MIOX RIO Zuni™ Operators Manual
P/N: 102-00094-I
Page 26
that have formed blockages
in the brine lines.
System faults immediately on
startup.
1.
Water or brine feed not
getting to system.
1.
Confirm brine and water
feeds are connected and all
valves in between supplies
and inlets are open.
Display Reads: VERY HIGH
CURRENT (Cell #1 or Cell
#2)
1.
Loss of water supply.
2.
Blockage of cell exit ports.
3.
Too much conductivity in
cell.
1.
Check water feed line to RIO
Zuni™ System.
2.
Turn system off, remove cell
exit port disconnects, and
remove any obstructions
within ports.
4.
Close the brine feed. Toggle
3X for 30 seconds each, let
third restart complete and
open brine feed.
Display Reads: VERY HIGH
CELL OX TEMP (Cell #1 or Cell
#2)
1.
Loss of water supply.
2.
Blockage of cell exit ports.
3.
Temperature sensor failure
1.
Check water feed line to RIO
Zuni™ System.
2. Turn system off, remove cell
exit port disconnects, and
remove any obstructions
within ports.
Display Reads: LOW FEED
WATER TEMP X˚F
1.
Feed water temperature too
low.
2.
Temperature sensor failure
1.
Increase feed water
temperature to above 50˚F
(10˚C) prior to restarting
system.
2.
Temporarily swap the
thermowell assemblies or
otherwise verify correct
temperature is being
displayed on the Rio Zuni,
Display Reads: HIGH BRINE
PUMP DUTY
1.
Low brine concentration.
2.
Brine pump air locked.
3.
Brine pump locked due to
debris.
4.
Brine line ruptured or
clogged.
5.
Controller board failure or
brine pump worn out.
6.
Cell life depleted
1.
Check the salt, water and
brine level in the brine tank.
Add salt to the brine tank to
salt fill level.
2.
Verify brine inlet valve is
open. Remove the tube on
the inlet to the brine pump
and purge the air from the
brine line.
3.
Remove debris from brine
pump.
4.
Replace peristaltic pump
brine line with provided
tubing.
5.
Verify pump turns by
removing the cover and
manually rotating the roller.
6.
Replace brine pump.
Display Reads: DELTA TEMP
CELL
1.
Blockage of fl ow through
cell (#1 or #2).
2.
Temperature sensor failure.
1.
Turn system off, remove cell
exit port disconnects and
remove any obstructions
within the ports.
2.
Replace temperature sensor.
3.
Verify temperature (inlet
oxidant temp).
Table 3 : General troubleshooting approaches
Содержание RIO Zuni 1
Страница 18: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 18 Figure 8 RIO Zuni Connections...
Страница 35: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 35...
Страница 36: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 36...
Страница 37: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 37...
Страница 38: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 38...
Страница 39: ...MIOX RIO Zuni Operators Manual P N 102 00094 I Page 39...