Model RB-MD-1086                      

Replacement Main Controller 
Board Installation Instructions

   

These instructions are for models RB-MD-1086-200, RB-MD-1086-1000, and RB-MD-1086-2000.

Caution: To prevent damage to the boards, always hold them by the edges.

A.

Remove the old board

1.

Turn off the current main controller board.

2.

Shut down the panel and disconnect the power.

3.

Disconnect the power harness from the current main controller board.

4.

Disconnect the ribbon cable from the current main controller board, if it is present.

5.

Disconnect all input, output, and networking harnesses from the current main controller board.

6.

Unscrew the seven #8-32 screws that hold the current board in place.

B.

Attach the new board

1.

Secure the new board with the seven screws you removed in step 6.

2.

If there are any daughter boards attached to the old board, remove them, and then install them on 
the new board.

3.

Connect all the input, output, and networking harnesses to the new board.

4.

Connect the ribbon cable to the new board, if it is present.

5.

Connect the power harness to the new board.

C.

Set the RS-485 address

1.

Use DIP switches 1-6 to set the RS-485 network address. See LT-969 for details.

Each TX3 panel must have a unique RS-485 address.

See Figures 3, 4, and 5 for the location of the DIP switches.

Figure 1    RS-485 DIP Switch Settings

2.

Follow the instructions under D to set JW11.

3.

Follow the instructions under E or F depending on the kind of panel that you have.

Address 1

ON

OFF

Address 4

Address 2

Address 3

1

8

1

8

1

8

1

8

Содержание RB-MD-1086 Series

Страница 1: ...that hold the current board in place B Attach the new board 1 Secure the new board with the seven screws you removed in step 6 2 If there are any daughter boards attached to the old board remove them and then install them on the new board 3 Connect all the input output and networking harnesses to the new board 4 Connect the ribbon cable to the new board if it is present 5 Connect the power harness...

Страница 2: ...oard 4 Turn on the Touch Screen You are done If you need more help call us at 1 888 660 4655 F If you are installing RB MD 1086 on a non Touch Screen unit 1 Set DIP switch 7 to OFF See Figure 5 2 DIP switch 8 Set DIP Switch 8 OFF if the IP address is assigned using a DHCP server Set DIP switch 8 ON if the IP address is assigned using the TX3 Configurator software 3 Turn on the main controller boar...

Страница 3: ...On Off switch Power switch on front of door Mounting screws Mounting screws There are seven screws holding the main controller board in place Mounting screw Power connector JW11 RS 485 address Switch 7 ON DIP switches Power button Mounting screws Mounting screw Mounting screws There are seven screws holding the main controller board in place Power connector On Off switch JW11 ...

Страница 4: ...talling on a non Touch Screen unit There are seven screws holding the main controller board in place Mounting Screw Mounting Screw Ribbon Cable Mounting Screws On Off Switch Power Connector RS 485 address Switch 7 OFF DIP Switch Settings JW11 ...

Отзывы: