Minuteman E1000RM1U Скачать руководство пользователя страница 1

User's Manual

Enterprise 1U

Rackmount Series

Содержание E1000RM1U

Страница 1: ...User s Manual Enterprise 1U Rackmount Series ...

Страница 2: ...l 1 Introduction 2 2 Controls and Indicators 6 3 Installation 8 4 Operation 12 5 Troubleshooting 15 6 Replacing the Battery 16 7 Obtaining Service 19 8 Specifications 20 9 Configurable Parameters Settings 22 10 Limited Product Warranty 23 11 Declaration of Conformity 25 English ...

Страница 3: ...d maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance Included is information on customer sup port and factory service if it is required If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the MINUTEMAN Technical Sup port De...

Страница 4: ...rounding AC wall outlet The receptacle must be connected to the appropriate branch protection circuit breaker or fuse Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes Do not use extension cords adapter plugs or surge strips English CAUTION To reduce the risk of electrical shock with the installa tion of this UPS equipment and the connected ...

Страница 5: ...ts are designed to provide reasonable protection against such interference in a residential installa tion This equipment generates and uses radio frequency and if not installed and used properly that is in strict accordance with the manufacturer s instruc tions this equipment may cause interference to radio and television reception If this equipment does cause interference to radio or television r...

Страница 6: ...ty of Para Systems Inc is adequately protected under the circumstances Examples of devices considered to be life support devices are neonatal oxygen analyzers nerve stimulators whether used for anesthesia pain relief or other purposes auto transfusion devices blood pumps defibrillators arrhythmia detectors and alarms pacemakers hemodialysis systems peritoneal dialysis systems neonatal ventilator i...

Страница 7: ...s The Buck yellow LED illuminates in a blinking state when the UPS is operating in the Buck mode The Buck LED will extinguish when operating in the AC normal Boost and Battery modes The Fault red LED illuminates in a steady state when the UPS detects an internal fault The Fault LED is extinguished when the UPS is operating properly The Weak Bad Battery red LED illuminates in a steady state when th...

Страница 8: ...en it will extinguish LED 70 70 battery capacity green yellow LED will be yellow and illuminated until the battery s capacity drops below 60 ca pacity and then it will extinguish LED 50 50 battery capacity green yellow LED will be yellow and illuminated until the battery s capacity drops below 40 ca pacity and then it will extinguish LED 30 30 battery capacity green red yellow LED will be yel low ...

Страница 9: ... F Storage Elevation 0 to 15 000m 0 to 50 000 ft REAR PANEL 1 The input power cord has a NEMA 5 15P Plug 2 The input circuit breaker will trip in the event the load exceeds the UPS s power rating 3 The Battery Backup output power receptacles are NEMA 5 15R type The output receptacles are electrically wired into two segments to support the Load Shedding Function The three receptacles on the left ar...

Страница 10: ...nstalling the UPS Connecting the Batteries 1 Remove the UPS from the shipping box and set on the floor or a bench top 2 Grasp the front panel and gently pull it off the UPS FIG 1 3 Remove the four retaining screws for the battery retaining bracket FIG 2 4 Remove the battery retaining bracket FIG 2 5 Grasp the battery tray and gently pull the battery tray out far enough to get to the battery connec...

Страница 11: ...y for normal operation see connecting your equipment Installing the UPS in a 2 post rack USE CAUTION The UPS is heavy Use the appropriate number of personnel when installing the UPS MINUTEMAN recommends that the UPS be installed at the bottom of the rack and that the rack ears be installed as FIG 4 1 Install the rack ears on the UPS FIG 4 NOTE If you are installing the rack ears in the middle of t...

Страница 12: ...ll be monitoring controlling the UPS NOTE Connecting to the Communications Port is optional The UPS works properly without this connection CONNECTING THE UPS TO AN AC SOURCE Plug the UPS into a two pole three wire grounded receptacle only Do not use extension cords adapter plugs or surge strips NETWORK PHONE FAX MODEM PROTECTION CONNECTION OPTIONAL Connect a 10 100 Base T network single line phone...

Страница 13: ...ial power is lost or unacceptable When the commercial power re turns or is at an acceptable level the UPS will automatically transfer back to the AC normal mode and start recharging the batteries During an extended outage when there is approximately two minutes of backup time remaining the audible alarm will sound twice every five seconds This Low Battery Warning is letting the user know that they...

Страница 14: ... of the batteries With the UPS in the AC normal mode press and hold the On Off Test Button for four beeps then release the button The UPS will perform a ten second self test During the self test the UPS will switch to battery power and the On Battery LED will illuminate and the audible alarm will sound The length of the test that is automatically performed every two weeks is longer than the start ...

Страница 15: ...und the alarm This alarm will be repeated until the batteries pass a self test If the battery is weak bad or disconnected the Weak Bad Battery LED will illuminate and the alarm will beep three times every five minutes until the battery is reconnected or replaced It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak Bad Battery condition NO...

Страница 16: ...ns port Site Wiring Fault LED is illuminated Have a Qualified Electrician correct the service wiring The batteries may be weak or at the end of useful service life Charge the batteries for 8 hours and retest If the runtime is still less than expected the batteries may need to be replaced even though the Weak Bad Battery LED is not illuminated UPS does not provide expected runtime Weak Bad Battery ...

Страница 17: ...resent a risk of electrical shock These batter ies produce sufficient current to burn wire or tools very rapidly producing molten metal Observe these precautions when re placing the batteries 1 Remove watches rings or other metal objects 2 Use hand tools with insulated handles 3 Wear protective eye gear goggles rubber gloves and boots 4 Do not lay tools or other metal parts on top of batteries 5 D...

Страница 18: ...F 3 Unplug the UPS s AC power cord from the AC wall outlet 4 Unplug the equipment from the output receptacles of the UPS 5 Unplug the computer interface cable from the rear panel of the UPS 6 Grasp the front panel and gently pull the front panel off the UPS FIG 2 7 Lay the front panel on top of the UPS E700RM1U E1000RM1U Battery Qty Rating 4 6V9Ah 4 6V9Ah E1500RM1U 4 6V9Ah Model Replace batteries ...

Страница 19: ...fy proper polarity Re install the battery jumper wires on the new batteries 17 Slide the battery tray into the UPS 18 Verify proper polarity Re connect the battery connectors red and black NOTE Some sparking might occur this is normal 19 Re install the battery retaining bracket 20 Re install the four retaining screws for the battery retaining bracket 21 Re install the front panel on the UPS 22 Pro...

Страница 20: ...ssible F A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Material Authorization Number RMA G If the UPS is under warranty the repairs will be done at no charge If not there will be a charge for repair 4 Pack the UPS in its original packaging If the o...

Страница 21: ...voltage E1500RM1U E1000RM1U E700RM1U Model Number SYSTEM SPECIFICATIONS Voltage Range Topology Line Interactive Sine Wave OUTPUT NON BATTERYOPERATION INPUT Number of Phase Single 1 2W G Nominal Voltage 120VAC Low Voltage Transfer Point 85V resets to Utility Power at 90V or higher High Voltage Transfer Point 150V resets to Utility Power at 145V or lower Voltage Regulation 120VAC 12 5 10 127VAC 17 3...

Страница 22: ...st Noise filter Surge voltage let through as a percentage of an applied ANSI C62 41 Cat A 6 kV Surge response time Surge current capability Surge energy rating 800 J 0 ns instantaneous normal mode 5 ns common mode 5 Normal and common mode EMI RFI suppression 45 dBA 1 5 6500 Amps total ENVIRONMENTAL Operating Temperature max Operating Storage Humidity Operating Elevation 0 to 40 C 32 to 104 F 95 No...

Страница 23: ... number of days experience in your environment or leave factory default Enter the current date when replacing batteries Use this function to uniquely identify the UPS in your network configuration Changes output voltage for bat tery mode operation Enabled the UPS will emit a short beep when in the battery mode At Low Battery the UPS will emit two beeps from low battery warning until shutdown Disab...

Страница 24: ... properly registered the product within 10 days of purchase The warranty shall be void if a the equipment is damaged by the customer is improperly used is subjected to an adverse operating environment or is oper ated outside the limits of its electrical specifications b the equipment is re paired or modified by anyone other than Para Systems or Para Systems ap proved personnel or c has been used i...

Страница 25: ...es or otherwise The sole and exclusive remedy for breach of any warranty expressed or implied concerning Para Systems s prod ucts and the only obligation of Para Systems hereunder shall be the repair or replacement of defective equipment components or parts or at Para Systems s option refund of the purchase price or substitution with an equivalent replace ment product This warranty gives you speci...

Страница 26: ...lton Texas 75007 USA Type of Equipment Uninterruptible Power Supplies UPS Model No E700RM1U Y E1000RM1U Y E1500RM1U Y I the undersigned hereby declare that the equipment specified above conforms to the above Directive s Place Carrollton Texas USA RobertCalhoun Signature Date August 1 2005 Robert Calhoun Name Manager Engineering Position Year of Manufacture Beginning August 1 2005 EN55022 EN55024 E...

Страница 27: ...26 English Notes ...

Страница 28: ...Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000256 Rev 1 ...