PL-550
IQ Radar 160/160 Ex
Page 49
Operation
Reset:
P999
master reset
Program:
P001
enter ‘1’
mode of measurement
= level
P002
enter ‘1’
material
= liquid
P003
enter ‘2’
measurement response
= 1m/min.
P004
enter ‘240’
antenna
= dielectric rod,
standard length
P005
enter ‘1’
units
= metres
P006
enter ‘5’
empty distance
= 5 m
P007
enter ‘4.5’
span
= 4.5 m
P070
enter ‘2’
fail-safe timer
= 2 min.
P071
enter ‘1’
fail-safe
= Hi
P652
enter tag value
offset correction
= factory
P820
enter ‘1’
algorithm
= factory
P830
enter ‘4’
TVT type
= factory
Run:
Press run to start normal operation. Press
.
Application Example: Sliding Waveguide on
Anaerobic Digesters
Blanking, P800 and offset P652 are set at the factory. Check the device tag
for specific values.
Maximum level should be maintained at
least .46 m (18”) from the end of the horn.
The raised position is for installation and
maintenance. The lowered position is for
operation. Program the unit for operation
in the lowered position.
P006
P007
horn
Содержание IQ Radar 160
Страница 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Страница 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Страница 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Страница 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Страница 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Страница 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Страница 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Страница 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Страница 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Страница 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...
Страница 80: ...Page 80 IQ Radar 160 160 Ex PL 550 Index ...