Open Chassis Microprocessor-based
Variable Frequency AC Drive
UPVFD04-D230AC
14300 De La Tour Drive
South Beloit, IL 61080
Phone: (800) 646-2745
Fax: (800) 394-6334
www.minarikdrives.com
Specifications
......................................................115/230 VAC ± 10%, 50/60 Hz, single phase
......... approx. 2x motor current
......... approx. 4x motor current
..........approx. 2x motor current
...........................................................115/230 VAC, 50/60 Hz, single or three phase
...............................................................................200% (2x) for 1 minute
.............................................................................................16 kHz
............................................................................................0 - 120 Hz
.....................................................30 - 120 Hz
.......................................0 - 50% of maximum
................................................................................0 - 35 VDC
.....................................................................................1 - 12 seconds
.....................................................................................1 - 12 seconds
................................................0 - 5 VDC
....................................................................................>100K ohms
............................................................................................0.5G maximum
..............................................................................................0.1G maximum
.....................................................................................0°C - 40°C
..............................................................................................................................1.4 lbs
AC Line Voltage
AC Line Current
with 115 VAC line voltage with a 115V motor
AC Line Current
with 115 VAC line voltage with a 230V motor
AC Line Current
with 230 VAC line voltage with a 230V motor
AC Motor Voltage
Overload Capability
Standard Carrier Frequency
Output Frequency Range
Adjustable Maximum Output Frequency Range
Adjustable Minimum Output Frequency Range
Adjustable DC Injection Voltage
Acceleration Time Range
Deceleration Time Range
Analog Input Voltage Range
(Signal must be isolated)
Input Impedance (S1 to S2)
Vibration
(0 - 50 Hz)
(>50 Hz)
Ambient Temperature Range
Weight
1/8 - 1/2
1/4 - 1
1/4 - 1
Motor
Horsepower
Range
4.0
Continuous
Motor Current
(Amps)
115
230
230
Motor
Voltage
(VAC)
Line
Voltage
(VAC)
UPVFD04-D230AC
Model
115
115
230
Safety Warnings
READ ALL SAFETY WARNINGS BEFORE INSTALLING THIS EQUIPMENT
•
DO NOT INSTALL, REMOVE, OR REWIRE THIS EQUIPMENT WITH POWER APPLIED.
Have a
•
qualified electrical technician install, adjust and service this equipment. Follow the National
•
Electrical Code and all other applicable electrical and safety codes, including the provisions of the
•
Occupational Safety and Health Act (OSHA), when installed equipment.
•
Circuit potentials are at 115 or 230 VAC above earth ground
. Avoid direct contact with the printed
•
circuit board or with circuit elements to prevent the risk of serious injury or fatality. Use a
•
non-metallic screwdriver for adjusting the calibration trim pots. Use approved personal protection
•
equipment and insulated tools if working on this drive with power applied.
• Reduce the chance of an electrical fire, shock, or explosion by proper grounding, over-current
•
protection, thermal protection, and enclosure. Follow sound maintenance procedures.
•
Minarik Drives strongly recommends the installation of a master power switch in the line voltage
•
input.
The switch contacts should be rated for 250 VAC and 200% of motor nameplate current.
•
Removing AC line power is the only acceptable method for emergency stopping.
Do not use
•
DC injection braking, decelerating to minimum speed, or coasting to a stop for emergency stopping.
•
They may not stop a drive that is malfunctioning. Removing AC line power is the only acceptable
•
method for emergency stopping.
• Line starting and stopping (applying and removing AC line voltage) is recommended for infrequent
•
starting and stopping of a drive only. DC injection braking, decelerating to minimum speed, or
•
coasting to a stop is recommended for frequent starts and stops. Frequent starting and stopping can
•
produce high torque. This may cause damage to motors.
•
Do not disconnect any of the motor leads from the drive
unless power is removed or the drive is
•
disabled. Opening any one lead while the drive is running may destroy the drive.
• Under no circumstances should power and logic level wires be bundled together.
• Be sure potentiometer tabs do no make contact with the potentiometer enclosure. Grounding the
•
input will cause damage to the drive.
• Caution should be taken when operating fan-cooled motors at low speeds because their fans may
•
may not move sufficient air to properly cool the motor. Minarik Drives recommends “inverter-duty”
•
motors when the speed range is beyond 10:1.
• Drive is designed to work with permanent split capacitor, shaded pole, and standard three phase
•
induction motors. In general, the drive can work with capacitor-start motors, but it is conditional
•
on the current pull when the capacitor is in effect and how long the application calls for a speed that
•
the capacitor will stay in the auxiliary winding. It is recommended to contact the motor manufacturer
•
to see if the motor can be ran with a VFD.
ALL DIMENSIONS IN INCH
E
S [MILLIMETER
S]
Dimensions
0 1
. 8
8
5
[ ]
0.700 [17.80]
4.41 [112]
3.71 [94.2]
6.90 [17.5]
DIR
S3
S2
S1
COM
EN
MAX
ACCEL
BOOST
MIN
TQ/LIM
1 2 3 4
ON
SLIP
COMP
SW501
TB501
U
V
W
MOTOR OUT
STATUS LEDS
3.45
[87.63]
N
L1
L2
DEC/BK
Installation
Mounting
• Drive components are sensitive to electrostatic discharge. Avoid direct contact with the circuit
•
board. Hold the drive by the chassis only.
• Protect the drive from dirt, moisture, and accidental contact.
• Provide sufficient room for access to the terminal block and calibration trim pots.
• Mount the drive away from heat sources. Operate the drive within the specified ambient operating
•
temperature range.
• Prevent loose connections by avoiding excessive vibration of the drive.
• Mount the drive with its board in either a horizontal or vertical plane. Four 0.20” (5 mm) wide slots
•
in the chassis accept #8 pan head screws.
• The heat sink should be earth grounded. Use a star washer beneath the head of at least one of the
•
mounting screws to penetrate the anodized heat sink surface and to reach bare metal.
Wiring
Use 18 - 24 AWG wire for logic wiring (COM, DIR, EN, S1, S2, S3).
Use 14 - 16 AWG wire for AC line (L1, L2, N) and motor (U, V, W) wiring.
Shielding Guidelines
As a general rule, Minarik Drives recommends shielding of all conductors. If it is not practical to shield
power conductors, Minarik Drives recommends shielding all logic-level leads. If shielding of logic-level
leads is not practical, the user should twist all logic leads with themselves to minimize induced noise.
Refer to the user’s manual for details on earth grounding shielded wires and filtering.
Fusing
Minarik Drives drives require an external line fuse for protection. Use fast acting fuses rated for 250
VAC or higher and 150% of the maximum line current. Fuse the HOT leg of the AC line when using 115
VAC or both legs when using a 230 VAC line.
Connections
Line Input
Connect the AC line power leads to terminals L1 and N if using 115 VAC line power or to L1 and L2 if using 230 VAC
line power. Minarik Drives recommends the use of a single-throw, double-pole master power switch. The switch
should be rated at a minimum of 250 VAC and 200% of motor current.
Motor
If using a three phase motor, connect the AC motor leads to terminals U, V, and W. If the motor does not
spin in the desired direction, power down the drive and swap any two of these connections. If using a single
phase motor, connect the AC motor leads to terminals U and V. Refer to the Operations section for
possible wiring setups.
Speed Potentiometer or Analog Input Signal
Use a 5K - 20K ohm, 1/4 W potentiometer for speed control. Connect the counter-clockwise end of the potentiometer
to S1, the wiper to S2, and the clockwise end to S3. If the potentiometer works inveresly of desired functionality,
(i.e. to increase motor speed, you must turn the potentiometer counterclockwise), power off the drive and swap
the S1 and S3 connections. The drive may also follow a 0-5 VDC analog signal that is isolated from earth ground. Connect
the signal common to terminal S1 and the signal input to terminal S2. To use a PWM signal, use adder card 200-0441.
Direction Switch
If a direction switch is desired, wire a switch to terminals COM and DIR. When the connection is open, the motor will
run in the forward direction. When the connection is closed, the motor will run in reverse. If no direction switch is
desired, leave this connection open.
Enable
Open the terminals COM and EN to coast the motor to minimum speed. Close terminals COM and EN to accelerate the
motor to set speed. If no enable switch is desired, jumper terminals COM and EN.
Do not use the enable for
emergency stopping.
POWER
LOGIC
115 VAC LINE
DIR
S3
S2
S1
COM
EN
TB501
DIRECTION SWITCH
ENABLE/ DISABLE SWITCH
(open to disable)
10K OHM SPEED
ADJUST POTENTIOMETER
MOTOR
U
V
W
STOP
SWITCH
FUSE
FUSE
STOP
SWITCH
FUSE
230 VAC LINE
OR
N
L1
L2