background image

SAVE THESE INSTRUCTIONS

GENERAL INFORMATION \ INSTALLATION

The TH-0023 digital thermostat provides precise
control for variety of 2 and 4 pipes fan coil system,
unit ventilators, dampers and other apparatus used in
commercial or residential applications.

This series features large LCD display, showing
temperature reading/setpoint, and variety of
configuration to meet application demands.

TH-0023 Fancoil Thermostat

Features

■Digital temperature display.
■Non-programmable,simple to wire,

easy temperature set-up.

■selectable continuous and cycling

fan switch.

■3-minute shortest cycle rate protection

for protecting compressor from too frquent
turned on-/Off, to avoid energy waste.

■Easy one touch button to set Comfort

& Economy

setpoint

■ High output contact rating with circuitry surge

absorber.

■Stand-by

function included for simple shut-off

Coo\Heat system when temperature regulation
is not required.

Choose correct location for thermostat

DANGER

Electric Shock Or Fire Hazard

Read all wire sizing, voltage requirement
and safety Data avoid property damage and
personal injury

Remove front cover using a
screw to press the cover
latch at top of front cover

Disconnect the main
before installation

Remove cover by holding
base and front cover.

Use screwdriver to remove
terminal protection cover

Mount base with wires
through the holes of the base
than mount the base with
screws(supplied) on the wall.

Install the wires into terminal
blocks, and mount back
terminal block.

Before wiring, you must check your system wiring
diagram. If your system differs from standard
wiring, please check with your local dealer
or consult with professional electrician.

Technical Data

1.Power supply : Switching power 24 Vac / 240 Vac
2.Display : LCD digital display
3.Output rating : 6A(3A)/250Vac, 60/50Hz.
4.Circuitry consumption : 7 VA
5.System switch : Heat-Off-Cool
6.Fan Auto/On selector switch

Auto: Fan turned on or off subject to setpoint.

On : Fan continuous on.

7.Fan speed selector : 3-speed High/Med./Low.
8..Shortest cycle rate protection : 3 minutes.
9.Temperature indication :

Celsius /Fahrenheit selectable to users

10.Temperature control rage : 5 ~ 35°C (40 ~ 113°F)
11.Temperature display range : -10 ~ 50°C (14 ~ 122 F).
12.Temperature adjustment scale : 0.5°C (1.0°F).
13.Comfort

setpoint adjustment range:

°

°

°

°

°

°

°

5 ~ 35°C (40 ~ 113°F), Default 24 C-Cool / 21 C-Heat

14.Economy

setpoint adjustment range:

5 ~ 35°C (40 ~ 113°F),Default 27°C-Cool /16°C-Heat

15.Switching differential (Hysteresis) :

Selectable to users (Default 0.4 ° C / 0.8 °F)
0.2/0.4/.06/.08/1.0

C ~~~ 0.4/0.8/1.2/1.6/2.0 F

16. Antifreeze protection: 5.0 C° constant

effects only when thermostat is OFF
by Stand-by. Also it effects in Heating only.

17.EEPROM for preserving internal setting in outage.
18.Temperature sensor : NTC 10K Ohm at 25 C.
19.Remote temperature sensor : Available.
20.Material : Non flammable plastics.
21.Colour : Standard white or RAL 9010
22.Storage temperature : -10 ~ 60 C.
23.Dimension :

( m/m)

Wiring backplate is provided for installation.

8

BACK-PLATE

THERMOSTAT

Be certain the voltage
system you plan to
connect this thermostat to,
is consistent with the
switching power
you have chosen.

The thermostat should situated in the room where the
heating/cooling is to be controlled.

The place of installation should be chosen so that the
sensors can capture the room temperature as
accurately as possible, without being affected
by direct solar radiation or other heating or cooling
source.

The mounting height should be approximate 1.5
meters above the floor. The unit can be fitted
directly on the wall.

To open thermostat for installation

72.3

OFF

Отзывы: