PL-550
IQ Radar 160/160 Ex
Page 43
Operation
In applications where the zero level is above the bottom of the vessel and it is
desired to monitor the zone below the normal zero, range extension (P801)
can be used to extend the range into the far end blanking. Range extension is
entered as a percentage of P006. As range extension reduces the protection
afforded by the far end blanking, it should be used judiciously. Avoid
excessive range extension as this can reduce the measurement’s reliability
and accuracy. Range extension is factory set for 5% of P006. If it is found that
false echoes are appearing, after the blanking zone, P801 should be
increased accordingly.
Analog Output
The IQ Radar 160/160 Ex can be programmed to provide an analog output
(P200) of 0 to 20 or 4 to 20 mA, and for proportional or inverse span.
Programming
Upon entering the Program mode, the analog output level holds its prior
value.
Содержание IQ Radar 160
Страница 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Страница 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Страница 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Страница 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Страница 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Страница 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Страница 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Страница 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Страница 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Страница 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...
Страница 80: ...Page 80 IQ Radar 160 160 Ex PL 550 Index ...