case of sink wiring In the case of source wiring S S L N 24V Class D grounding 1 Fuse FX5U 32MT ES Example of wiring of FX5U 32MT ES Example of wiring of FX5 16ET ES H Example of wiring of FX5U 32MT ESS Example of wiring of FX5 16ET ESS H 0V X0 3 ...

Страница 145: ...n the case of sink wiring In the case of source wiring S S L N 24V Class D grounding 1 Fuse 24 V DC 0V X0 3 wire type S S L N 24V Class D grounding 1 Fuse 24 V DC 0V X0 3 wire type S S L N 24V Class D grounding 1 Fuse 24 V DC 0V X0 S S 3 wire type S S L N 24V Class D grounding 1 Fuse 24 V DC 0V S S X0 3 wire type Example of wiring of FX5U 32MT ES Example of wiring of FX5 16ET ES H Example of wirin...

Страница 146: ...e example is the wiring for the input output of the FX5U 32MT ES Source wiring The example is the wiring for the input output of the FX5U 32MT ESS DSW SM400 X10 Y10 D100 K1 X10 X11 X12 X13 X15 X14 X16 X17 COM2 Y10 Y11 Y12 Y13 Sink input FX5U 32MT ES 1 2 4 8 103 102 101 100 103 102 101 100 0 1A 50V diode is necessary Digital switch of BCD Transistor output sink S S 0V 24V X10 X11 X12 X13 X15 X14 X1...

Страница 147: ...Manual Instructions Standard Functions Function Blocks Example of program Example of wiring Sink wiring The example is the wiring for the input output of the FX5U 32MT ES Source wiring The example is the wiring for the input output of the FX5U 32MT ESS BIN SM400 K2X10 D102 X10 X11 X12 X13 X15 X14 X16 X17 1 2 4 8 1 2 4 8 101 100 FX5U 32MT ES S S 0V 24V Sink input X10 X11 X12 X13 X15 X14 X16 X17 1 2...

Страница 148: ...11 X12 X13 X14 X15 X16 X17 Y10 Y11 Y12 Y13 M30 M31 M32 M33 M34 M35 M36 M37 M40 M41 M42 M43 M44 M45 M46 M47 M50 M51 M52 M53 M54 M55 M56 M57 0 1A 50V diode is necessary Transistor output sink X11 X13 X15 X17 X12 X14 X16 X11 X13 X15 X17 X12 X14 X16 Sink input FX5U 32MT ES To use X0 to X17 of the input connect a pull up resistor 3 3 k 0 5 W S S 0V 24V X10 V2 X11 X12 X13 X14 X15 X16 X17 Y10 Y11 Y12 Y13...

Страница 149: ...he wiring for the input output of the FX5U 32MT ESS 1 Use a 7 segment display with a latch and a built in BCD decoder SEGL SM400 D100 Y10 K1 103 102 101 100 1 2 4 8 103 102 101 100 1 2 4 Y10 Y11 Y12 Y13 Y14 COM3 Y15 Y16 Y17 8 Transistor output sink 1 COM2 FX5U 32MT ES Signal Internal circuit Seven Segment with Latch Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor ...

Страница 150: ...input output of the FX5U 32MT ESS BCD SM400 D100 K2Y10 Y10 Y11 Y12 Y13 Y14 COM3 Y15 Y16 Y17 1 2 4 8 1 2 4 8 8 4 2 1 8 4 2 1 Signal Internal circuit Seven Segment with Latch Y COM1 PLC 7 segment display to be used for sink wiring in the case of transistor output COM2 FX5U 32MT ES Transistor output sink Fuse FX5U 32MT ESS Transistor output source Signal Internal circuit Seven Segment with Latch Y PL...

Страница 151: ...resistance test of the PLC should be measured in accordance with the following procedure 1 Remove all input output wires and power supply wires from the PLC 2 Connect a crossing wire to each of the PLC terminals power supply terminal input terminals and output terminals except the ground terminal For the dielectric withstand voltage test of each terminal refer to the generic specifications for the...

Страница 152: ...t in memory using the engineering tool GX Works3 Operating Manual 4 Parameter setting Set the parameters needed for startup GX Works3 Operating Manual System parameters CPU parameters Unit parameters 5 Programming Create a program using the engineering tool MELSEC iQ F FX5 User s Manual Application 6 Write the parameters and the program Write the parameters and the program set with the engineering...

Страница 153: ...e specified Click the CPU Module Direct Coupled Setting button on the Specify Connection Destination Connection window to display the CPU Module Direct Coupled Setting window Select the adapter on the window Connection via HUB GX Works3 settings No Item Selection item Internal setting Input value 1 PC side I F Ethernet Board 2 PLC side I F PLC Module Ethernet Port Direct Connection Other Station S...

Страница 154: ...53 Running Stopping and Resetting If any error is detected the ERR LED flashes or lights up Monitoring and debugging The ON OFF status of PLC s devices current values or set values can be monitored or changed by using engineering tools For details refer to GX Works3 Operating Manual No Item Selection item Internal setting Input value 1 PC side I F Serial USB RS 232C COM Port COM1 Transmission Spee...

Страница 155: ...tatus of the CPU module can be changed externally with the RUN STOP RESET switch set to the RUN position The operation status of the CPU module can be set to the PAUSE status Remote operation can be performed by either of the following methods Using contacts MELSEC iQ F FX5 User s Manual Application Using engineering tools GX Works3 Operating Manual Using external devices using SLMP MELSEC iQ F FX...

Страница 156: ...le connectors securely 3 LED status Check that the LED status is normal Page 159 Checking with LEDs User s manuals for each module Item Inspection item Description 1 Ambient environment Operating ambient temperature The temperature in the panel should be 20 to 55 1 Operating ambient humidity The humidity in the panel should be 5 to 95 RH Working atmosphere Free from corrosive or flammable gas and ...

Страница 157: ...hment The battery is not incorporated in the CPU module during shipment from the factory To use the battery attach it following the procedure below Parameter setting is required to back up the device memory and clock data using the battery Page 156 Setting an optional battery using the engineering tool Attachment procedure 1 Turn the power supply off 2 Remove the expansion board connector cover A ...

Страница 158: ... cover If an expansion board was removed in step 2 reinstall it Setting an optional battery using the engineering tool The following setting is required when the capacity of the latch device latch label is increased using the optional battery Note that the battery does not back up the data if the following setting is not provided Select the Navigation window Parameter FX5UCPU CPU Parameter Memory ...

Страница 159: ...anning for battery replacement please estimate the battery life according to the graph below and order replacement batteries in advance Replacement procedure If the battery voltage is reduced replace it following the procedure below Even with the battery removed the built in capacitor holds the data of the memory for the power interruption time 20 sec Battery replacement steps 3 and 4 must be comp...

Страница 160: ...te of manufacture How to read the battery lot number Special relay for low battery voltage Prepare a system which allows constant external monitoring of the battery status using a GOT etc SM52 SM8005 The special relay turns ON when the battery voltage is the specified value or less The special relay turns OFF when the battery voltage is normal SM51 SM8006 The special relay turns ON when the batter...

Страница 161: ...or and take corrective actions 9 2 Checking with LEDs Check the module status with LEDs as a means to perform the primary diagnosis Checking the PWR LED If the PWR LED is turned off check the following items If the PWR LED still does not turn on even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Checking the BAT LED If t...

Страница 162: ...y default setting has no programs the ERR LED flashes Set the CPU module to the STOP status and turn on the power supply again When the ERR LED turns off a watchdog timer error has probably occurred Take any of the following measures Review the program and avoid the maximum value SD524 SD525 of the scan time exceeding the the scan time monitoring time setting value set by the parameter Check that ...

Страница 163: ...Information required for troubleshooting such as the current error details and cause of the error and action to be taken are displayed The incorrect parameter setting and program error location can also be identified by selecting the error and clicking the Error Jump button On the Module Information List tab the LED status and the switch status of the target module can be checked Diagnostics Modul...

Страница 164: ... be displayed the error cause can be identified based on the errors The displayed information can also be saved in CSV file format Diagnostics Module diagnostics CPU Diagnostics Event History button Use the event history function to identify the cause of failure that occurred in facilities or devices For details on this function and collected information refer to the following MELSEC iQ F FX5 User...

