PL-601
EnviroRanger Installation Guide
Page 25
Wi
ri
n
g
Cables
The EnviroRanger uses a transceiver that requires a shielded two-wire
connection to the transducer.
Connection
Cable Type
mA input
sync
temperature sensor
discrete input
dc input
Transducer
2-3 copper conductors, twisted, with foil shield, drain wire, 300V
0.5-0.75 mm
2
(22 - 18 AWG)
Do not use a coaxial transducer cable extension with the
EnviroRanger because of electrical noise.
Relay output
ac input
Relay to be copper conductors per local requirements to meet
250V 5A contact rating.
Transducers
Warning:
Hazardous voltage present on transducer terminals during
operation.
Run the transducer cable in a grounded metal conduit, separate from other
wiring, (except TS-3 temperature sensor wiring, if applicable).
Notes:
•
Do not use coaxial cable because of electrical noise.
•
Do not connect the shield and white transducer wires.
•
Older transducer manuals will recommend these practices. Disregard
that information.
Rack or Panel Mount
Wall Mount
transducer
2
transducer
1
transducer
2
transducer
1
black
white
shield
shield
white
black
black
white
shields
white.
black.