Mirtone QuickStart

Front Panel Programming

Getting Started Guide

Revision 1

9JAN04

Содержание QuickStart

Страница 1: ...Mirtone QuickStart Front Panel Programming Getting Started Guide Revision 1 9JAN04...

Страница 2: ...figuration dialer strings 13 Running AutoLoop 16 Programming system options 18 Card configuration SLIC 20 Card configuration SLIC detectors 21 Card configuration SLIC modules 23 Zones and output group...

Страница 3: ...and output groups to further reduce programming time Zones are collections of circuits and devices you assign to match the building layout Specific messages and correlations entered at the zone level...

Страница 4: ...he database revisions in all panels are the same If they are not the system enters a trouble state and display an Incompatible Database message Be aware that any loss of power during an FPP session ma...

Страница 5: ...em and transmit CID Monitor sprinkler system waterflow and tampers and transmit CID Activate shut off gas valve upon alarm from kitchen hood system Activate relays for primary elevator recall and alte...

Страница 6: ...GSA CR Intelligent control relay 5 GSA CT2 Intelligent dual input module flow tamp 1 GSA CT1 Intelligent single input module kitchen hood system 1 GSA CT1 Intelligent single input module monitor Knox...

Страница 7: ...rmal message followed by monitor trouble Line Initialization and system trouble Unexpected Card messages Wait until the Line Initialization message clears before proceeding The Unexpected Card message...

Страница 8: ...tus 1 Time Date 1 AutoLearn 2 Reports 2 Reports 2 Edit Password 2 System 3 Test 3 Test 3 Restart 3 Cards 4 Login 4 Enable 4 Clear History 4 Zone 5 Disable 5 Configure 5 Outputs 6 Activate 6 ECP Port 6...

Страница 9: ...hrough the list to verify that all the cards installed in the system are listed If not check the connections and repeat steps 1 through 3 4 Press Menu twice then choose Program Configure Wait for the...

Страница 10: ...rt 3 Cards 3 Delete 3 Retry Count 4 Enable 4 Clear History 4 Zone 4 Accounts 5 Disable 5 Configure 5 Outputs 5 Default Msgs 6 Activate 6 Exit 7 Restore 8 Program 9 Login During the AutoLearn process t...

Страница 11: ...n you don t need to enter values for Rcvr 2 Prim and Rcvr 2 Sec 3 Choose Retry Count and enter the number of times the dialer should attempt to contact the CMS from 5 to 10 times Subscriber account nu...

Страница 12: ...0000 5 Choose Test abnormal and enter the abnormal test string for contact ID it s 160800000 6 Choose Test Time and enter the time the dialer will call in the test strings using 24 hour format 7 Choos...

Страница 13: ...correlations The default string will be used automatically The typical format for the Contact ID strings is XEEEGGPPP Where X Event qualifier 1 for activation 3 for restoration EEE Event code a three...

Страница 14: ...1 s of CMS 1 Alarm 1 Account 2 CMS Phone Number 2 Trouble 2 Active Msg 3 Retry Count 3 Supervisory 3 Restore Msg 4 Accounts 4 Exit 4 Exit 5 Default Msgs To set the dialer default message strings 1 Fr...

Страница 15: ...se Save and Sync If there are no remote annunciators in your actual project choose Save The system goes through its reboot process This completes the AutoLearning process for the panel If there is an...

Страница 16: ...s Menu and log in as a level 4 user 2 Choose Program Configure The system displays a message to advise you that it is initializing the SIGA devices Wait until this process finishes and the message is...

Страница 17: ...base has been saved the system goes through its reboot process After the reboot a System Normal message is displayed on the LCD The panel is now fully functional with default general alarm system prog...

Страница 18: ...enience of the building owners and for technicians servicing the system MAIN MENU PROGRAM CONFIGURE SYSTEM USER LABELS 1 Status 1 Time Date 1 AutoLearn 1 User Labels 1 Facility Name 2 Reports 2 Edit P...

Страница 19: ...arameters 1 From the Configure menu choose System ALM RST Inhib 2 From the Alarm Reset Inhi screen choose the desired value This sets the time for which these operations are inhibited after an alarm h...

Страница 20: ...Module 3 Wiring Class 4 Zone 4 Autoloop 4 Exit 5 Outputs 5 Accept Map 6 Exit 6 Exit To configure an SLIC card 1 Choose Cards Edit 2 Enter the address of the SLIC 3 From the SLIC menu choose Config Car...

Страница 21: ...ss shown is the one assigned to the device during the AutoLoop process Record this address on your device programming worksheet beside the device serial number The address of the device will be used i...

Страница 22: ...ice Instead when you create your zones shown later under Configuring Zones you can create a message for the zone that can contain multiple devices This can save you a lot of data entry time if individ...

Страница 23: ...e number manually with the panel keypad or by using the scanning wand Note The Config Module screen shows the module address and serial number The address shown is the one assigned to the module durin...

Страница 24: ...the panel front This brings you back the SLIC menu 12 Choose Exit from the SLIC menu This returns you to the Configure menu At this point all detector and module information as well as the basic syste...

Страница 25: ...output group can include signals relays and dialer strings It can contain one item or several items When a panel is AutoLearned any device that is configured as visual or audible is automatically assi...

Страница 26: ...choose Outputs 2 Choose Delete The system displays a list of the output groups 3 Choose output group 250 then press Enter on the panel Note Output group 249 contains responses for use with service gro...

Страница 27: ...is for the AH relays so the first relay could be address 01126 where 01 is the SLIC card address and 126 is the GSA CR relay address 5 From the Response Relay menu choose the rate at which you want t...

Страница 28: ...ut group Sometimes however an individual device needs to send its own dialer string The kitchen hood system monitor point in our example project has this requirement In this case a separate output gro...

Страница 29: ...nse Dialer menu choose Priority 8 From the Priority menu choose Life Safety Life Safety is used for any alarm input device 9 From the Response Dialer menu choose String enter the dialer string then pr...

Страница 30: ...ZONE TYPE ZONE EDIT ZONE MEMBERS 1 AutoLearn 1 Add 1 Alarm 1 Message 1 Device Address 2 System 2 Edit 2 Supervisory 2 Members 2 Enter Serial 3 Cards 3 Delete 3 Monitor 3 Output Group 3 Delete 4 Zone...

Страница 31: ...oup to which this zone is being correlated then press Enter on the panel This returns you to the Output Group menu 9 Press Menu on the panel This returns you to the Zone Edit menu 10 From the Zone Edi...

Страница 32: ...Choose Enable Loop Mapping 3 Enter the address of the SLIC After you enter the address the panel will begin mapping 4 Press menu to exit programming The screen should display a Mapping in Progress me...

Страница 33: ...ront Panel Programming Getting Started Guide 33 5 Exit the SLIC menu 6 Exit the Configure menu 7 Choose Save and Sync or just save if system does not have a remote annunciator The panel will go throug...

Страница 34: ...eventually get a Map Fault 2 Press Menu on the panel then log in 3 Choose Program Configure Cards Edit then enter the address of the SLIC card to which the device was added 4 From the SLIC menu choos...

Страница 35: ...l display a trouble for the missing device and possibly a Map Fault if mapping is enabled 2 Press Menu on the panel then log in 3 Choose Program Configure Cards Edit then enter the address of the SLIC...

Страница 36: ...the new device 2 Press Menu on panel then log in as before 3 Choose Program Configure Cards Edit Config Detector or Config Module 4 Choose Delete then enter the address or serial number of the old dev...

Страница 37: ...ng Started Guide 37 Menu tree The following diagram is a basic menu tree for front panel programming It does not show all possible choices but it does include the commands and options essential for fr...