Страница 165: ...ing engineering tools Using special relay SM Page 164 Canceling Errors Operation settings of the CPU module on occurrence of an intelligent function module error The operation of the CPU module on occurrence of an intelligent function module error can be set with the engineering tool Configure the settings with I O Assignment Settings in the system parameters Error status Program execution status ...

Страница 166: ...es and buffer memory using the engineering tool is explained below Online Read from PLC 1 Click the Device Memory check box 2 Click Detail 3 Input character strings in Device Data Name and select the devices to back up 4 Select the Buffer Memory Intelligent Module No and input module number 5 Click OK and then click Execute to read the data from the PLC 9 6 Canceling Errors Only continuable errors...

Страница 167: ...nal wiring properly Stop the PLC and check that the output turns off When the output turns off The output may be turned off unintentionally in the program Review user program Duplicate coils or RST instructions When the output does not turn off There may be a hardware fault Consult your local Mitsubishi Electric representative Item to check Action Disconnect the external wiring and connect the S S...

Страница 168: ...ation refer to MELSEC iQ F FX5 User s Manual Application Boot operation Boot operation cannot be performed from the SD memory card If the boot operation cannot be performed even after the items shown above are checked there may be a hardware issue Consult your local Mitsubishi Electric representative Item to check Action Check if a password is not registered When a password has been registered aut...

Страница 169: ...58 Reading the date of manufacture Ex Check on the module front surface The year and month of production of the product can be checked from the manufacturer s serial number LOT on the front at the bottom of the CPU module 4 1 X 0 0 0 Control number Year Example 2014 Last two digits of year 1 Month Example October 1 to 9 January to September X October Y November Z December Right side Example namepl...

Страница 170: ...to EMC directive and LVD directive of the entire mechanical module should be checked by the user manufacturer For more details please contact to the local Mitsubishi Electric sales site Requirement for compliance with EMC directive The following products have shown compliance through direct testing of the identified standards below and design analysis through the creation of a technical constructi...

Страница 171: ... DSS FX5 C1PS 5V from May 1st 2016 FX5U 32MR DS FX5U 32MT DS FX5U 32MT DSS FX5 32ER DS FX5 32ET DS FX5 32ET DSS FX5 16ET ES H FX5 16ET ESS H FX5 CNV IF FX5 30EC FX5 65EC FX5 CNV BC from October 1st 2016 FX5U 64MR DS FX5U 64MT DS FX5U 64MT DSS FX5U 80MR DS FX5U 80MT DS FX5U 80MT DSS FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 4AD PT ADP FX5 4AD TC ADP Electromagnetic compatibility EMC directive Remark...

Страница 172: ...readings This can be achieved either through functions on the analog devices or through a user s program in the FX5U CPU module Perform the following when using the analog expansion adapter Installation in Enclosure Control cabinet Cables It is possible that the accuracy temporarily fluctuates within 10 Perform the following when using the FX5 4AD ADP Set the number of times of winding to 2 turns ...

Страница 173: ...D The FX5 4DA ADP requires that the cable used for power supply is 30 m or less Caution for when the built in Ethernet port is used Use a shielded twisted pair cable for the 10BASE T or 100BASE TX cable Strip a part of the jacket of the shielded twisted pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cable Connect a ferrite core to both ends of t...

Страница 174: ... a resistor consider the maximum input current 2 For unused channels short circuit the V and V terminals Specifications 1 The digital output value can be changed using the scaling function Example of using the scaling signal For details of the scaling function refer to MELSEC iQ F FX5 User s Manual Analog Control CPU module built in Expansion adapter Item Specifications Analog input 4 to 20 mA DC ...

Страница 175: ...erating ambient temperature below 0 specifications are different from when used at an operating ambient temperature of 0 to 55 Device name FX5 40SSC S FX5 80SSC S FX5 CNV BUS FX5 CNV BUSC Battery FX3U 32BL SD memory card NZ1MEM 2GBSD NZ1MEM 4GBSD NZ1MEM 8GBSD NZ1MEM 16GBSD L1MEM 2GBSD L1MEM 4GBSD FX3 expansion module Terminal module Input output cable FX 16E 500CAB S FX 16E CAB FX 16E CAB R Item W...

Страница 176: ...minal block FX5 16EX ES 24 V DC 16 Terminal block Model Input Output Connection type Type No of points Common wiring system Type No of points Common wiring system Input extension sink input only FX5 C16EX D 24 V DC 16 Connector FX5 C32EX D 24 V DC 32 Connector Input extension sink and source input type FX5 C16EX DS 24 V DC 16 Connector FX5 C32EX DS 24 V DC 32 Connector I O module Input type Power ...

Страница 177: ...or 32 Connector Output extension source output only FX5 C16EYT DSS Transistor 16 Connector FX5 C32EYT DSS Transistor 32 Connector Model Input Output Connection type Type No of points Common wiring system Type No of points Common wiring system Input output extension sink and source input relay output only FX5 16ER ES 24 V DC 8 Relay 8 Terminal block Input output extension sink and source input sink...

Страница 178: ...ower supply DC input type FX5 32ER DS 24 V DC 16 Relay 16 Terminal block Input output extension sink and source input sink output only DC power supply DC input type FX5 32ET DS 24 V DC 16 Transistor 16 Terminal block Input output extension sink and source input source output only DC power supply DC input type FX5 32ET DSS 24 V DC 16 Transistor 16 Terminal block Model Input Output Connection type T...

Страница 179: ... power supply or external power supply 5 V DC supplied from PLC Output 24 V DC supplied from PLC 5 V DC supplied from PLC Current consumption 5 V DC FX5 16E E 100 mA FX5 C32ET 120 mA Current consumption 24 V DC FX5 16E E 125 mA 82 mA 1 FX5 C32ET Input 65 mA 2 Output 100 mA Item Specifications Voltage rating FX5 32E E 100 to 240 V AC FX5 32E D 24 V DC Allowable supply voltage range FX5 32E E 85 to ...

Страница 180: ...1 Item Specifications External color Munsell 0 6B7 6 0 2 Mass weight FX5 8E Approx 0 2 kg FX5 16E Approx 0 25 kg FX5 C16EX FX5 C16EYT Approx 0 1 kg FX5 C32EX FX5 C32EYT Approx 0 15 kg Accessories FX5 8E FX5 16E Dust proof protection sheet FX5 C32EX FX2NC 10BPCB1 Item Specifications Exterior color Munsell 0 6B7 6 0 2 Mass weight FX5 16E E Approx 0 25 kg FX5 C32ET Approx 0 15 kg Accessories FX5 C32E...

Страница 181: ...V DC Input impedance Other than FX5 16ET E H 5 6 kΩ FX5 16ET E H 4 3 kΩ Input sensitivity current ON Other than FX5 16ET E H 3 0 mA or more FX5 16ET E H 3 5 mA or more OFF 1 5 mA or less Input response frequency FX5 16ET E H X0 to 5 200 kHz X6 X7 10 kHz Input response time Other than FX5 16ET E H ON 50 μs or less OFF 150 μs or less FX5 16ET E H X0 to X5 ON 2 5 μs or less OFF 2 5 μs or less X6 X7 O...

Страница 182: ...ifications Source input wiring 0V 24V S S X S S Sink input wiring CPU module 0V 24V S S X S S CPU module Input module Input module Powered input output module Powered input output module 24V N L 100 to 240 V AC Fuse X S S 0V Source input wiring 24V N L 100 to 240 V AC Fuse X S S 0V Sink input wiring Input module Input module Source input wiring 0V 24V S S X S S Sink input wiring CPU module 0V 24V ...

Страница 183: ...ing value 4 output points common terminal 8 A or less 8 output points common terminal 8 A or less Open circuit leakage current Min load 5 V DC 2 mA reference values Response time OFF ON Approx 10 ms ON OFF Approx 10 ms Output circuit configuration Item Specifications No of output points FX5 8EYT ES 8 points FX5 16EYT ES 16 points FX5 16ET ES 8 points FX5 32ET S 16 points FX5 16ET ES H 8 points FX5...

Страница 184: ...T ES FX5 16ET ES FX5 32ET S 0 2 ms or less 200 mA at 24 V DC FX5 C EYT D FX5 C32ET D 0 2 ms or less 100 mA at 24 V DC FX5 16ET ES H Y0 Y1 Y4 Y5 2 5 μs or less 10 mA at 5 to 24 V DC Y2 Y3 Y6 Y7 0 2 ms or less 200 mA at 24 V DC Maximum frequency FX5 16ET ES H Y0 Y1 Y4 Y5 200 kpps Voltage drop when ON 1 5 V or less Y0 Y1 Y4 and Y5 of FX5 16ET ES H is 1 0 V or less Output circuit configuration FX5 EYT...

Страница 185: ... 0 8 A or less Open circuit leakage current 0 1 mA 30 V DC Min load Response time OFF ON FX5 EYT ESS FX5 16ET ESS FX5 32ET SS 0 2 ms or less 200 mA at 24 V DC FX5 C EYT DSS FX5 C32ET DSS 0 2 ms or less 100 mA at 24 V DC FX5 16ET ESS H Y0 Y1 Y4 Y5 2 5 μs or less 10 mA at 5 to 24 V DC Y2 Y3 Y6 Y7 0 2 ms or less 200 mA at 24 V DC ON OFF FX5 EYT ESS FX5 16ET ESS FX5 32ET SS 0 2 ms or less 200 mA at 24...

Страница 186: ... display LED output display LED Lit when input or output is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 Extension connector Connector for connecting the extension cable of an extension mo...

Страница 187: ...es whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 I O connectors Connector for connecting input signal cables or output signal cables 5 DISP switch Switches the display of smaller and larger numbers of the input display LED or output display LED Smaller number F Larger number L 6 Extension ...

Страница 188: ...t is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable used to connect the extension module 5 Extension connector Connector for connecting the extension cable of an extension module Without cover W 8 83 80 mounting hole pitch 90 2 4...

Страница 189: ... modules are powered or not Lit Powered Off Not powered or hardware error 3 I O display LED Lit when input or output is on 4 Input connector Connector for connecting input signal cables 5 Output connector Connector for connecting output signal cables 6 DISP switch Switches input output of the I O display LED Input IN Output OUT 7 Extension connector Connector for connecting the extension connector...

Страница 190: ...LED Lit when input is on 5 Output display LED Lit when output is on 6 Extension connector cover for next module Cover for protecting the extension connector cover for next module 7 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 8 Terminal block mounting screws Gradually loosen the left and rig...

Страница 191: ...t is on 2 POWER LED Indicates whether the input modules output modules is powered or not Lit Powered Off Not powered or hardware error 3 Pullout tab They are used when drawing out an extension cable 4 Extension cable Cable connected to extend modules 5 Extension connector Connector for connecting the extension cable of an extension module Without cover W 8 83 80 mounting hole pitch 90 2 4 5 mounti...

Страница 192: ...6 X 0 1 2 3 4 5 6 7 Lower numbers Higher number Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Lower numbers Higher number C O M 0 C O M 1 Y 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 Lower numbers Higher number V 0 V 1 X 0 1 2 3 4 5 7 6 Y 0 1 2 3 4 5 6 7 S S V Y4 2 3 V1 1 Y0 V0 5 6 7 Y0 1 2 3 Y4 5 6 7 V2 V3 FX5 32ET ESS X0 S S 0V 24V N L 1 2 3 4 5 6 7 X0 1 2 3 4 5 6 7 Y4 2 3 COM1 1 Y0 COM0 5 6 7 Y0 1 2 3 Y4 5 6 7 CO...

Страница 193: ... Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 Notch Smaller numbers Larger numbers Output Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM0 Input X0 X1 X2 X3 X4 X5 X6 X7 COM X0 X1 X2 X3 X4 X5 X6 X7 COM Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Notch Input X0 X1 X2 X3 X4 X5 X6 X7 COM0 X0 X1 X2 X3 X4 X5 X6 X7 COM0 Input X0 X1 X2 X3 X4 X5 X6 X7 COM1 X0 X1 X2 X3 X4 Notch X5 X6 X7 C...

Страница 194: ...PU module Page 20 Generic Specifications External color weight accessories Model W mm FX5 CNV IF 14 6 No Name Description 1 Extension connector for preceding module Connector for connecting the supplied extension cable that connects to the preceding module the CPU module side 2 Extension connector for next module Connector for connecting the extension connector of an extension module extension con...

