Page 28
AiRanger XPL Plus – INSTRUCTION MANUAL
7ML19981AN02
mmmm
m
Applicat
ion P
a
ra
met
e
rs
* Steps to enter a Level Breakpoint or Breakpoint Volume:
1.. Press
to display the index symbol,
.
2. Scroll (
or
) or direct access the desired Breakpoint.
3. Key in the desired level or volume value.
4. Press .
Refer to
Technical Reference
Volume Calculation for breakpoint value selection.
P051
MAX VOLUME
Use this feature to display the Reading in volumetric units rather than percent.
Enter the vessel volume between Empty (P006) and Span (P007).
e.g. 1
If the volume = 3650 m
3
, enter 3650.
e.g. 2
If the volume = 267,500 U.S. gallons, enter 267.5 (1000’s of gallons).
values: 0.000 to 9999
P052
TANK DIMENSION A
Enter the height of the tank bottom if P050 = 2,3,4, or 5, or the length of one end
section of the tank if P050 = 7, in Units (P005).
values: 0.000 to 9999
P053
TANK DIMENSION L
Enter the length of the tank (excluding both end sections) if P050 = 7, in Units
(P005).
values: 0.000 to 9999
P054
LEVEL BREAKPOINTS ( Universal Volume Calculation )
Enter level breakpoints* (where volume is known) if P050 = 9 or 10
values: 0.000 to 9999
P055
BREAKPOINT VOLUMES ( Universal Volume Calculation )
Enter the volume* corresponding to each Level Breakpoint entered.
values: 0.000 to 9999
Содержание airanger XPL plus
Страница 1: ...Instruction Manual March 2005 XPL PLUS airanger ...
Страница 10: ...Page 6 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 26: ...Page 22 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 82: ...Page 78 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 106: ...Page 102 AiRanger XPL Plus INSTRUCTION MANUAL 7ML19981AN02 ...
Страница 113: ......