SNMP-SSL
29
UPS Shutdown
This menu allows you to modify the parameters associated with the shutdown events.
The available shutdown events are:
1.
AC Failed
: Utility power has failed
2.
Battery Low
: The battery capacity has reached a low level
3.
UPS Overload
: The output of the UPS is overloaded
4.
UPS Over Temperature
: UPS is overheating internally
5.
Weekly Schedule
: UPS Shutdown/Restore pre-set for each week
6.
Special Day
: UPS Shutdown/Restore pre-set on certain day
7.
EMD Temperature over Threshold
: The EMD has detected an out of tolerance
condition either a high or a low temperature
8.
EMD Alarm-1
: Alarm-1 sensor detects an active alarm.
9.
EMD Alarm-2
: Alarm-2 sensor detects an active alarm.
When a shutdown event has occurred, SNMP-SSL card will take the selected action as
define in the Shutdown Actions column. Available actions are:
a.
Disabled:
Action is disabled
b.
Warning:
Warning message will be broadcast to the connected clients
c.
Client Shutdown:
Warning message will be broadcast and shutdown command will
be sent to the connected clients. UPS will then go into a sleep mode
d.
UPS Turn Off:
Warning message will be broadcast and shutdown command will be
sent to both the connected clients and the UPS.
1.
Warning Period (Min):
Specifies the time when the Shutdown command will be sent
to the clients.
2.
1
st
Warning (Sec):
Specifies the time of the first warning message to be
broadcasted to the connected clients.
3.
Warning Interval (Sec):
Specifies the frequency of the next warning message.
4.
UPS Shutdown Delay (Sec):
The time the Shutdown command is sent out after the
event has occurred.
5.
Set Value:
Saves the settings.
Figure 4-5 SNMP-SSL UPS Shutdown