47
(PENTACARE-V12-OWNER'S MANUAL-2019-Rev-014)
“V
ENTILATION
”
SETTINGS SCREEN
(
CONT
’
D
)
Figure 37
–
Examples of options to adjust the default bathroom timers and recirculation speed.
1.4 Recirculation Mode Default Speed:
o
LOW
. Ventilation speed will be equal to the configured fresh air setpoint in
the previous “Ventilation” screen
, but never less than 80 cfm (40 l/s).
o
HIGH
. Ventilation speed will be double the configured setpoint in the
previous
“
V
entilation” screen,
but not more than
the device’s
upper limit
and but never less than 80 cfm (40 l/s).
1.5 Bathroom Timers and Shower Detector Default Speed:
o
TURBO
. Ventilation speed will be the maximum airflow rate allowed by the
machine 180 cfm
–
250 cfm (85 l/s
–
120 l/s). This cannot be changed.
“V
ENTILATION
”
SETTINGS SCREEN
(
CONT
’
D
)
Figure 38
–
Examples of options to adjust winter limits.
1.6 Air exchanger mode outside temperature limit:
o
-30°C to 0°C (-22°F to 32°F).
This setting applies to air exchanger mode
during winter months. Set the minimum outside temperature at which the
device will stop ventilation in air exchanger mode. The device will then
switch to recirculation mode and display an exception symbol [
!
].
1.7 Indoor humidity too low:
o
YES.
When indoor humidity drops below setpoint, the device will stop
ventilation in air exchanger mode. The device will then switch to
recirculation mode and display an exception [
!
].
o
NO.
When indoor humidity drops below setpoint, the device will continue
to ventilate per normal but at the risk of further drying out the indoor air.
1.4
1.5
1.6
1.7