PL-550
IQ Radar 160/160 Ex
Page 51
Operation
This mounting arrangement can also be used to provide optimum signal
conditions on foaming materials.
Suitable pipe diameters are 50 mm (2”) to 250 mm (10”).
Note:
The measurement range is reduced to 13 m (43’) for a 50 mm (2”)
still pipe or 14.5 m (47’) for an 80 mm (3”) still pipe.
Reset:
P999
master reset
Program:
P001
enter ‘1’
mode of measurement
= level
P002
enter ‘1’
material
= liquid
P003
enter ‘2’
measurement response
= 1m/min.
P004
enter ‘240’
antenna
= dielectric rod,
standard length
P005
enter ‘1’
units
= metres
P006
enter ‘5’
empty distance
= 9.6 m
P007
enter ‘4.5’
span
= 8.5 m
P655
enter ‘0.955
propagation factor
= 100 mm (4”) pipe
P820
enter ‘6’
algorithm
= first echo
P830
enter ‘4’
TVT type
= factory
Run:
Press run to start normal operation. Press
.
Pipe
P655 Value
50 mm (2”)
0.827
80 mm (3”)
0.915
100 mm (4”)
0.955
150 mm (6”)
0.980
200 mm (8”)
0.990
Note:
See the P655 table on page 58 for other pipe diameters.
Содержание IQ Radar 160
Страница 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Страница 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Страница 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Страница 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Страница 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Страница 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Страница 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Страница 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Страница 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Страница 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...
Страница 80: ...Page 80 IQ Radar 160 160 Ex PL 550 Index ...