Relay Parameters (P100 to P104, P110 to P113, P129)
If relays are to be used, alter the following parameters as required. Otherwise, proceed to
mA Output Parameters.
Relays may be programmed as Standard Alarms or for Custom Relay operation.
For Standard Alarms (relays operate based on material level), select the Relay Set Up
(P100) desired and alter the Standard Alarm (P101 to P104) parameters as required,
before proceeding to Relay Failsafe (P129).
For Custom Relay operation, select the Relay Set Up (P100) which most closely matches
your requirements, and alter the Custom Relay Parameters (P110 to P113) as required,
before proceeding to Relay Failsafe.
P100 (G) RELAY SET UP
T
his parameter presets relays to operate as Standard Alarms. The Relay
Allocation (relay / point number association) and Standard Alarm (P101 to
P104) parameters are also preset.
SET UP
SAM-20 #
RELAY #
POINT #
STANDARD ALARM (as %
of Span, P007)
1
1
1 -10
1 - 10
(Hi Alarm) P101 = 80.00%
1
11 - 20
1 - 10
(Lo Alarm) P102 = 20.00%
2
1 -10
1 - 10
(Hi Hi Alarm) P103 = 90.00%
2
11 - 20
1 - 10
(Lo Lo Alarm) P104 = 10.00%
2
1
1 - 10
1 - 10
(Hi Alarm) P101 = 80.00%
1
11 - 20
1 - 10
(Hi Hi Alarm) P103 = 90.00%
2
1 - 10
1 - 10
(Lo Alarm) P102 = 20.00%
2
1 - 20
1 - 10
(Lo Lo Alarm) P104 = 10.00%
3
1
1 - 5
1 - 5
(Hi Alarm) P101 = 80.00%
1
6 - 10
1 - 5
(Lo Alarm) P102 = 20.00%
1
11 - 15
1 - 5
(Hi Hi Alarm) P103 = 90.00%
1
16 - 20
1 - 5
(Lo Lo Alarm) P104 = 10.00%
2
1 - 5
6 - 10
(Hi Alarm) P101 = 80.00%
2
6 - 10
6 - 10
(Lo Alarm) P102 = 20.00%
2
11 - 15
6 - 10
(Hi Hi Alarm) P103 = 90.00%
2
16 - 20
6 - 10
(Lo Lo Alarm) P104 = 10.00%
Relay status during a measurement difficulty is dependent upon Failsafe
programming. (See Failsafe Parameters (P070 to P072) and Relay Failsafe (P129).
As preset, relay status is "held" at last known material levels until a valid
measurement is made.
Independently altered Standard Alarms (P101 to P104), Relay Allocation (P110),
Relay Function (P111) and Relay A / B Setpoints (P112/P113) are automatically
reset when a Relay Set Up value is altered.
values: 1 = Set Up 1
2 = Set Up 2
3 = Set Up 3
Содержание airanger XPL plus
Страница 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Страница 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 113: ......