OM-223 Page 15
2-5. Weld Output Terminals And Selecting Cable Sizes
Y
ARC WELDING can cause Electromagnetic Interference.
To reduce possible interference, keep weld cables as short as possible, close together, and down low, such as on the floor.
Locate welding operation 100 meters from any sensitive electronic equipment. Be sure this welding machine is installed
and grounded according to this manual. If interference still occurs, the user must take extra measures such as moving
the welding machine, using shielded cables, using line filters, or shielding the work area.
Total Cable (Copper) Length In Weld Circuit Not Exceeding
100 ft (30 m) Or Less
150 ft
(45 m)
200 ft
(60 m)
250 ft
(70 m)
300 ft
(90 m)
350 ft
(105 m)
400 ft
(120 m)
Turn Off power before
connecting to weld
output terminals.
Welding
Amperes
10
−
60%
Duty
Cycle
60
−
100%
Duty
Cycle
10
−
100% Duty Cycle
100
4
4
4
3
2
1
1/0
1/0
150
3
3
2
1
1/0
2/0
3/0
3/0
200
3
2
1
1/0
2/0
3/0
4/0
4/0
250
2
1
1/0
2/0
3/0
4/0
2-2/0
2-2/0
300
1
1/0
2/0
3/0
4/0
2-2/0
2-3/0
2-3/0
350
1/0
2/0
3/0
4/0
2-2/0
2-3/0
2-3/0
2-4/0
400
1/0
2/0
3/0
4/0
2-2/0
2-3/0
2-4/0
2-4/0
Negative
Positive
Hi h
500
2/0
3/0
4/0
2-2/0
2-3/0
2-4/0
3-3/0
3-3/0
High
Inductance
Positive
600
3/0
4/0
2-2/0
2-3/0
2-4/0
3-3/0
3-4/0
3-4/0
Inductance
Positive
Low
Inductance
700
4/0
2-2/0
2-3/0
2-4/0
3-3/0
3-4/0
3-4/0
4-4/0
Inductance
800
4/0
2-2/0
2-3/0
2-4/0
3-4/0
3-4/0
4-4/0
4-4/0
Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
S-0007-D
2-6. Electrical Service Guide
60 Hertz Models
300 Amp Model
450 Amp Model
650 Amp Model
Input Voltage
230
460
575
200
230
460
575
230
460
575
Input Amperes At Rated Output
42
21
17
72
63
32
25
96
48
38
Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes
60
30
25
110
90
45
40
150
70
60
Min Input Conductor Size In AWG/Kcmil
8
10
12
4
6
8
10
3
8
8
Max Recommended Input Conductor
Length In Feet (Meters)
128
(39)
340
(104)
324
(99)
141
(43)
123
(37)
317
(97)
328
(100)
144
(44)
198
(60)
309
(94)
Min Grounding Conductor Size In AWG/
Kcmil
10
10
12
6
8
10
10
6
8
10
Reference: 1993 National Electrical Code (NEC)
S-0092-J
50 Hertz Models
300 Amp Model
450 Amp Model
650 Amp Model
Input Voltage
380
400
440
380
400
440
380
400
440
Input Amperes At Rated Output
27
25
23
39
37
33
58
54
50
Max Recommended Standard Fuse Or
Circuit Breaker Rating In Amperes
40
35
35
60
50
50
90
80
80
Min Input Conductor Size In AWG/Kcmil
10
10
10
8
8
8
6
6
6
Max Recommended Input Conductor
Length In Feet (Meters)
232
(71)
257
(78)
311
(95)
216
(66)
240
(73)
290
(88)
210
(64)
233
(71)
282
(86)
Min Grounding Conductor Size In AWG/
Kcmil
10
10
10
10
10
10
8
8
8
Reference: 1993 National Electrical Code (NEC)
S-0092-J