background image

 

 

 
 
 
 
 
 
 
 

ALLIANCE SERIES 

 
 
 

OWNER'S MANUAL 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание A1250

Страница 1: ...ALLIANCE SERIES OWNER S MANUAL ...

Страница 2: ...L SPECIFICATIONS 3 6 TYPICAL RUN TIME VERSUS LOAD 5 7 PHYSICAL SPECIFICATIONS 5 8 UNIT DESCRIPTION 6 9 INSTALLATION AND TEST 7 10 OPERATION 8 11 SYSTEM BATTERIES 8 12 BATTERY SYSTEM CHECKOUT 9 13 UPS MONITORING CONFIGURATIONS 9 14 UPS DB9 PIN OUT 9 15 SERVICE 10 16 UPS PROBLEM CHART 10 17 POLICY AND INSTRUCTIONS FOR RETURN OF PRODUCT 11 ...

Страница 3: ...st to facilitate low commercial voltage operation without battery utilization except A300 A425 Transfer voltage adjustment switches except A300 A425 RECEIVING INSPECTION SAVE THE PACKING MATERIALS Remove and inspect the unit for shipping damage If damage is found immediately notify the carrier and your dealer If no damage is found save both the shipping container and the packing foam in case of a ...

Страница 4: ... is removed On 120 volt models improperly connected power will indicate a Site Wiring Fault CAUTION Do not allow water or any foreign object to enter the UPS In case this occurs immediately turn the unit power switch off and unplug the MINUTEMAN from the commercial receptacle Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautio...

Страница 5: ...5 A900 900 630 60 120 8 8 120 7 5 24 540 130 A900 2 900 630 50 220 4 2 220 4 1 24 540 130 A1250 1250 900 60 120 12 1 120 10 4 24 770 185 A1250 2 1250 900 50 220 5 8 220 5 7 24 770 185 A2000 1440 1400 60 120 12 120 12 36 1200 300 A2000 41 1900 1400 60 120 16 120 15 8 36 1200 300 A2000 43 1900 1400 60 120 16 120 15 8 36 1200 300 A2000 44 2000 1400 60 120 20 120 16 7 36 1200 300 A2000 2 2000 1400 50 ...

Страница 6: ...ation for Synchronization 10 Inrush Current 1 5x rated Surge Protection 3 way meets IEEE STD 587 RFI EMI Filtering Both Common and Normal Modes Inverter mode Backup Operation Synchronized Simulated Waveform Sinewave Approximation Crest Factor Non Linear Load 3 1 Overload Capacity 50 msec Maximum 3x rated Voltage Regulation 5 Frequency Regulation 1 DC to AC Efficiency Full Load 75 Overload Short Ci...

Страница 7: ...m 47m 500VA 6m 9m 15m 16m 37m 600VA 7m 12m 13m 28m 700VA 6m 10m 11m 23m 750VA 5m 9m 10m 21m 800VA 8m 9m 19m 900VA 7m 8m 16m 1000VA 7m 14m 1100VA 6m 12m 1250VA 5m 10m 1400VA 8m 1600VA 7m 1800VA 6m 2000VA 5m PHYSICAL SPECIFICATIONS Model Net Wt lbs Shipping Wt lbs Dimensions L x W x H inches A300 15 18 13 5 x 3 3 x 6 A425 15 18 13 5 x 3 3 x 6 A500 23 25 13 x 4 6 x 6 6 A750 29 30 16 x 4 6 x 6 6 A900 ...

Страница 8: ...n Inverter mode LED illuminates momentarily along with the audible alarm If UPS goes to low battery overload or software generated shutdown while in Inverter mode UPS shuts down On AC return UPS goes to AC mode and Fault and Alarm operate continuously The Fault is reset either by pressing Test or any subsequent loss of power and successful return to AC During normal Inverter mode alarm sounds once...

Страница 9: ...e are available through your supplier Units ordered from the factory with an input line cord provided contain only 1 output power cord INSTALLATION AND TEST 1 Ensure that the UPS power switch is off position On models with an IEC 320 input socket insert the cord set supplied or the computer cord set into the UPS socket then plug the UPS power plug into a grounded commercial power receptacle with p...

Страница 10: ...usually of a short duration thus sounding of the alarm is delayed so as not to be a nuisance If the low voltage condition above can be corrected by the boost winding in all models except A300 and A425 the Boost LED will light signifying the Boost mode is operative and the output voltage has been corrected SYSTEM BATTERIES The internal batteries used in the MINUTEMAN ALLIANCE UPS UNITS are sealed m...

Страница 11: ...formation The standard UPS DB9 PIN out is provided below for your information COMMUNICATIONS PORT The communications port on the back of the UPS DB9 Female Connector labeled Signal can be connected by a cable to a computer to provide the UPS monitoring capability described above Following are the pin connections of this connector UPS DB9 PIN OUT PIN 1 N C PIN 2 UPS simulates a relay closing open c...

Страница 12: ...use blown breaker tripped on A2000 No commercial power at wall receptacle or commercial voltage is too low or too high Check fuses and replace if blown see below Reset A2000 breaker Verify proper available commercial voltage When main power switch is turned on UPS comes on goes to AC Normal mode Fault LED and Alarm operate continuously UPS batteries are Low Weak UPS is overloaded Turn UPS off and ...

Страница 13: ... RMA This number must be placed on the shipping carton preferably on the return shipping label The RMA on the carton will ensure prompt handling when received at Para Systems Inc b Pack the UPS for shipment in the original carton and foam Other packaging methods can result in damage to the UPS c Be sure to enclose the name and telephone number of the person who can authorize repair charges Also in...

Страница 14: ...onnected to and powered by the UPS and registered under the Minuteman Platinum Protection Plan shall be protected from damage caused by AC power surges subject to the following terms and conditions Para Systems or its designated representative will at Para Systems option repair or replace any equipment so damaged provided the cost of repair or replacement of the equipment does not exceed twenty fi...

Страница 15: ...e if applicable _______________________________________________ Address ________________________________________________________________ City State __________________________________ Zip __________________________ CONNECTED EQUIPMENT Necessary for Platinum Protection 1 MFG _______________________ Model ____________________ Serial ________________ 2 MFG _______________________ Model _______________...

Отзывы: