59
11.0
Configuration with the CFG-300 LCD
Service Tool
There are three methods of configuring the FA-300 LED Series Fire Alarm Panels:
•
Using the CFG-300 LCD Tool. See this chapter.
•
Using a PC or laptop computer with a UIMA converter module.
•
Using a PC or laptop computer with remote connection (must use fire alarm with built-in
UDACT).
This chapter describes how to configure an FA-300 LED Series Fire Alarm Panel with the
CFG-300 LCD service tool.
Table 12 Settings permitted in CAN/ULCS527
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in CAN/
ULCS527? (Y/N)
Possible settings\methods
Settings permitted in
CAN/ULCS527
Auto signal silence
timer
Y
Disabled or 5, 10, 15, 20, or
30 minutes
All
Table 13 Settings permitted in UL864
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in UL864, Standard for Control Units and Accessories for Fire Alarm Systems, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in UL864?
(Y/N)
Possible settings\methods
Settings permitted in
UL864
Auto signal silence
timer
N
Disabled or 5, 10, 15, 20, or
30 minutes
Disabled