PL-550
IQ Radar 160/160 Ex
Page 31
Installation
IQ Radar 160 Wiring
AC version
DC version
IQ Radar 160 Ex Wiring
AC version
DC version
Notes for AC version only:
•
Line,
12
– 14 AWG, copper wire
•
The equipment must be protected by a 15 A fuse or circuit breaker in
the building installation.
•
A circuit breaker or switch in the building installation, marked as the
disconnect switch, shall be in close proximity to the equipment and
within easy reach of the operator.
All field wiring must have insulation suitable for at least 250 V.
Note for DC version only:
DC terminals shall be supplied from an SELV source in
accordance with IEC 1010.1 Annex H.
4-20 mA,
to instrumentation
RS-485,
to host device
V supply,
see nameplate
4-20 mA,
to instrumentation
RS-485,
to host device
enclosure
to reliable
earth ground
V supply,
see nameplate
Содержание IQ Radar 160
Страница 1: ...33455500 Rev 3 1 IQ RADAR 160 Instruction Manual PL 550 January 2001 Q RADAR I60 ...
Страница 10: ...Page 10 IQ Radar 160 160 Ex PL 550 Specifications ...
Страница 32: ...Page 32 IQ Radar 160 160 Ex PL 550 Installation ...
Страница 35: ...PL 550 IQ Radar 160 160 Ex Page 35 Start Up Display Aiming the Hand Programmer ...
Страница 40: ...Page 40 IQ Radar 160 160 Ex PL 550 Start Up ...
Страница 52: ...Page 52 IQ Radar 160 160 Ex PL 550 Operation ...
Страница 62: ...Page 62 IQ Radar 160 160 Ex PL 550 Parameter Descriptions ...
Страница 66: ...Page 66 IQ Radar 160 160 Ex PL 550 Appendix I ...
Страница 68: ...Page 68 IQ Radar 160 160 Ex PL 550 Appendix II ...
Страница 74: ...Page 74 IQ Radar 160 160 Ex PL 550 Appendix III ...
Страница 80: ...Page 80 IQ Radar 160 160 Ex PL 550 Index ...