PL-550
IQ Radar 160/160 Ex
Page 55
Parameter Descriptions
P005
Units
Determines the units for programming and measurement.
Entry:
1 = metres
2 = centimetres
3 = millimetres
4 = feet
5 = inches
P006
Empty
Distance from flange face to empty level or
maximum target range.
P007
Span
Distance from empty (P006) to full/100% level
or minimum target range.
P050
Tank Shape
This parameter, in conjunction with parameters P051, P052 and P053, enable
the IQ 160/160 Ex to show readings based on reservoir volume (rather than
level).
Enter the Tank Shape value that matches the monitored vessel or reservoir.
When Operation is "level" (P001 = 1), liquid (material) volume is calculated.
In the
run mode, Readings are displayed in volumetric units, see Max Volume
(P051) on page 56. When percent is selected the displayed Reading is the
calculated volume as a percentage of Max Volume.
Entry:
0 = disabled (Factory)
1 = flat bottom
2 = conical or pyramidal
bottom
Содержание IQ Radar 160
Страница 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Страница 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Страница 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Страница 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Страница 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Страница 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Страница 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Страница 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Страница 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Страница 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...
Страница 80: ...Page 80 IQ Radar 160 160 Ex PL 550 Index ...