Controller setup

Controller setup

To get into the SETUP menu, press and hold down the

key and then press the

key. After

entering the access code you can change the controller parameters.

CONTROLLER SETUP

No.

Description

Default

value

Range

MODBUS network address

Baud rate

0 – 9600 ,1 – 19200, 2 – 38400,3 – 57600,4 – 115200

Channel 1 measuring input type

0 – PT-500,

1 – PT-100,

2 – PT1000,

3 – 0..20 mA*,

4 – 4..20 mA*

5 – thermocouple s**, 6 – thermocouple b**,

7 – thermocouple r**,

8 – thermocouple t**

9 – thermocouple j**, 10 – thermocouple e**, 11 – thermocouple k**, 12 – thermocouple n**

*

current input version, ** thermocouple operation version

SF3

1

0..12

Measuring input type for channel 2

SF2

1

0..12

SF1

0

0..4

SF0

1

0..128

SF4

1

0..12

Measuring input type for channel 3

SF5

0

-99,0 .. 999 C

Value corresponding to 0 mA for channel 1 0..20 mA input

°

°

C

SF6

200

-99,0 .. 999 C

Value corresponding to 20 mA

1 0..20 mA input

for channel

°

°

C

SF7

0

-99,0 .. 999 C

Value corresponding to 0 mA

2 0..20 mA input

for channel

°

°

C

SF8

200

-99,0 .. 999 C

Value corresponding to 20 mA

2 0..20 mA input

for channel

°

°

C

SF9

0

-99,0 .. 999 C

Value corresponding to 0 mA

3 0..20 mA input

for channel

°

°

C

SF10

200

-99,0 .. 999 C

Value corresponding to 20 mA

3 0..20 mA input

for channel

°

°

C

SF11

0

-99,0 .. 999 C

Value corresponding to 4 mA

1 4..20 mA input

for channel

°

°

C

SF12

200

-99,0 .. 999 C

Value corresponding to 20 mA

1 4..20 mA input

for channel

°

°

C

SF13

0

-99,0 .. 999 C

Value corresponding to 4 mA

2 4..20 mA input

for channel

°

°

C

SF14

200

-99,0 .. 999 C

Value corresponding to 20 mA

2 4..20 mA input

for channel

°

°

C

SF15

0

-99,0 .. 999 C

Value corresponding to 4 mA

3 4..20 mA input

for channel

°

°

C

SF16

200

-99,0 .. 999 C

Value corresponding to 20 mA

3 4..20 mA input

for channel

°

°

C

SF17

0,0

-20,0 .. 20,0 C

Temperature readout adjustment for channel 1

SF18

0,0

-20,0 .. 20,0 C

Temperature readout adjustment for channel 2

SF19

0,0

-20,0 .. 20,0 C

Temperature readout adjustment for channel 3

SF20

On

On / Off

Regulator operation in channel 1

OFF- always

ON- only in the START mode

SF21

On

On / Off

as above for channel 2

SF22

On

On / Off

as above for channel 3

SF23

-99

-99..400 C

Minimum allowable setpoint for channel 1

SF24

150

-99..400 C

Maximum allowable setpoint for channel 1

SF25

-99

-99..400 C

Minimum allowable setpoint for channel 2

SF26

150

400

Maximum allowable setpoint for channel 2

SF27

-

-

-

SF28

-

-

-

SF29

0

0..3

Regulator type for channel 1

0 – normal hysteresis

1 – reversed hysteresis

2 – normal hysteresis, ”setpoint ramping” algorithm

3 –PID regulator

SF30

0

0..3

Regulator type for channel 2

SF31

0

0..3

Regulator type for channel 3

°

°

°

°

°

°

°

°

°

°

°

°

°

°

C

C

C

C

C

C

C

C

SF32

1,0 C

0,0 .. 5,0 C

Low hysteresis for channel 1

SF33

1,0 C

0,0 .. 5,0 C

Low hysteresis for channel 2

SF34

1,0 C

0,0 .. 5,0 C

Low hysteresis for channel 3

SF35

1,0 C

0,0 .. 5,0 C

High hysteresis for channel 1

SF36

1,0 C

0,0 .. 5,0 C

High hysteresis for channel 2

SF37

1,0 C

0,0 .. 5,0 C

High hysteresis for channel 3

SF38

120 C

-99..999 C

Channel 3 temperature setpoint

SF39

20 C

0..200 C

Regulator activation temperature (Tza) for channel 1

For “setpoint ramping” algorithm

SF40

20 C

0..200 C

SF41

20 C

0..200 C

SF42

1

0..100 sek

Regulator activation delay [seconds] for channel 1

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

Regulator activation temperature (Tza) for channel 2

For “setpoint ramping” algorithm

Regulator activation temperature (Tza) for channel 3

For “setpoint ramping” algorithm

R

R

-

EDIT

16

17

No.

Description

Default

value

Range

Indu-50 version: 1.4

Indu-50 version: 1.4

Содержание INDU-50

Страница 1: ...the MIKSTER SERVICE S C Company serial no sale date MIKSTER R INDUSTRIAL MICROPROCESSOR CONTROLLER INDU 50 Logginet User s Manual INDUSTRIAL TECHNOLOGY R v 1 4 Industrial Microprocessor Controller IND...

Страница 2: ...evices as governors digital recorders indicators Microprocessor controller INDU 50 cooperaters with computer software with INDU monitor and Loggisoft from version 2 12 or higher Versions of software a...

Страница 3: ...B A 29 30 RS 485 PC ALARM 1 ALARM 2 Microprocessor Controller INDU 50 serial no R www mikster com 65mm 80mm 134mm 134mm Power supply 230 V option 24 V 90 mm 90 mm rack mount opening R R Silicon washe...

Страница 4: ...lines on the left side of displayed measured value indicate regulator status diode on signals that an output is programmed Key LEDS indicates the current operating mode The following modes can be indi...

Страница 5: ...el 3 measurement Ad 3 Measurement on Channel 2 when the pasterisation number is being counted channel 1 and channel 2 temperature setpoints current date current time To get the next previous informati...

Страница 6: ...ring element missing or damaged in channel 3 Err 4 MAX temperature exceeded in channel 1 To get into the user s setting press and hold down the key and then press and hold down the key The functions m...

Страница 7: ...Setting of the adequate integration time which means the time between consecutive moments of counting pasterisation number setup cell SF79 was also taken into account in INDU50 controller The possibil...

Страница 8: ...ed parameter is done on the middle display pulsating value Increase of parameter Value by the key decrease by the key Shift to the next parameter and confirmation of changes by the key Exit from editi...

Страница 9: ...for channel C SF16 200 99 0 999 C Value corresponding to 20 mA 3 4 20 mAinput for channel C SF17 0 0 20 0 20 0 C Temperature readout adjustment for channel 1 SF18 0 0 20 0 20 0 C Temperature readout a...

Страница 10: ...T mode only 0 continuous recording SF47 HMd HMd HM AUTOSTART mode parameter format HMD hour minute and daily delay for START HM hours and minutes to START SF48 5 0 10 godz Maximum time period after wh...

Страница 11: ...2 0 2 Number of the measuring channel versus which the regulation is carried on governor 3 0 measuring channel 1 1 measuring channel 2 2 measuring channel 3 SF85 0 50 0 100 C Shifting of the set temp...

Страница 12: ...set time is elapsed or temperature setpoint is exceeded bar SF45 6 Cycle ends after the preset time is elapsed or temperature setpoint is exceeded shell SF45 7 Cycle ends after the preset time is elap...

Страница 13: ...nputs PT 100 PT 500 PT 1000 temperature measuring range 24 25 LGTD R 01 wersja 1 3 Assuming full responsibility we declare that our product The person undersigned representing the below mentioned Prod...

Страница 14: ...anel mounnting Dual silicon gasket 50 65 Small depth Water proof Chemical proff Alcohol proff from the front IP 65 from the front the resistance to strong cleaning agents used in the food industry Fea...

Отзывы: