background image

19

18

WEAK/BAD/DISCONNECTED BATTERY

The UPS automatically tests the battery’s condition.  If the battery is weak, bad or
disconnected, the Weak/Bad/Disconnected Battery icon will illuminate and the alarm
will beep three times every five-minutes until the battery is reconnected, replaced or
passes a self test.  It is recommended that the UPS be allowed to charge overnight
before performing a battery test to confirm a Weak/Bad Battery condition.

OVERLOAD

When the amount of load attached to the UPS is > 106% of its power rating; the
Overload icon will flash Off and On, all of the LEDs in the Load Level Bar Graph will
be illuminated and the audible alarm will beep continuously.  This alarm will remain
on until the excess load is removed or the UPS’s self protection circuit shuts the
UPS down.  If the UPS shuts down because of an Overload condition, the UPS
must perform an Inverter function or a Self Test to clear the Overload Alarm.

ALARMS

ON BATTERY

When the UPS is operating on the batteries, the On-Battery icon will illuminate and
the audible alarm will sound one beep every ten-seconds.  The alarm will stop once
the UPS returns to the AC normal mode.

LOW BATTERY WARNING

When the UPS is operating on the batteries and the battery reserve is running low,
the audible alarm will sound two beeps every five-seconds.  This condition will con-
tinue until AC returns or the UPS shuts down from battery exhaustion.

UPS FAULT

When the UPS detects a hardware and/or internal fault, the Fault icon will illuminate
and the audible alarm will beep continuously.  The fault condition, in some instances,
may be reset by turning the UPS off and then on again.

POWER MONITORING SOFTWARE

The UPS comes with a Power Monitoring Software CD or you can go to our web
site at www.minutemanups.com/support, then look under Downloads, and then
Software Download Center.  Please download (Free of Charge) the latest version
of the Minuteman SentryHD software.  See the software CD for the installation of
the Power Monitoring Software.  

NOTE:  If you are using an External Battery

Pack with this UPS series, the UPS must be configured so that the UPS will
report the correct estimated runtime on the LCD screen and in the Power
Monitoring software and/or the SNMP card.  See the Power Monitoring soft-
ware or the SNMP card’s User's Manual to configure the UPS.

NOTE:  

The LCD backlight will illuminate for 20-seconds when the UPS switches

to the Battery mode.  When the UPS has an event and/or an error code the LCD
backlight will turn on and remain on to alert the user that an event has occurred.

(These items may require optional software or hardware)

Function

Factory
Default

Description

User Choices

Set
inverter
output
voltage

Shut-

down

Type

Set

audible

alarm

state

Enable/

Disable

auto

restart

Battery

life in

days

Battery

install

date

UPS ID Endeavor

Series

Date of

manufac-

ture

1826

Enabled

Enabled

Entire UPS

120VAC

Up to 64 charac-

ters to define the

UPS

Date of battery

replacement -

month/day/year

XX/XX/XXXX

Up to 5

characters

Enable

or

Disable

Enabled, at

low battery,

disabled

Entire UPS  or

UPS output

110, 120VAC

At first battery replacement, re-
set to reflect actual number of
days experience in your environ-
ment or leave factory default.

Enter the current date when

replacing batteries.

Use this function to uniquely

identify the UPS in your network

configuration.

Changes output voltage.

Enabled - the UPS will emit a short

beep when in the battery mode.

At Low Battery  the UPS will emit

two beeps from low battery warn-

ing until shutdown.

Disabled - Use only when soft-

ware is controlling the UPS or to

silence the alarm.

When  enabled, the UPS will

automatically restart from a low

battery shutdown when normal AC

returns.

Enable/

Disable

RPo

Disabled

Enable

or

Disable

Enabled - the UPS will be

powered off and  remain off until

the UPS is reset.

Entire UPS - Turns off the entire  UPS.
UPS Output -  Turns off the UPS's
output receptacles only.

Chapter 5: Configurable Parameters

   and Settings

Set
External
Battery
Pack

0

0 - 10

Configures the UPS so that it will

report the correct estimated runt-

ime on the LCD screen and in the

Power Monitoring software and/

or the SNMP card.

Enable/

Disable

ECo

Disabled

Enable

or

Disable

Enabled - the UPS will operate in

the Economy mode.

Содержание ED3000RTXL2U

Страница 1: ...User s Manual Endeavor LCD RTXL UPS Series Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000516 R2...

Страница 2: ...6 3 Installation 9 4 Operation 15 5 Configurable Parameters Settings 19 6 Obtaining Service 20 7 Troubleshooting 21 8 Replacing the Battery 22 9 Specifications 25 10 Limited Product Warranty 27 A1 De...

Страница 3: ...k Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected CAUTION To reduce the risk of electrical shock in conditions where the load equ...

Страница 4: ...3 To de energize the UPS completely disconnect the battery Life Support Policy As a general policy we do not recommend the use of any of our products in life support applications where failure or malf...

Страница 5: ...ght will turn on and remain on to alert the user that an event has occurred Chapter 2 Controls and Indicators The UPS output is off bPS EPo RPo E24 ECo PAS off The UPS output has been turned on The UP...

Страница 6: ...he locking and Always On receptacles Lab eled Load 3 do not support the Load Shedding Function NOTE The lo cking recptacle is not on all models 8 The input circuit breaker will trip in the event the l...

Страница 7: ...e units have been installed The rack may become unstable due to the weight distribution 2 The Rackmount Configuration is complete See Connecting your Equipm ent CONNECTING THE BATTERIES QUALIFIED SERV...

Страница 8: ...ng screws Slide the UPS down until its resting securely on the four retaining s crews 7 Tighten the four retaining screws to secure the UPS to the wall 8 The Wallmount Configuration is complete See Co...

Страница 9: ...PTIONAL Connect one end of the RJ11 cable to the EPO port and the other end of the RJ11 cable to the EPO switch In the AC or the Battery mode short pin4 to pin5 for approximately 0 5 seconds to shutdo...

Страница 10: ...ad 3 does not support the Load Shed ding Function TURNING THE UNIT ON OFF On Off Test Button When the UPS is connected to an AC source and there is an acceptable AC volt age present Press and release...

Страница 11: ...are using an External Battery Pack with this UPS series the UPS must be configured so that the UPS will report the correct estimated runtime on the LCD screen and in the Power Monitoring software and...

Страница 12: ...n though there isAC present The AC normal icon is illumi nated but there is no output Disconnect the computer cable from the UPS press the On but ton If UPS works normally the software has control of...

Страница 13: ...f batteries in a fire The batteries may explode The batteries in this UPS are recyclable Dispose of the batteries properly The batteries contain lead and pose a hazard to the environment and human hea...

Страница 14: ...ent Short Circuit Protected and Latching Shutdown True Sine Wave Frequency 50 60Hz 0 5Hz unless synchronized to utility Nominal Voltage Adjustable Maximum Power Capacity 0 ms Typical 90 Full Load Rese...

Страница 15: ...cus tomer pays for shipping the product to Para Systems Para Systems pays ground freight to ship the product back to the customer Replacement parts and warranty labor will be borne by Para Systems For...

Страница 16: ...XL2U Y ED3000RTXL2U Y I hereby declare that the equipment specified above conforms to the above Directive s Place Carrollton Texas USA Date February 1 2017 Robert Calhoun Name Manager Engineering Posi...

Отзывы: