The TH-0023 digital thermostat provides precise
control for variety of 2 and 4 pipes fan coil system,
unit ventilators, dampers and other apparatus used in
commercial or residential applications.
This series features large LCD display, showing
temperature reading/setpoint, and variety of
configuration to meet application demands.
TH-0023 Fancoil Thermostat
Features
■Digital temperature display.
■Non-programmable,simple to wire,
easy temperature set-up.
■selectable continuous and cycling
fan switch.
■3-minute shortest cycle rate protection
for protecting compressor from too frquent
turned on-/Off, to avoid energy waste.
■Easy one touch button to set Comfort
& Economy
setpoint
■ High output contact rating with circuitry surge
absorber.
■Stand-by
function included for simple shut-off
Coo\Heat system when temperature regulation
is not required.
Choose correct location for thermostat
DANGER
Electric Shock Or Fire Hazard
Read all wire sizing, voltage requirement
and safety Data avoid property damage and
personal injury
Remove front cover using a
screw to press the cover
latch at top of front cover
Disconnect the main
before installation
Remove cover by holding
base and front cover.
Use screwdriver to remove
terminal protection cover
Mount base with wires
through the holes of the base
than mount the base with
screws(supplied) on the wall.
Install the wires into terminal
blocks, and mount back
terminal block.
Before wiring, you must check your system wiring
diagram. If your system differs from standard
wiring, please check with your local dealer
or consult with professional electrician.
Technical Data
1.Power supply : Switching power 24 Vac / 240 Vac
2.Display : LCD digital display
3.Output rating : 6A(3A)/250Vac, 60/50Hz.
4.Circuitry consumption : 7 VA
5.System switch : Heat-Off-Cool
6.Fan Auto/On selector switch
Auto: Fan turned on or off subject to setpoint.
On : Fan continuous on.
7.Fan speed selector : 3-speed High/Med./Low.
8..Shortest cycle rate protection : 3 minutes.
9.Temperature indication :
Celsius /Fahrenheit selectable to users
10.Temperature control rage : 5 ~ 35°C (40 ~ 113°F)
11.Temperature display range : -10 ~ 50°C (14 ~ 122 F).
12.Temperature adjustment scale : 0.5°C (1.0°F).
13.Comfort
setpoint adjustment range:
°
°
°
°
°
°
°
5 ~ 35°C (40 ~ 113°F), Default 24 C-Cool / 21 C-Heat
14.Economy
setpoint adjustment range:
5 ~ 35°C (40 ~ 113°F),Default 27°C-Cool /16°C-Heat
15.Switching differential (Hysteresis) :
Selectable to users (Default 0.4 ° C / 0.8 °F)
0.2/0.4/.06/.08/1.0
C ~~~ 0.4/0.8/1.2/1.6/2.0 F
16. Antifreeze protection: 5.0 C° constant
effects only when thermostat is OFF
by Stand-by. Also it effects in Heating only.
17.EEPROM for preserving internal setting in outage.
18.Temperature sensor : NTC 10K Ohm at 25 C.
19.Remote temperature sensor : Available.
20.Material : Non flammable plastics.
21.Colour : Standard white or RAL 9010
22.Storage temperature : -10 ~ 60 C.
23.Dimension :
( m/m)
Wiring backplate is provided for installation.
8
BACK-PLATE
THERMOSTAT
Be certain the voltage
system you plan to
connect this thermostat to,
is consistent with the
switching power
you have chosen.
The thermostat should situated in the room where the
heating/cooling is to be controlled.
The place of installation should be chosen so that the
sensors can capture the room temperature as
accurately as possible, without being affected
by direct solar radiation or other heating or cooling
source.
The mounting height should be approximate 1.5
meters above the floor. The unit can be fitted
directly on the wall.
To open thermostat for installation
72.3
OFF