“V
ENTILATION
”
SETTINGS SCREEN
(
CONT
’
D
)
Figure 39
–
Examples of options to adjust exhaust airflow.
1.8 Exhaust airflow relative to intake airflow:
o
90% to 110 %.
Set the exhaust fan airflow to make it lower or higher than
the intake fan airflow in order to balance the airflows with greater accuracy.
See "Balancing the MINOTAIR" for more information.
NOTE:
This is an advanced setting and only ventilation professionals
equipped with proper measuring equipment should adjust it.
“V
ENTILATION
”
SETTINGS SCREEN
(
CONT
’
D
)
Figure 40
–
Examples of options to adjust the maximum airflow.
1.9 Maximum Airflow:
o
250 cfm
–
180 cfm (120 l/s
–
85 l/s).
Adjust this setting to the highest
airflow rate that will allow the static pressure to remain lower than or equal
to 1.6" WC when the unit is operating in either Air Exchanger mode and
Recirculation mode at High speed. Start by setting the Minotair to
Recirculation mode at High speed with a Fresh Air setpoint of
125 cfm (60 l/s), i.e. will run at 250 cfm (120 l/s) at High speed. Adjust for the
highest airflow by waiting 30 seconds between each adjustment. Once you
are satisfied with the setting, trigger the bathroom timer to switch to Air
Exchanger mode. Readjust the maximum airflow setting downward if the
static pressure becomes higher than 1.6" WC. Once done, do not forget to
readjust the Fresh Air setting as required.
o
See next page to determine the static pressure.