STEP #4
Configure jumpers JMP501 and JMP502 on the bottom board for 115 or 230 VAC Power Input.
JMP502
JMP501
STEP #2
Configure jumpers JMP504 and JMP505 on the top board for the appropriate signal input.
JMP504
1 2 3
1 2 3
JMP505
1 2 3
JMP505
JMP504 (on top board)
Pins 1 & 2 for Voltage Input, or using a speed pot.
Pins 2 & 3 for Current Input
JMP505 (on top board)
Pins in Column 1 for 0 - 5 VDC Voltage Input,
or using a speed pot
Pins in Column 2 for 0 - 10 VDC Voltage Input
Pins in Column 3 for 4 - 20 mA Current Input
example:
STEP #3
Configure jumpers JMP503 on the bottom board and JMP506 on the top board.
JMP503
JMP503 (on bottom board)
Pins 1 & 2 to Trip
Pins 2 & 3 to Restart
TRIP: Drive has a low voltage fault & must
be manually re-enabled to restart.
RESTART: Drive has a low voltage fault &
will momentarily stop then auto-restart
when input voltage returns to minimum level.
UV TRIP
RESTART
1
2
3
JMP506
JMP506 (on top board)
Pins 1 & 2 to Brake
Pins 2 & 3 to Coast
BRAKE
COAST
1
2
3
C O N N E C T I O N S
STEP #5
Connect motor leads of a 3-
phase motor to U, V, and W
(TB502 on BOTTOM board)
using 14 - 16 AWG wire as
shown in the figure below.
STEP #6
Connect 115 or 230 VAC power
input using 12 AWG wire.
NOTE: Minarik strongly
recommends installing an
emergency stop switch on both
the L1 and L2 inputs.
STEP #1-skip this step if provided FWD/OFF/REV and speed potentiometer will be used.
Otherwise disconnect factory-wired connections from the FWD/OFF/REV switch and speed
potentiometer.
Connect the enable/disable switch, direction switch, and speed potentiometer or
signal input to TB501 on the TOP board using 20 - 24 AWG wire as shown below.
DIRECTION
SWITCH
ENABLE/DISABLE
SWITCH
(open to disable)
NOTE:
The factory-wired speed
potentiometer on the
case cover must be
disconnected prior to
wiring to a signal input
TO SPEED POT
OR SIGNAL INPUT
Copyright 2003 by Minarik Corporation - All rights reserved. No part of this document may be reproduced or transmitted in any form without
written permission from Minarik Corporation. The information and technical data in this document are subject to change without notice.
Minarik Corporation and its Divisions make no warranty of any kind with respect to this material, including, but not limited to, the implied
warranties of its merchantability and fitness for a given purpose. Minarik Corproation and its Divisions assume no responsibility for any errors
that may appear in this document and make no commitment to update or to keep current the information in this document. mvd092503
M I N A R I K D R I V E S
w w w . m i n a r i k d r i v e s . c o m
14300 De La Tour Drive, South Beloit, IL 61080; Phone: (800) MINARIK (646-2745); Fax: (815) 624-6960
Document Number: 250-0379, Revision 0; Printed in the U.S.A. - September 2003