Страница 195: ...liant with IEC61131 2 The SDHC memory card can be used only with devices with an SDHC logo or whose user s manual lists an SDHC logo Note that SDHC cards cannot be used with devices that support only SD specifications Turning off or resetting the CPU module or removing the SD memory card while the card is being accessed may corrupt the data in the SD memory card Always turn off or reset the CPU mo...

Страница 196: ... When SM605 mount and remove memory card disabling flag is ON the CARD LED is not turned OFF even if the SD memory card stop switch is pressed If the CARD LED is not turned OFF turn ON SM606 instruction of forcibly stop using SD memory card so that the SD memory card cannot be used 1 Insert the SD memory card 1 straight into the SD memory card slot Make sure that the notch of the card is directed ...

Страница 197: ...16 100 V AC input type FX5 C EX D FX5 C32ET D 24 V DC 48 mA FX 16EYR TB 16 Relay output type FX5 C EYT D FX5 C32ET D 24 V DC 80 mA FX 16EYT TB 16 Transistor output type sink 24 V DC 112 mA FX 16EYS TB 16 Triac output type Sink and source common input source output transistor output FX 16E TB UL 16 input points or 16 output points Directly connected to I O terminals of a PLC FX5 C EX DS FX5 C EYT D...

Страница 198: ...0 Hz Input sensitivity ON 3 8 mA 80 V AC or more OFF 1 7 mA 30 V AC or less Input response time 1 25 to 30 ms Input signal format Voltage contact Input circuit insulation Photo coupler insulation Indication of input operation No input LED However the 24 V power LED display exists Power consumption 1 2 W 48 mA 24 V DC Input output configuration circuit Unsupported applications High speed counter in...

Страница 199: ...rcuit Mechanical insulation Indication of output operation LED is lit when the power is supplied to relay coils Power consumption 1 92 W 80 mA 24 V DC Input output configuration circuit FX 16EYR TB FX 16EYR ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O fun...

Страница 200: ...sulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYT TB FX 16EYT ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN in...

Страница 201: ...ge of output element 1 5 V Insulation of circuit Photo coupler insulation Indication of output operation LED is lit when the power is supplied to photo couplers Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of...

Страница 202: ... Indication of output operation LED is lit when the power is supplied to photo thyristors Power consumption 2 7 W 112 mA 24 V DC Input output configuration circuit FX 16EYS TB FX 16EYS ES TB UL Unsupported applications Positioning Pulse Y Output D PLSY instruction Pulse Width Modulation D PWM instruction ABS Current Value Read DABS instruction Start stop of high speed I O function D HIOEN instruct...

Страница 203: ...for connecting input signal cables or output signal cables for CN2 FX 32E TB and FX 32E TB UL only 3 POWER LED Indicates the conduction status FX 16EX A1 TB only Lit Powered Off Not powered or hardware error 4 Operation display LED Turns on when the output is on FX 16EYR TB FX 16EYR ES TB UL FX 16EYT TB FX 16EYT ES TB UL FX 16EYT ESS TB UL FX 16EYS TB and FX 16EYS ES TB UL only 5 Terminal block fo...

Страница 204: ... 6 7 COM COM Smaller numbers Larger numbers CN1 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN2 0 1 2 3 COM COM 4 5 6 7 COM COM 0 1 2 3 COM COM 4 5 6 7 COM COM Smaller numbers Larger numbers CN1 CN2 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2 0 1 2 3 COM3 COM3 4 5 6 7 COM4 COM4 Smaller numbers Larger numbers 24 24 POWER 0 1 2 3 COM1 COM1 4 5 6 7 COM2 COM2...

Страница 205: ...19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 3 2 1 0 COM 7 6 5 4 3 2 1 0 CN1 1 COM 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM 7 6 5 4 3 2 1 0 0 COM 7 6 5 4 3 2 0 1 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB FX 32E TB 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers 5 4 1 ...

Страница 206: ...4 5 6 0 2 7 1 3 0 2 4 5 6 7 COM COM COM COM COM COM COM 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 0 COM0 7 6 5 4 3 2 0 1 1 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 4 1 2 COM0 7 6 5 4 3 2 1 0 COM0 7 6 5 4 3 2 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 FX 16E TB UL FX 32E TB UL 1 1 1 0 to 7 Smaller numbers 0 to 7 Larger numbers 0 to 7 Smaller numbers 0 to 7 Larger numbers CN2 ...

Страница 207: ...3 COM4 COM4 4 to 7 20 COM 6 7 5 4 3 2 1 0 COM 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 CN1 Photocoupler Photocoupler Photocoupler Photocoupler 0 to 3 0 to 3 4 to 7 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 0 to 7 Smaller numbers 0 to 7 Larger numbers 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 ...

Страница 208: ... COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 4 5 6 7 1 1 3 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 COM0 6 7 5 4 3 2 1 0 COM0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 2 2 2 2 0 to 7 Smaller...

Страница 209: ... V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 3 3 k 3 3 k 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo coupler Photo coupler 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 ...

Страница 210: ...5 6 7 3 3 k 3 3 k U U U U U Surge absorbers are connected to each output 3 3 k 3 3 k 0 to 7 Smaller numbers 0 to 7 Larger numbers 1 1 Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor Photo thyristor 1 3 4 5 6 0 2 7 1 3 0 2 4 5 6 7 24 24 COM1 COM1 COM2 COM2 COM3 COM3 COM4 COM4 20 V0 6 7 5 4 3 2 1 0 V0 6 7 5 4 3 2 1 0 10 19 9 18 8 17 7 6 5 4 3 2 1 16 15 14 13 12 11 0 1...

Страница 211: ...ot include batteries when shipped from the factory Battery only spare parts and optional parts 1 Weight in packaging Precautions for transportation When transporting the product above follow IATA Dangerous Goods Regulations IMDG Code International Maritime Dangerous Goods Code and domestic transportation regulations in each country For details contact the transportation company to be used Model Ba...

Страница 212: ...ry Directive 2006 66 EC Article 20 Information for end users and Annex II Exportation precautions The new EU Battery Directive 2006 66 EC requires the following when marketing or exporting batteries and or devices with built in batteries to EU member states To print the symbol on batteries devices or their packaging To explain the symbol in the manuals of the products Labeling To market or export ...

Страница 213: ...ating Manual for details on the software version Add Change Function Supported CPU module firmware version Supported engineering tool software version Reference High speed input output module is supported 1 030 and above 1 025B and above Page 42 FX5 CCLIEF is supported 1 030 and above 1 025B and above Page 43 Event history is supported 1 040 and above 1 030G and above Page 162 FX5 80SSC S is suppo...

Страница 214: ...over 17 Extension connector 18 Extension connector cover 17 G Genuine product certification label 19 I Input display LED 17 Installing directly 81 85 Installing on DIN rail 81 M Memory capacity 28 N Nameplate 19 Number of input output points 50 Number of remote I O points 57 O Output display LED 17 P P RUN LED 17 PWR LED 17 R RD LED 17 RS 485 terminal resistor selector switch 18 RUN STOP RESET swi...

Страница 215: ...I 213 MEMO ...

Страница 216: ...ESS TB UL FX 16EYS ES TB UL Added or modified parts RELEVANT MANUALS TERMS Section 2 1 2 2 2 3 2 8 2 10 3 1 3 2 3 3 3 4 3 9 Chapter 4 Section 5 1 5 2 5 4 5 5 6 1 6 2 6 4 6 5 6 8 9 7 Appendix 2 3 6 October 2016 E Added models FX5U 64MR DS FX5U 64MT DS FX5U 64MT DSS FX5U 80MR DS FX5U 80MT DS FX5U 80MT DSS FX5 16ER ES FX5 16ET ES FX5 16ET ESS FX5 80SSC S FX5 4AD PT ADP FX5 4AD TC ADP Applicable model...

Страница 217: ...tions in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies and applications in which a special quality assurance system is required such as for railway companies or public service purposes shall be excluded from the programmable controller applications In addition applications in which human life or property that could ...

Страница 218: ...nywire and ANYWIREASLINK is a registered trademark of the Anywire Corporation MODBUS is a registered trademark of Schneider Electric SA Phillips is a registered trademark of Phillips Screw Company SD logo and SDHC logo are trademarks or registered trademarks of SD 3C LLC The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company...

Страница 219: ......

Страница 220: ...0 JAPAN Specifications are subject to change without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission Manual number JY997D55301F Model FX5U U HW E Model code 09R536 ...

Отзывы: