background image

8

frequency shift will cause the "AC Fault" light to turn yellow and a blown fuse or tripped circuit
breaker will cause the fuse/breaker light to illuminate (RED).

The audible alarm can be silenced in both the "Normal Inverter" and the "Low Battery Warning"
modes by depressing the "Test/Alarm Silencer Switch" toward the "Alarm Silencer" position.  The
alarm will automatically reset upon return to the "AC Normal" mode, providing an audible
indication of the next power problem.   For long duration power outages or problems, the unit will
provide a low battery warning a minimum of two (2) minutes prior to low battery shutdown.  At low
battery warning the "Battery Status" light will turn yellow and the audible alarm will turn back on, if
silenced previously.  The alarm speed at low battery warning is more rapid -- four (4) times per
second.

If you have not already saved your data and turned off your critical loads, you must do so at this
time.  The UPS will shut off automatically to protect the internal batteries form excessive
discharge.  However, to conserve battery power you can turn off the UPS power switch after your
data is saved and loads are ready to be turned off.  When commercial power is restored, switch
the MINUTEMAN power switch back on if it was turned off previously. The "AC Normal" LED will
come on after a short delay.  Return your system to operations and the MINUTEMAN System will
automatically recharge the internal batteries during system operation.

Since most commercial power outages are of short duration, commercial power will probably be
restored before the low battery warning.  IF COMMERCIAL POWER RETURNS BEFORE THE
WARNING SIGNAL, THERE IS NO NEED TO SHUT DOWN YOUR SYSTEM AT ALL.  The
MINUTEMAN will switch back to normal AC mode operation automatically.

During normal AC mode operation, the MINUTEMAN unit will quietly protect your system form
power surges, voltage spikes and noise interference.  No alarms will sound and the "AC Normal"
indicator light will remain "ON'" during this operation.

SYSTEM BATTERIES

The batteries used internally in AT Series MINUTEMAN units are sealed, maintenance free, lead-
acid batteries with electrolyte totally absorbed in the plates and separator material.  These
batteries can be used in any position, except upside down.  For maximum battery life, batteries
should be maintained at as cool a temperature as is practical indoors at proper trickle charge
voltage.  The most effective charging temperature range is 41ºF to 95ºF.  However, batteries can
be charged within the range of 32ºF to 104ºF (0ºC to 40ºC) without any detrimental effects.
Expected float life of the batteries is 3 to 6 years at 85ºF.  We recommend replacement after 3
years of use.  Replacement batteries can be purchased from Para Systems, Inc. or from your
local distributor or dealer.  If the UPS must be stored, leave it plugged in with commercial power
applied and the power switch on for 24 hours prior to storage.  Store the unit in a cool dry
location.  For extended storage the unit must be removed from storage and recharged as above
every 4 months.

If batteries require replacement, refer to the "Important Safety Instructions" section on page 1 of
this manual.  A trained service technician who is familiar with batteries and UPS systems must
accomplish replacement.  Used batteries should be provided to a recycling center for reclamation
of the lead.

Содержание AT1200

Страница 1: ...MODELS DESCRIBED IN THIS MANUAL AT650 GS650 650VA AT800 GS800 800VA AT1200 GS1200 1200VA AT1600 GS1600 1600VA AT2300 GS2300 2300VA OWNER S MANUAL...

Страница 2: ...Physical Specifications 4 Unit Description 5 GS Models 6 Installation and Preliminary Testing 6 Load Testing 7 Operation 7 System Batteries 8 Battery System Checkout 9 UPS Monitoring Configurations 9...

Страница 3: ...TRATION Locate your warranty registration card in the back of this manual and complete and return within 10 days of receipt of the unit s to register your warranty Failure to register your warranty re...

Страница 4: ...igh short circuit current The current capability of each battery system is sufficient to burn large wire or tools very rapidly producing molten metal The following precautions should be observed when...

Страница 5: ...00 800 560 50 220 4 0 220 3 6 48 8 20 382 AT1200 1200 840 60 120 11 1 120 10 0 48 7 18 573 GS1200 1200 840 50 220 6 1 220 5 5 48 7 18 573 AT1600 1600 1120 60 120 14 8 120 13 3 72 8 20 765 GS1600 1600...

Страница 6: ...er Crest Factor Non Linear Load 3 1 Inverter Waveform Synchronized Computer Grade Sinewave Harmonic Distortion Less than 3 THD at full linear load Inverter Voltage Regulation Static 3 Dynamic 5 with 5...

Страница 7: ...Audible Noise 40 dB ANSI Scale A at 3 UNIT DESCRIPTION AT SYCHRONIZED SINEWAVE MODELS 1 Power Switch 2 Alarm Silencer Test momentary rocker switch 3 AC Normal LED Green On when commercial voltage is...

Страница 8: ...15P Plug standard or AWG 12 3 SJT AT2300 with NEMA L5 30P Plug 11 Input Fuse Holder Breaker At650 AT800 and AT2300 units use fuse and fuse holder at input AT1200 and AT1600 units use AC circuit break...

Страница 9: ...r This testing should be repeated 5 to 10 times 3 Verify that UPS and load functions were proper during this testing see items under INSTALLATION AND PRELIMINARY TESTING for UPS function If all functi...

Страница 10: ...y warning IF COMMERCIAL POWER RETURNS BEFORE THE WARNING SIGNAL THERE IS NO NEED TO SHUT DOWN YOUR SYSTEM AT ALL The MINUTEMAN will switch back to normal AC mode operation automatically During normal...

Страница 11: ...ystems also offers its own software package Network Manage which functions with Novell Unix OS 2 LAN Manager LAN Server and MacIntosh Operating Systems Network Manager offers many advantages over exis...

Страница 12: ...mon problems Do not remove the unit cover or attempt to service this unit There are no user serviceable components inside Unauthorized service will void the warranty COMMON UPS PROBLEMS No normal AC m...

Страница 13: ...Other packaging methods can result in damage to the unit Enclose the name and telephone number of the person who can authorize repair charges inside the carton or packing list folder Also include you...

Страница 14: ...INDIRECT INCIDENTAL CONSEQUENTIAL OR OTHER TYPES OR DAMAGES RESULTING FROM THE USE OF THIS PRODUCT OTHER THAN THE LIABILITY STATED ABOVE THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTIES EXPRESSED OR I...

Отзывы: